Cable Gland Assembly Instructions
151 RAC
A: Component Parts
B: Cable Preparation
Slide shroud (if included), backnut , middlenut  and armour clamp ring  onto cable.
Con rm orientation of armour clamp ring is correct (see table below).
Cut cable length, strip outer sheath and cut armour to lengths as shown in table below.
y
Strip Lengths
Gland Size
Dim
Os-C
C2-F
x
20mm
25mm
y
To suit equipment
Tape Armour
After tape is spread, ensure ends are
trimmed at 90° as shown
AI393 - Issue H / Page 1 of 4
1
Entry
x
G-J
32mm
x
3
2
Spigot
3
4
5
4
Middlenut
Armour Clamp Ring
Shroud
(If applicable)
Armour Clamp Ring Orientation
Orientation
Gland
Size
Equipment Side
Os-A
0.8 - 1.25mm
B
1.25 - 1.6mm
C-C2
1.6 - 2.0mm
D-F
1.8 - 2.5mm
G-H
2.0 - 3.5mm
J
2.5 - 4.0mm
5
Backnut
Equipment Side
0 - 0.8mm
0 - 0.7mm
0 - 0.7mm
0 - 1.0mm
0 - 1.0mm
0 - 1.0mm

Advertisement

loading

Summary of Contents for Hawke 151 RAC

  • Page 1 Cable Gland Assembly Instructions 151 RAC A: Component Parts Backnut Middlenut Armour Clamp Ring Spigot Entry B: Cable Preparation Slide shroud (if included), backnut , middlenut  and armour clamp ring  onto cable. Con rm orientation of armour clamp ring is correct (see table below).
  • Page 2 C: Installing Cable Gland STEP 1: Fit Armour To Spigot Slide spigot  over cable. Push armour/braid up to spigot shoulder. Slide clamping ring  up to the armour/braid by hand. STEP 2: Prepare to Clamp Armour/Braid Slide Entry  over cable. STEP 3: Clamp Armour/Braid Slide middlenut ...
  • Page 3 STEP 6: Install Backnut Tighten the backnut  until a seal is formed around the cable. Use a wrench/spanner to grip the middlenut . While preventing the middlenut  turning, use a second wrench to apply one further full turn to the backnut  . STEP 7: Inspect Backnut Use the middlenut ...
  • Page 4 ACCESSORIES 4. To maintain IP66, Hawke sealing washer or other approved sealing Hawke o er the following accessories to enable correct sealing and ground method must be used. of cable gland. 5. Sealing face surface must be smooth and free from damage 6.