Page 1
Cable Gland Assembly Instructions 151 RAC A: Component Parts Backnut Middlenut Armour Clamp Ring Spigot Entry B: Cable Preparation Slide shroud (if included), backnut , middlenut and armour clamp ring onto cable. Con rm orientation of armour clamp ring is correct (see table below).
Page 2
C: Installing Cable Gland STEP 1: Fit Armour To Spigot Slide spigot over cable. Push armour/braid up to spigot shoulder. Slide clamping ring up to the armour/braid by hand. STEP 2: Prepare to Clamp Armour/Braid Slide Entry over cable. STEP 3: Clamp Armour/Braid Slide middlenut ...
Page 3
STEP 6: Install Backnut Tighten the backnut until a seal is formed around the cable. Use a wrench/spanner to grip the middlenut . While preventing the middlenut turning, use a second wrench to apply one further full turn to the backnut . STEP 7: Inspect Backnut Use the middlenut ...
Page 4
ACCESSORIES 4. To maintain IP66, Hawke sealing washer or other approved sealing Hawke o er the following accessories to enable correct sealing and ground method must be used. of cable gland. 5. Sealing face surface must be smooth and free from damage 6.