Lithium Valley TeLiF-AiO 48100 EU/T User Manual

Energy storage all in one

Advertisement

Quick Links

Energy Storage All In One User Manual
v1.0-20230503

Advertisement

Table of Contents
loading

Summary of Contents for Lithium Valley TeLiF-AiO 48100 EU/T

  • Page 1 Energy Storage All In One User Manual v1.0-20230503...
  • Page 2: Table Of Contents

    Purpose 1.1 Electrical Safety 1.2 Environment Safety This document describes the TeLiF-AiO 48100 EU/T (also referred to as product, equipment, 1.3 Battery Safety system or energy storage) in terms of its overview, application scenarios, installation and commissioning, system maintenance, and technical specifications.
  • Page 3: Safety

    1. Safety ●Avoid direct contact with the power supply equipment or conductors using damp objects. Always measure the voltage at the contact point before touching any conductor surface or terminal to ensure there is no risk Before transporting, storing, installing, operating, using, and/or maintaining the equipment, read this of electric shock.
  • Page 4: Battery Safety

    ●Ensure that the installation surface is solid enough to support the weight of the equipment. General Requirements: ●Do not install or operate the equipment in harsh weather conditions such as lightning, rain, snow, ●Read and comply with the battery manufacturer's instructions for installation, operation, and maintenance. or strong winds.
  • Page 5: Product Introduction

    1.When PV, Grid, Battery are available: A. Solar energy provides power to the loads as first priority, if solar energy is sufficient to The TeLiF-AiO 48100 EU/T system is a combination of a three-phase grid-tied PV inverter and a Grid Inverter high-voltage direct current (HVDC) battery.
  • Page 6: Storage

    Work modes: Bat priority 2.4 Storage 1. When PV, grid, and battery are available: A. Solar energy will charge battery as first priority, if solar energy is excess, the excess power will supply load. If there is still some extra energy, then the excess power will be fed to the grid.
  • Page 7: Installation

    3. Installation 3.1 Check for Physical Damage 3.2 Packing List NOTICE...
  • Page 8 3.4 Installation step...
  • Page 9: Electrical Connection

    4. Electrical Connection DANGER ●Before connecting cables, ensure that the DC switch on the battery and all switches connected to the battery are turned OFF to avoid electric shocks. ●Take note of the polarities when installing batteries and avoid connecting the positive and negative poles together to prevent short circuits.
  • Page 10: Interface Definition

    4.2 Battery Connection 4.1 Interface definition Battery connection diagram: BM S Bat t e r y 4 Bat t e r y 3 Bat t e r y 2 Bat te r y 1 High voltage box + - + - + - + - Battery outpuput/input Note...
  • Page 11: Grid And Load Connection

    4.3 Grid and load connection Electrical connection diagram GRID M eter G rid s ide + - + - G R I D B A C K - U P 1 M a in B A C K - U P 2 CT/ M E T E R E X T E N D P V 1 P V 2...
  • Page 12: Communication Interface Definition

    4.5 Communication interface definition CT/ M E T E R E X T E N D P V 1 P V 2 + - + - C A N B M S B AT + B AT- The communication interface between the optical storage integrated machine and the instrument is an RS485 connector IGRID-AP IGRID-AN...
  • Page 13: System Operation Guide

    5. System Operation Guide 4.7 Inverter Manipulation 5.1 Control Panel Start inverter after checking all bel ow St ep s: Ensure the inverter fixed well on the wall. Make sure a ll the DC wiring and AC wiring are completed. Make sure the meter/CT is co nn ected we ll.
  • Page 14: Instructio Ns Fo R Led Indicato R

    7.2 Instructio ns fo r LED Indicato r 5.2 Instructions for LED Indicator 5.3 Instructions for the use of three modes 1. SELF CONSUME 2. PEAK SHIFT 1. WORK MODE Grid Grid Alarm Alarm Fault Fault 3. BAT PRIORITY Green Green (Ye llow) (Ye llow)
  • Page 15: Lcd Operation

    8. LCD Operation 5.4.5 PV1 I npu t display interface 5.4 LCD interface Interface Description INPUT 5.4.1 Error information PV1 input real - time voltage 8.1LCD Interface VOLT: 0.0V PV1 input real - time current Interface Description CURR: 0.00A PV1 input real - time power. POWER: Numbers represent error codes and text is error information.
  • Page 16 5.4.15 GRID POWER 5.4.10 Battery current interface Interface Description Interface Description The CT arrow points to the power grid. The discharge from the POWER PRMETER inverter to the grid is “+”, and the opposite is “- “. CHAR VOL: Battery BMS request Max. charging voltage GRID U : 0.0W CHAR VOL :...
  • Page 17: Setting

    5.5.4 System Setting 5.5 Setting 5.5.4.0 Interface Description 5.5.1 State SYS SETTING Interface Description 1: WORK MODE This interface is used to access system information. 2: EPS ENABLE USER SETUP: Press Enter to user settings interface. Press Up/Down button to move corresponding options. 3: BAT WAKE -UP 1:SETUP INQUIRE: Query inverter model, serial number, software version .
  • Page 18 5.5.4.7 i t n 5.5.4.2 EPS enable 40 / 61 40 / 61 Interface Description Description Interface 38 / 61 Anti Reverse EPS ENABLE Anti- Reverse: Whether Inverter isn’t allowed to generate 1.DISABLE When the Grid and PV are powered o , Enable the battery to 1:DISABLE electricity to the Grid.
  • Page 19 Interface Description 12:CUSTOM- User defined 13:POL 230V/380V/50HZ This interface is used to set the lithium battery charging BAT CHARGE CURRT 14:EN50549 217V/220V/240V 380V/400V current. (The input value ranges from 20-50A) 50HZ/60HZ INPUT: Charge current, as recommended by the battery manufacturer. 15:VDE4105 —Germany: 230V/380V/50Hz UNIT: A...
  • Page 20 5.5.7.6 VAC MAX Interface Descr iption The input value should range between - 60% and REACT POWER + 60 %, which varies with the standard. INPUT: +00% D VOLT HIGH The input value of Grid high voltage. INPUT: (T h is is v a lid o n ly if th e g rid s ta n d a rd s "c ustom) UN IT 5.5.7.
  • Page 21 5.5.11 BACKLIGHT 5.5.11.0 BACKL IG HT 8.2.8 485 Address 5.5.8 485 Address Interface Description 5.5.8.0 4 85 Address 8.2.8.0 485 Address LIGHT TIME Interface Descr ip tion Interface Description INPUT: This screen is used to set the screen light time. This interface is used to se lect 485 addre ss .
  • Page 22: Inquire

    5.5.15 MAINTENANCE 5.5.15.0 MAINTENANCE Interface Description 5.6.2 MODULE SN PASSWORD Reserved INPUT: XXXXX Interface Description S / N GUID: XXXXXXXX This interface show module SN. XXXXXXXXXXXXXX 5.5.16 F CTRY RE SET SN:FXXXXXXXXXXX 5.5.16.0 FACTO RY RESET 5.6.3 FIRMWARE Interface Description Interface Description FACTORY RESET...
  • Page 23: Statistic

    8.4 STA TISTIC 6. Smart APP 5.7 STATISTIC 6.1 Battery Deployment 5.7.0 STATISTIC Registration 8.4.0 STATISTIC Go to SOLARMAN Smart and register. Interface Descr ip tion Interface Description Click "Register" and create your account here. This interface show inverter operation statistic. STAT.
  • Page 24 8.4 STA TISTIC Step 1: Confirm Wi-Fi Info Add a Logger Please make sure your phone has connected to the right WiFi Method 1: Enter logger SN manually. network. And click "Start". 8.4.0 STATISTIC Method 2: Click the icon in the right and scan to enter logger SN You can find logger SN in the external packaging or on the logger Interface Descr ip tion...
  • Page 25: Querying The Status

    Step 3: Auto Configuration 6.2 Querying the Status Please wait for a while to complete the configuration. Then system will switch to the following page. Meter configuration guidance Click "Done" to check plant data. (Usually, the data will be updated in 10 mins) Step 1: Add the electricity meter to the plant through Logger SOLARMAN Smart platform does not support directly adding electricity meter equipment.
  • Page 26 Step 2: Perform Meter configuration (1 )Installation position of CT The three-phase meter supports the selection of single-phase system and three-phase system in the Select the appropriate installation location according to the data type to be monitored by each CT in the configuration page.
  • Page 27 (2 )CT installation site W e support setting the installation direction of CT in the electricity meter. If the CT is installed correctly, this setting can be set by default without changing. If the data value is wrong or abnormal due to the wrong installation direction, you can try to change the CT direction here, and then observe whether the data is ideal.
  • Page 28: Plant Detail

    F u n c tio n a l O v e r v ie w R eal-t im e D at a 6.3 Plant Detail In the "Real time" interface, you can see the real-time data of the Plant, such as real-time generation power and output, energy flow chart, 24-hour power curve, generation and consumption data, etc.
  • Page 29 same time, it is recommended that you select "Self consumption" as the System T ype of the Plant (3 ) If your equipment (such as inverter) collects power generation data, power consumption data, battery data and grid data at the same time, it is recommended that you select "Storage System" as the System Type of the Plant 3、D ev ic e in f o In the "Device"...
  • Page 30 meter configuration can be carried out 、 P lant A lerts 5、 P lant Info In the Alerts interface, you can view all alarm information under the plant. The alarm information will distinguish By clicking the "..." button at the upper right corner of the details page, you can select to click 【Plant Info】 to the corresponding alarm level and alarm content, so that you can quickly understand the importance of the enter the page, where you can view the basic information, system information, and income information of the alarm.
  • Page 31 7、 D elete 6、 Layout Click [Delete] through the "..." button at the top right corner of the details page, and the system will pop up a By clicking the "..." button at the upper right corner of the details page, you can choose to click 【 Layout】to enter second confirmation window.
  • Page 32: Technical Data

    7 Technical Data Safety and Protection LV-AST-3H10K5.32Aa B a tt ery M odu le AC s id e on -g r id p ara m e t ers (a pp ly t o vers ion E ,I ) A C ou tpu t 800 0 1000 0 1200 0...
  • Page 33 Gird low vol Grid voltage is abnormal (1) Check if the grid is abnormal. Annex 1 Fault diagnosis and solutions (2) Restart the inverter and wait until it functions normally. When you encounter the following problems, please refer to the Soluti ons below, and Grid over vol (3) Contact customer service if error warning contact the local distributor if the problem remains unsolved.
  • Page 34 Shenzhen Lithium Valley Technology CO.,LTD. Communication between (1) Check the cable, crystal, Line sequence.