Mounting A D20E Module; Required Clearances - GE Multilin D20E Installation And Maintenance Manual

Ethernet i/o module
Table of Contents

Advertisement

D20E Ethernet I/O Module
Chapter 4: Mounting a D20E Module
Mounting
Rack spacing

Required clearances

D20E ETHERNET I/O MODULE INSTRUCTION MANUAL

Mounting a D20E Module

This chapter describes:
Mounting
on page 75
Rack spacing
on page 75
Rack mounting procedure
Once you have configured your D20E module, you can:
1.
Physically locate and mount it in a 19" rack or cabinet.
2.
Connect ground, power and link cabling
3.
Turn power on to the module, and test it to make sure D20E module is functioning
properly.
It is recommended that you complete the above tasks, before you connect and test your
field wiring.
When mounting multiple D20E modules in a rack, or when mounting D20E modules in a
rack with other equipment, verify that there is at least one rack unit (RU) of space above
and below the D20E module to allow for cooling air flow and cable routing (1 RU = 1.75
inches or 44.5 mm).
The exterior dimensions of the D20E module are:
19" wide x 5.2" high x 1.6" deep (483 mm x 132 mm x 63.5 mm)
on page 76
GE INFORMATION
75