Testing And Certification; Approvals; Tests And Standards - GE Multilin D20E Installation And Maintenance Manual

Ethernet i/o module
Table of Contents

Advertisement

Testing and certification

Approvals

Tests and Standards

32
Approval
Applicable council directive ...
CE compliance
Low voltage directive
EMC Directive
ISO
Manufactured under a registered
quality program
Test
Dielectric voltage withstand
Impulse voltage withstand
Insulation resistance
Damped Oscillatory
Electrostatic Discharge
RF immunity
Fast Transient Disturbance
Surge Immunity
Conducted RF Immunity
Power Frequency Immunity
Voltage interruption and Ripple
DC
Radiated and Conducted
Emissions
Sinusoidal Vibration
Power magnetic Immunity
Conducted RF Immunity 0 to
150 kHz
Ingress Protection
Environmental (Cold)
Environmental (Dry heat)
Relative Humidity (Steady State)
EFT
Damped Oscillatory
Make and Carry
Electrostatic Discharge (ESD)
Product Safety
GE INFORMATION
According to ...
EN 61010-1, EN 61010-2-030
EN61326-1
ISO9001
Reference Standard
EN60255-5/IEC 60255-27
EN60255-5/IEC 60255-27
IEC 60255-5/IEC 60255-27
IEC 60255-22-1
EN61000-4-2/IEC 60255-22-2
EN61000-4-3/IEC 60255-22-3
EN61000-4-4/IEC 60255-22-4
EN61000-4-5/IEC 60255-22-5
EN61000-4-6/IEC V 60255-22-6
IEC 61000-4-16
IEC 60255-11
CISPR11 /CISPR22/ IEC 60255-25
IEC 60255-21-1
IEC 61000-4-8
IEC 61000-4-16
IEC 60529
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-78
IEEE/ANSI C37.90.1
IEEE/ANSI C37.90.1
IEEE C37.90
IEEE/ANSIC 37.90.3
IEC 61010-1
D20E ETHERNET I/O MODULE INSTRUCTION MANUAL
CHAPTER 1: BEFORE YOU START
Test Level
2.8 kV
5 kV
500 VDC (test level)
2.5 kV CM, 1 kV DM, 1 MHz
Level 4
Level 3
Level 4
Level 3
Level 3
Level 4
PQT levels based on
IEC 61000-4-29, and
IEC 61000-4-17
Class A
Class 1
Level 5
b
Level 4
IP30 front
-40 °C
+85 °C
95% RH, +40 °C
4 kV, 5 kHz
2.5 kV, 1 MHz
4 A
8 kV CD/ 15 kV AD
As per Normative sections