Download Print this page

Nailor D1200 Series Manual page 16

Multi-blade fire dampers

Advertisement

AIRFOIL BLADE FIRE DAMPERS
MULTI-BLADE FIRE DAMPERS
MODELS: 1200 / 1201 / 1202 / 1203
HOW TO ORDER:
Select model number and size, then select from each variable as applicable. Choose accessories as desired.
See previous page for description of variables and accessories.
E
1200
1201
1202
1203
Notes:
1. * Standard sleeve is 16" (406) long (suitable for 4" (102) thick wall) x 20 ga. (1.0).
SUGGESTED SPECIFICATION:
Provide and install, as shown on plans and/or schedules, multi-blade fire dampers, as manufactured by Nailor Industries, meeting
or exceeding the following criteria: Frame shall be constructed of 16 ga. (1.6) galvanized steel hat channel with mitered corners
reinforced with die-formed corner gussets for strength. Blades shall be 14 ga. (2.0) equivalent galvanized steel formed double
skin, airfoil design, on 5 1/2" (140) centers. Dampers shall be of opposed blade configuration with an interlocking blade design
that provides complete flame and smoke seal under fire conditions at an elevated temperature of 2000°F (1093°C) when in closed
position. Blade axles shall be plated steel, double bolted at each end of blade to provide positive locking connection. Hex or
square friction-fit, or press-fit axles are not acceptable. Bearings shall be self-lubricating oilite bronze type. Blade linkage shall be
zero-maintenance, concealed in frame, out of airstream.
Fire dampers shall meet the requirements of NFPA 90A and shall be manufactured, tested and labeled in accordance with UL
555 Safety Standard for Fire Dampers – Sixth Edition, June 1999 and shall have a 1 1/2 hour fire resistance rating.
Each fire damper shall bear a UL label verifying fire resistance rating in addition to the intended mounting position.
Each fire damper shall be complete with a (specifier select one) 165°F (74°C) or 212°F (100°C) UL Listed fusible link that will
cause the damper to close and lock in closed position by means of an over center/knee lock linkage for assured closure. Fire
dampers shall each include a steel sleeve of appropriate length/gauge as field verified by contractor, and retaining angles,
supplied by damper manufacturer to ensure proper installation in accordance with damper manufacturer's instructions. Each
damper shall be supplied with an internal manual quadrant(s) for setting and locking of blades in desired position. Contractor shall
provide and install an access door at each fire damper, of appropriate size to allow for inspection, testing and fusible link
replacement. Information submitted for approval shall include independent pressure drop data and confirmation of UL
qualifications in addition to manufacturer's installation instructions. Each shipment of fire dampers shall include same installation
instructions. Standard of acceptance: Nailor Industries Model Series 1200.
Previous View
E16
HOW TO SPECIFY OR TO ORDER
ie: 36" x 24"
V
FL
or
H
18" dia.
Home
Contents
165
20G
CR
212
18G
CO
16G
CSR
14G
10G
Dimensions
L8
NONE
300
L0
JSM
SMP
QS1
QS2
TDF1
TDF2
Specification Text File
Performance
Specification

Advertisement

loading