Download Print this page

OmniMetrix TrueGuard-PRO CAT EMCP1 Installation Manual

Advertisement

Quick Links

1. Unpack the monitor, antenna and the data/power cable. The 25 pin
connector plugs onto the front of the Omnimetrix
cable includes wires to power the monitor as well as wires for alarm
inputs, relay outputs and analog inputs. Take a moment to inspect
all components to verify there is no shipping damage.
2. Place the antenna vertically on the roof of the generator and route
the antenna cable into the area of the generator control. The
antenna used for transmitting must be installed to provide a
separation distance of at least 20 cm from all persons and must not
transmit simultaneously with any other antenna transmitters. BE
SURE to provide a drip loop lower than the monitor to keep water
from running down the antenna cable into the monitor connection.
3. Attach the monitor via its magnetic feet, on top of the engine
controller or other appropriate location. Horizontal surfaces are
best, but the unit may be mounted vertically or even upside down if
necessary. Note: If mounted vertically, install the monitor with the
cables down to prevent water from entering the enclosure.
4. Route the data/power cable into the generator control enclosure.
5. Connect the RED wire to generator Battery B+, the BLACK wire to
generator Battery B- (GND), and the ORANGE wire to Run Relay
Terminal 20. Connect the WHITE/GRAY wire to the Alarm Module
Terminal 2. If there is no Alarm Module, look for a terminal strip
labeled ALM, and connect there. Use the 20K OHM Resistor Wire
and connect it from ALM to generator B+ to provide the necessary
pull-up voltage for the EMCP 1 Open Collector Drive in the ALM
Terminal.
6. Attach the antenna cable to the front of the monitor, and tighten
thumb tight.
7. Turn on the monitor and confirm that the LEDs light up and blink.
If not, check for power on the terminal strip. If, after 5 minutes, the
only LED lit is the Power LED, check the antenna mount and cable
connection.
8. Allow 15 minutes for the monitor to log into the network and then
call OmniMetrix at 770-209-0012 to confirm installation. Access to
machine data is through the OmniView
www.omnimetrix.net. Contact OmniMetrix for login instructions and
web training.
®
monitor. This
®
web interface at
TrueGuard-PRO
CAT EMCP1
Installation Guide
Data/Power Cable
CAT EMCP 2 Control shown. CAT EMCP 1
Control is similar but has only one display.
CAT EMCP 1 Wiring

Advertisement

loading

Summary of Contents for OmniMetrix TrueGuard-PRO CAT EMCP1

  • Page 1 LED lit is the Power LED, check the antenna mount and cable connection. 8. Allow 15 minutes for the monitor to log into the network and then call OmniMetrix at 770-209-0012 to confirm installation. Access to ® machine data is through the OmniView web interface at www.omnimetrix.net.
  • Page 2 If you have any questions, please call OmniMetrix Tech Support at 770-209-0012 or email at techsupport@omnimetrix.net. 4295 Hamilton Mill Road, Suite 100 ▪ Buford, GA 30518 IM-714 Rev G www.omnimetrix.net ▪ 770-209-0012 Feb 2016...