Parameter
No.
Description
Eliminate visualisation error chronology
To eliminate the visualisation, set the parameter to 1,
130
then to 2
Answer 0: process successful
Answer -1: timeout of 1_2 - sequence
Default output for TÜV test:
Not valid for TÜV test when output is activated
133
2,000 ..... 10,000 = low flame or first / second / third
stage
Remote management of flame control
0 = off
141
1 = Modbus
2 = reserved
Standby time before a new attempt in event of com-
munication fault
142
Set values:
0 = not active
1 = .... 7200 s
143
Reserved
144
Reserved
Peripheral address for Modbus
145
Set values:
1 ... 247
Baud Rate for Modbus
Set values:
146
0 = 9600
1 = 19200
Parity for Modbus
0 = none
147
1 = odd
2 = even
Selection of the burner operation during the interrup-
tion of the switch-over with the system of remote man-
agement.
Set values:
With modulating operation the settings of the values
are the following:
148
0...19.9 = burner switched off
20...100 = 20...100% modulation field of the burner.
With stage operation:
0 = burner off P1, P2, P3
No setting = no function in the event of communication
interruption
161
Total number of errors
162
Hours of operation (that can be reset)
163
Total hours of power supply to flame control
164
Total number of start-ups (that can be reset)
166
Total number of start-ups
Volumetric delivery of fuel in the selected unit of meas-
167
urement (that can be reset)
200
BURNER CHECKS
Control and display
Unit of
No. of
Modifica-
measure-
elements
tion
ment
1
-
Modification
Modification /
1
%
zero setting
1
-
Modification
1
s
Modification
1
-
Modification
1
s
Modification
1
-
Modification
1
-
Modification
1
-
Modification
Modification /
1
%
zero setting
1
-
Reading only
1
h
Reset
1
h
Reading only
1
-
Reset
1
-
Reading only
3
m
, l,
1
Reset
3
ft
, gal
47
GB
Values interval
Degree of
precision
Min.
Max.
-5
2
1
20%
100%
0.1%
0
2
1
0s
7200s
1s
1
8
1
10s
60s
1s
1
247
1
0
1
1
0
2
1
0%
100%
0.1%
0
65535
1
0 h
999999h
1 h
0h
999999h
1h
0
999999
1
0
999999
1
0
99999999
1
Predefined
Access mode
setting
0
Service Mode
Not defined
Service Mode
0
Service Mode
120s
Service Mode
1
Info Mode
30s
Service Mode
1
Service Mode
1
Service Mode
0
Service Mode
Not defined
Service Mode
0
Info mode
0h
Info mode
0h
Info mode
0
Info mode
0
Info mode
0
Info mode
20205255