HEATER WIRING

All electrical work must be installed in the United States in accordance with the latest version of the National Electrical Code ANSI/NFPA No. 70, in
Canada, with the latest version of Canadian Electrical Code CSA C22.1, must conform to all local code authority having jurisdiction. AN ELECTRICAL
GROUND IS REQUIRED TO REDUCE RISK OF ELECTRICAL SHOCK OR POSSIBLE ELECTROCUTION.
If any of the original wire as supplied with the appliance must be replaced, use only type 105°C thermoplastic or equivalent, 250°C type F must be used
for the flame sensor leads and the spark ignition cable must be high voltage 250°C.
CAUTION
LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS
OPERATION. VERIFY PROPER OPERATION AFTER SERVICING.
WIRING DIAGRAM AND SCHEMATIC - FIGURE 4