Diagnostics Functions
RESET DEVICE (2 seconds): same as the FAAST LT RESET button
RETRIEVE LOG (10 seconds): this will retrieve the entire
log and save it in a file on the desktop (assuming the
Diagnostic Tool is run from the desktop as suggested).
EXECUTE DIAGNOSTIC (variable time required):
This will retrieve all the information from the device and tests
various functions. Again, if the Diagnostic Tool is run from the
desktop, the results will be saved in a file on the desktop.
At the end, the Diagnostic will automatically
perform a RESET on the FAAST LT.
Please note:
• Running the Diagnostics will cause FAULT
relay activation during the tests.
• With TEST ALARMS selected, the program
will activate the alarm relays.
• With FULL DIAGNOSTIC selected, an
extended set of functions is checked.
• Return the Diagnostic data file to sse.technical@systemsensor.com
• Important- after using this program it is necessary
to restart the device by powering it OFF and ON again
after 10 seconds to restore normal behavior.
Time required for the diagnostic depends on the options selected:
FULL DIAGNOSTIC
NO
NO
YES
YES
To stop the Diagnostics, click on the ABORT button
repeatedly until execution is stopped.
Please contact your Representative if you have any questions.
www.faast-detection.com
TEST ALARMS
TIME REQUIRED
NO
~100sec
YES
~140sec
NO
~15min
YES
~17min