Ansell Watchman AWLED/3M Installation Instructions

Led exit sign emergency

Advertisement

Quick Links

General Installation Instructions

These instructions should be read carefully prior to any installation and retained after completion for further
reference and maintenance. Please give these instructions to the building owner/occupier after installation.

Important Safety

1.
Before installation, maintenance or lamp replacement, ensure that the mains supply to the luminaire is switched off and the circuit supply fuses are removed or
the circuit breaker is turned off.
2.
It is recommended that only a qualified electrical contractor carries out the installation of this luminaire and that the luminaire is installed in compliance with the
current edition of the IEE Wiring Regulations.
3.
The person carrying out the installation is to check and verify that the total load on the circuit, including that of this luminaire does not exceed the rating of the
circuit cable, fuse or circuit breaker.
4.
Where a luminaire incorporates discharge control gear (inductive load), the circuit capacity and ratings require careful sizing to avoid nuisance tripping of the
protective device used in the installation.
5.
Where applicable, careful consideration should be taken during installation to ensure that all fixings and/or suspensions are of a suitable size for the luminaire
being installed.

Ratings

1. All luminaires are manufactured & tested in compliance with the requirement contained within BS EN 60598 and are CE marked.
2. All luminaires that are of Class 1 construction and that are marked accordingly, MUST be earthed.
3. All luminaires are designed to operate at 230Volts AC -6%/+10% = 216Volts to 252Volts. Do not operate outside these voltages.
4. All luminaires are only suitable for applications within their rated Ingress Protection limits as stated

Exclusions to Warranty

Please Note - The limited warranty shall be null and void in the following circumstances:-
Failure by the installer, end user or any third party to exercise caution to protect any covered product or part from outside damage, adverse temperature (normal
operating ambient temperature 0 - 25°C), humidity conditions, fluctuations in the electrical system or physical abuse as well as failure related to workmanship in the
installation of the products or parts.
-------------------------------------------------------------------------------------------------------------------------------------------------------------------------------

INSTALLATION

Remove the end plate by releasing the two screws.
Select a suitable mounting surface and provide a suitable power supply.
Bring in the incoming supply through the base and terminate into the terminal block on the gear tray.

Electrical Connection

Connect as follows:-
PERMANENT LIVE
SWITCHED LIVE
EARTH
NEUTRAL
Connect the battery plug to the PCB board where indicated.
Refit the required legend in the correct orientation and replace the end plate.
Switch on the mains supply. Check the unit operates correctly.
Check the LED indicator is GREEN and ON.

Note

Switch on the mains supply. Check the unit operates correctly.
Check the LED indicator is ON and GREEN.
Leave the unit on charge for one hour, then remove the supply to simulate mains failure and check the lamp operates in emergency
mode.
The unit requires 48 hours to fully charge the battery and achieve 3 hours emergency operation.
DO NOT deep discharge the batteries pack in emergency output for over a period of 48hrs as this will cause irreparable damage
to the battery.
-------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Page No. 1
Description –
Installation Instructions
®
Luminaire Code(s) –
(L)
BLACK (continuous)
(L1)
BROWN (switched)
GREEN / YELLOW
(N)
BLUE
www.anselluk.com
3W 6500K IP20 Watchman LED Exit Sign
Emergency Maintained / Non-maintained
AWLED/3M
Issue Date: td 20140716

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Watchman AWLED/3M and is the answer not in the manual?

Questions and answers

Summary of Contents for Ansell Watchman AWLED/3M

  • Page 1 Description – 3W 6500K IP20 Watchman LED Exit Sign Emergency Maintained / Non-maintained Installation Instructions ® AWLED/3M Luminaire Code(s) – General Installation Instructions These instructions should be read carefully prior to any installation and retained after completion for further reference and maintenance. Please give these instructions to the building owner/occupier after installation. Important Safety Before installation, maintenance or lamp replacement, ensure that the mains supply to the luminaire is switched off and the circuit supply fuses are removed or the circuit breaker is turned off.
  • Page 2 ® Operating and recommended Routine Test Procedure Follow these instructions carefully to ensure safe and reliable operation of this emergency luminaire. The following testing is designed to ensure the continued protection of your premises and occupants, in the event of the possibility of a failure of the normal lighting supply. Testing should be carried out in accordance with the recommendations of BS5266-8-2004.