Fujitsu AJY090LELDHS Installation Manual page 14

Vrf system outdoor unit
Table of Contents

Advertisement

Level 1 (stop)
Level 2
(operated at 40% capacity)
Level 3
Energy saving
(operated at 60% capacity)
level setting (*1)
Level 4
30
(operated at 80% capacity)
Level 5
(operated at 100% capacity)
The capacity limit can be selected by the external input terminal (CN133) when
operating with the "Energy Saving Peak Cut function".
The lower the level, the more the effect of energy saving, but the cooling/heating
performance will also drop.
31
Prohibited (Factory default)
Capacity priority
Off (quiet priority)
setting (in low
On (capacity priority)
noise mode) (*1)
40
If the cooling/heating performance becomes insufficient when the low noise mode
is set, it is possible to set "capacity priority" that automatically cancels the low
noise mode (once performance is restored, the mode will automatically return to
the low noise mode).
Off (Normal)
Low noise mode
41
setting (*1)
On (Low noise mode)
Level 1
Low noise mode
42
Level 2
level setting
Prohibited
52
Prohibited (Factory default) (*4)
Enable
Disable
Intelligent refrig-
Enable only evaporation
53
erant control
temperature control
Enable only condensation
temperature control
60
Prohibited (Factory default)
Setting number (x00)
Setting number (x01)
Electricity meter
No. setting 1 (*2)
70
Setting number (x98)
Setting number (x99)
Set the ones digit and tens digit of the No. of the electricity meter connected to
CN135.
Setting number (0xx)
Electricity meter
Setting number (1xx)
No. setting 2 (*2)
71
Setting number (2xx)
Set the hundreds digit of the No. of the electricity meter connected to CN135.
Setting number (xx00)
Setting number (xx01)
Electricity meter
pulse setting
1 (*3)
72
Setting number (xx98)
Setting number (xx99)
Set the ones digit and tens digit of the No. of the electricity meter pulse setting
connected to CN135.
Setting number (00xx)
Setting number (01xx)
Electricity meter
pulse setting
2 (*3)
73
Setting number (98xx)
Setting number (99xx)
Set the hundreds digit and thousands digit of the electricity meter pulse setting
connected to CN135.
90
Prohibited (Factory default)
*1: Do not set this for outdoor units with subordinate setting.
*2: When electricity meter No. is set to "000" and "201 to 299", the pulses input to
CN135 become ineffective. Available setting number is "001" to "200"
*3: When the electricity meter pulse setting is set to "0000", the pulses input to CN135
become ineffective. Available setting number is "0001" to "9999"
*4: This item is not displayed for 072, 090, and 108 models.
En-13
0
0
0
1
0
2
3
0
0
3
0
4
3
1
0
0
0
0
4
0
0
1
0
0
4
1
0
1
0
0
4
2
0
1
0
2
5
2
0
0
0
0
0
1
5
3
0
2
0
3
6
0
0
0
0
0
0
1
7
0
9
8
9
9
0
0
7
1
0
1
0
2
0
0
0
1
7
2
9
8
9
9
0
0
0
1
7
3
9
8
9
9
9
0
0
0
(1) Turn on the power of the outdoor unit and enter standby mode.
• When system is normal
POWER/MODE lamp is on. (ERROR
lamp is off.)
POWER/MODE
POWER
ERROR
MODE
lamp: on
7-segment
display: off
MODE/EXIT button
MODE
SELECT ENTER
/NEXT
ENTER button
SELECT button
(2) Setting method
Use the "MODE/EXIT", "SELECT",
and "ENTER" buttons to configure
settings according to the proce-
dures below.
(If no setting is made, the factory
default setting will be displayed.)
1) Function setting
First 2 digits Last 2 digits
2) Settings the first
Every press of the
"SELECT" button will
change the setting
number for the first 2
digits.
EXIT: Press the "MODE/EXIT" button to cancel the setting mode.
• When system is abnormal
Check the settings as there is an error in the
settings for outdoor unit address
(DIP switch SET 3-1, 2).
ERROR
lamp: off
POWER/MODE
lamp: on
7-segment display:
"-" display
MODE
SELECT ENTER
/NEXT
: Press the "MODE/EXIT" button
: Press the "SELECT" button
: Press the "ENTER" button.
: Press the "ENTER" button for
more than 3 seconds.
7-segment display (LED 105, LED 104)
(When [F3] to [F9] are displayed, continue to press
the "SELECT" button until [F2] is displayed.)
(Blinking)
2 digits
3) Settings the last 2 digits
Continue to press the "SELECT" button until the
desired number appears at the last 2 digits.
The setting is complete when the display
changes from blinking to light.
Press "ENTER" button to return to "2) Settings the
first 2 digits" (If there is no operation for 5 seconds
after the setting, the display will return to "2) Set-
tings the first 2 digits".)
(Continue to press the "SE-
LECT" button until the desired
number appears at the last 2
digits.)
The setting is complete when the display
changes from blinking to light.
Press "ENTER" button to return to "2) Settings the
first 2 digits" (If there is no operation for 5 seconds
after the setting, the display will return to "2) Set-
tings the first 2 digits".)
ERROR lamp:
POWER
ERROR
MODE
blinking

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ajy108leldhs

Table of Contents