Summary of Contents for DV Power TRT03

  • Page 1 TRT03 THREE-PHASE TRANSFORMER TURNS-RATIO TEST INSTRUMENT Manual...
  • Page 2: Table Of Contents

    8.5 Dimensions and Weight........................16 8.6 Applicable Standards ........................17 Accessories ............................18 Manufacturer Contact Information ....................... 19 Manual Version: M-T003NN-205-EN This Manual refers to the following TRT03 models and their corresponding firmware versions Model Firmware versions TRT03A TR0A-3.08 TRT03B TR0B-3.08...
  • Page 3: Introduction

    1.1.2 Terms of Use • TRT03 shall be used only if it is in good technical condition. Its use shall be in accordance with local safety and industrial regulations. Adequate precautions must be taken to avoid any risks related to high voltages associated with this equipment and nearby objects.
  • Page 4: Orderly Practices And Procedures

    1.1.6 Safe Operating Procedures • Hazardous voltages of up to 400 V can occur inside TRT03. Therefore, it is not permitted to remove the protective casing of TRT03. •...
  • Page 5: Power Supply

    (e.g., L1-L2; A-B). However, the voltage must not exceed 264 V AC. Please refer to the section “Technical Data”. • TRT03 should be positioned in such a way that it is possible to safely disconnect it from the power supply at any moment. WARNING / AVERTISSEMENT This is a class A product.
  • Page 6: Description

    Connect TRT03 to the mains power supply with a power cord. Power switch – Double pole switch • I In this position, TRT03 is connected to the mains power supply. • 0 In this position, TRT03 is separated from the mains power supply.
  • Page 7 TRT03 is equipped with an USB serial interface to connect to external computer if required. Flash Drive TRT03 is equipped with a USB flash drive connector to save test results to a flash drive for additional analysis if desired. 7. TC Control TC Connector Output for the remote control of the transformer tap changer.
  • Page 8: Getting Started

    Getting Started 3 Getting Started 3.1 Connecting TRT03 to a Test Object Before TRT03 has been connected to a test object (e.g. power transformer), the following steps have to be verified: • The test object is disconnected from its circuit in accordance with the national safety regulations and is properly grounded to the protective earth.
  • Page 9: Setting The Measurement Parameters

    ENTER 1. If the vector group is selected, TRT03 will perform the phase by phase test by applying single phase test voltages to all phases in turn. 2. If SINGLE is chosen, TRT03 will test a single phase transformer by applying the single phase test voltage between 1U/H1/A and 1N/H0/N.
  • Page 10 Getting Started If the name plate voltages are not entered, TRT03 will perform the test and display the results, but it will not calculate or display the turns ratio deviation. After the name plate voltages and tap changer position(s) are entered, press to confirm a selection.
  • Page 11 “Unable to detect vector group” and the test will be aborted. Once the vector group is detected and confirmed, TRT03 continues with the test. After the test is finished, TRT03 displays the test results. To scroll between all the results, the user will press .
  • Page 12: Error Messages

    "Turns ratio too low’’ 4.3 Error Message “Malfunction” In the case of an internal error, TRT03 will display the massage “Malfunction”. In this case, TRT03 device should be restarted. If the error occurs repeatedly, please contact the DV P Support Team (refer to OWER the Section ”Manufacturer Contact Information”).
  • Page 13: Error Message "Check Paper

    4.8 Error Message “Connections” The “Connections” is displayed if the H or X cables are not connected properly to TRT03. There are also green LED lights next the connectors that lights up to indicate that these connectors are connected properly.
  • Page 14: Troubleshooting Guide

    YNyn0 test Short circuited clamps 2. Connect the shorted primary and secondary cables (clamps) of TRT03 instrument to the primary side of the transformer as shown in the figure below. Perform the test three times, using each test voltage. Save all results.
  • Page 15: Customer Service

    TRT03 Customer Service & Packing the Instrument for Shipment 6 Customer Service Before calling or sending an e-mail to the DV Power Customer Service for assistance, please perform the following steps:  Check all cable connections.  If possible, try testing on another instrument of the same type ...
  • Page 16: Technical Data

    TRT03 Technical Data 8 Technical Data 8.1 Mains Power Supply - Connection: According to IEC/EN60320-1; UL498, CSA 22.2 90 – 264 V AC, or 110 – 350 V DC - Voltage: 50 – 60 Hz - Frequency: - Input power:...
  • Page 17: Applicable Standards

    TRT03 Technical Data 8.6 Applicable Standards - Installation/overvoltage category: - Pollution degree: - Safety LVD 2006/95/EC (CE Conform) Standard EN 61010-1:2001 - EMC Directive 2004/108/EC (CE Conform) Standard EN 61326-1:2006 M-T003NN-205-EN...
  • Page 18: Accessories

    TRT03 Accessories 9 Accessories Article No Included DV-Win PC software including USB cable Built-in Tap Changer Control Unit Tap Changer Control cable 5 m Mains power cable Ground (PE) cable Article No Recommended H winding test cable 5 m, 3~ connection, with TTA clamps...
  • Page 19: Manufacturer Contact Information

    TRT03 Manufacturer Contact Information IBEKO Power AB 2014 This Manual is a publication of IBEKO Power AB, 181 50 Lidingö, Sweden. These documents are protected by Swedish Copyright law and international contracts as intellectual property of the IBEKO Power AB. The documents contain confidential information of IBEKO Power AB which is protected by patent, copyright, trademarks or otherwise as inventions, trademarks or creations of IBEKO Power AB.