LG ART COOL LA181HSV5 Engineering Manual page 55

Single zone mirror wall mounted 3/4 to 2 tons
Table of Contents

Advertisement

Minimum Allowable Clearance and Service Access Requirements
Proper clearance for the outdoor unit coil is critical for proper operation. When installing the outdoor unit, consider service, inlet and outlet,
and minimum allowable space requirements as illustrated in the diagrams below.
• Include enough space for airflow and for service access. If installing multiple outdoor units, avoid placing the units where the discharge of
one unit will blow into the inlet side of an adjacent unit.
• If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that the discharge air of the outdoor unit isn't restricted.
No obstacles to air circulation around the unit; keep proper distances from ceilings, fences, floor, walls, etc. (Install a fence to prevent
pests from damaging the unit or unauthorized individuals from accessing it.)
Single Zone Art Cool Mirror Outdoor Unit (9,000, 12,000, 18,000 Capacities) Service Access and Allowable Clearances
Specific clearance requirements in the diagram below are for 9,000, 12000, 18,000 Btu/h capacities. Figure below shows the overall
minimum clearances that must be observed for safe operation and adequate airflow around the outdoor unit.
When placing the outdoor unit under an overhang, awning, sunroof or other "roof-like structure", observe the clearance requirements (as
shown in Cases 1 and 2) for height in relation to the unit. To have successful service access to the outdoor unit, see the Figure below for
minimum spacing. When installing multiple outdoor units, see Cases 4 and 5 for correct spacing requirements.
If the outdoor unit is installed between standard and minimum clearances, capacity decreases approximately 10%.
Figure 41: Single Zone Art Cool Mirror 9,000, 12,000, 18,000 Capacity Outdoor Unit Service Access and Allowable Clearances Diagram.
Case 1
A
B
Case 4
Table 32: Single Zone Art Cool Mirror 9,000, 12,000, 18,000 Outdoor Unit Service Access and Allowable Clearances Diagram Legend.
Unit: Inch
Standard
Case 1
Minimum
Standard
Case 2
Minimum
Standard
Case 3
Minimum
Standard
Case 4
Minimum
Standard
Case 5
Minimum
PLACEMENT CONSIDERATIONS
Case 2
G
D
Case 5
D
F
E
A
B
12
24
4
10
-
-
-
-
-
-
-
-
-
-
-
-
-
24
-
10
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Case 3
G
C
and/or plants will be in the path of the warm
air, or where the warm air and/or noise will
disturb neighbors.
B
B
D
C
D
-
12
-
4
20
-
14
-
20
12
14
4
-
12
-
4
-
12
-
4
Outdoor Unit
D
C
Do not place the unit where animals
E
F
-
-
-
-
-
-
-
-
-
-
-
-
24
-
8
79
-
-
-
-
APPLICATION | 55
G
-
40
-
40
-
-
-
-
-
-

Advertisement

Table of Contents
loading

Table of Contents