High voltage spikes (noise) present in the industrial environment can cause malfunctioning of the instrument like erratic display, latch up, data loss or permanent damage to the instrument. To reduce the chances of malfunction
While TX2 is running/ waiting for inputs, set value/ values can be recalled (viewed) without disturbing the timing process.
Briefly press the button on the TX2 timer.
While TX2 is running/ waiting for inputs pressing the button for 3 seconds causes to display to show the configuration setting of parameters 1 to 6 one after the other.
TX2 is a multifunctional timer. To make it function in the desired way it has to be configured.
Configuration can be done through the front panel buttons.
To enter into the configuration mode.
To change parameter value
To save the changes and exit the configuration mode
# | Name. | Setting range for parameter | |
1 | Time Units | Seconds | |
Minutes | |||
Hours | |||
2 | Range | 9.99 When Time units is set to seconds 9.59 When Time units is set to Minutes or Hours. | |
99.9 | |||
999 | |||
3 | Direction | UP: Once the timer starts the display increases from 0 to Set value. | |
DOWN: Once the timer starts the display decreases from Set value to 0. | |||
4 | Mode | On delay | |
Interval | |||
Cyclic with ON time first. | |||
Cyclic with OFF time first. | |||
5 | Front Reset | Reset by front panel Enable. | |
Reset by front panel Disable. | |||
6 | Output 2 | Output 2 follows Output 1. | |
Output 2 pulses on for 750ms when START input is | |||
given. Output 2 is opposite off Output 1. | |||
7 | Reset | Normal: To start a new cycle a RESET input has to be given. | |
Auto: A new cycle can be started without first giving a RESET signal. | |||
8 | Start type | Level: The START input can be closed permanently and the timer will always read it as start input present. | |
Gate: When START is open the relay state does not change but the time counting stops. On make of START contact time counting starts from the last time count. | |||
Edge: Timing starts on application of START input (Open to Close). | |||
Exit Config | On pressing button at this parameter configuration is saved and timer goes into normal operation. |
Display: | 0.56" height 3 digit Red. |
Time ranges: | 9.99 / 99.9 / 999 sec, 9:59 min: sec, 99.9 / 999 min, 9.99 / 99.9 / 999 Hrs. |
Counting Direction: | Up / Down. |
Modes: |
|
Time setting: | By front keypad. |
Outputs: | 2 C/O. |
Relay rating: | 7A @ 240VAC. |
Inputs: |
|
Reset: |
|
Reset Time: | Less than 100ms. |
Accuracy: | ±0.05% or 50msec which ever is greater. |
Supply: | 220VAC ±10% @ 50 / 60 Hz. |
Mounting: | Panel mounting. |
Housing: | ABS. |
Operating Temperature: | 0˚C to 50˚C. |
Humidity: | 95% R.H. Non condensing. |
Specifications subject to change as development is a continuous process.