Mitsubishi Electric NTXMSM36A142BA Technical & Service Manual page 144

Outdoor unit
Table of Contents

Advertisement

Method of Combined Branching of Lines and
Headers
Connection Examples
(Connecting to 5 Indoor Units)
Total Piping Length
Permissible
Farthest Piping Length
Length
Farthest Piping Length After First Branch
High/Low Difference in Indoor/Outdoor Section
Permissible High/
Low Difference
High/Low Difference in Indoor/Indoor Section
Selecting the Refrigerant Branch Kit
Select Each Section of Refrigerant Piping
(1) Section From Outdoor Unit
to First Branch (A)
(2) Sections From Branch to
Indoor Unit (a,b,c,d,e)
(3) Section From Branch to
Branch (B,C)
Select the size from the table to the right.
Additional refrigerant charge
OCHT810A
A
A
B
A+B+C+a+b+c+d+e is 492 ft [150 m]
(L)
A+B+b is 262 ft [80 m]
( )
B+b
98 ft [30 m]
(H)
164 ft [50 m] (If the outdoor unit is lower, 131 ft [40 m] or less)
(h)
49 ft [15 m]
Please select branching kit, which is sold separately, from the table below.
(The kit comprises sets for use with liquid pipes and for use with gas pipes.)
Branch Joint
CMY-Y62-G-E
(1) Refrigerant Piping Diameter In Section
From Outdoor Unit to First Branch
(Outdoor Unit Piping Diameter)
Model
Each
Section of
NTXMSM60A182BA
Piping
(3) Refrigerant Piping Diameter In Section
From Branch to Branch
Liquid Line (inch [mm])
3/8 [ø9.52]
Refer to the same section in the previous page.
Note: Pipe re-branching after the header branching
is not possible.
C
c
d
3
4
B
D
D
L
b
a
C
D
1
Branch Header (4 branches)
CMY-Y64-G-E
Piping Diameter (inch [mm])
Liquid Line
3/8 [ø9.52]
Gas Line
3/4 [ø19.05]
Gas Line (inch [mm])
3/4 [ø19.05]
144
E
F
e
5
D
A
Outdoor unit
B
First branching (branching
joint)
C
Branching joint
D
Indoor unit
2
D
E
Branching header
F
Blind caps
Branch Header (8 branches)
CMY-Y68-G-E
(2) Refrigerant Piping Diameter In Section
From Branch to Indoor Unit
(Indoor Unit Piping Diameter)
Model number
Piping Diameter (inch [mm])
Liquid Line
1/4 [ø6.35]
018 or lower
Gas Line
1/2 [ø12.7]
Liquid Line
3/8 [ø9.52]
024 to 054
Gas Line
5/8 [ø15.88]
Liquid Line
3/8 [ø9.52]
072
Gas Line
3/4 [ø19.05]

Hide quick links: