8-6. OUTDOOR UNIT INPUT/OUTPUT CONNECTOR
State (CN51)
L
1
~
L
2
Auto change over (CN3N)
SW1
~
SW2
Silent Mode/Demand Control (CN3D)
SW1
~
SW2
The silent mode and the demand control are selected by switching the DIP switch 9-2 on outdoor controller board.
It is possible to set it to the following power consumption (compared with ratings) by setting SW1, 2.
Silent mode
Demand control
OCHT810A
X
X
Y
Y
5
4
3
X
1
X
2
3
Y
Y
X
1
X
2
3
Y
Y
Outdoor controller board DIP SW9-2 SW1 SW2
OFF
ON
Distant control board
Relay circuit
External output adapter
CN51
(PAC-SA88HA-E)
Outdoor unit control board
L
: Error display lamp
1
L
: Compressor operation lamp
2
X, Y: Relay (coil rating: ≤ 0.9 W, 12 V DC)
Remote control panel
Relay circuit
External input adapter
CN3N
(PAC-SC36NA-E)
Outdoor unit control board
SW1: Switch
SW2: Switch
X, Y: Relay (contact rating: ≥ 0.1 A, 15 V DC)
(min. applicable load: ≤ 1 mA)
ON
Heating
SW1
Validity of SW1
SW2
Remote control panel
Relay circuit
CN3D
External input adapter
(PAC-SC36NA-E)
Outdoor unit control board
SW1: Switch
SW2: Switch
X, Y: Relay (contact rating: ≥ 0.1 A, 15 V DC)
(min. applicabl load: ≤ 1 mA)
Function
ON
Silent mode operation
OFF
OFF
100%
(Normal)
ON
OFF
75%
ON
ON
50%
OFF
ON
0%
(Stop)
111
Lamp power supply
Procure locally
Max. 33 ft [10 m]
Relay power supply
Procure locally
Max. 33 ft [10 m]
OFF
Cooling
Invalidity of SW1
Relay power supply
Procure locally
Max. 33 ft [10 m]