6.2

Output test

It is possible to activate the devices connected to the mainboard "A" (PWR).
NOTE:
Both quick couplers must be installed!
Turn COOLIUS SELECT to select the output to be activated.
Press ENTER to activate the selected OUTPUT.
NOTE:
In order to avoid the exit of refrigerant from the vacuum pump outlet or from the oil/UV bottles, the
activation of VP, UV, NO, HO and of all the combinations containing at least one of them, are possible only
when the pressure is lower than 1100 mb.
• CP
Compressor and Compressor fan
• VP
Vacuum pump
The HP and LP gauges must show 0 (Zero) bar!
• EO
Used oil drain valve (EO)
Nitrogen discharge valve (EO2)
Refrigerant analysis circuit oil drain (E3)
• NO
New oil valve
The HP and LP gauges must show 0 (Zero) bar!
• UV
Dye tracer valve
The HP and LP gauges must show 0 (Zero) bar!
• HO
Hybrid oil valve
The HP and LP gauges must show 0 (Zero) bar!
• RF
Refrigerant valve
• XP
Recovery valve
• LP
Separation valve
• A1
Aggregate valve
• A2
Aggregate valve 2
• A3
Nitrogen valve
COOLIUS A50 / Y50