Olimpia splendid SITALI CXRA 120 Instructions For Installation, Use And Maintenance Manual
Olimpia splendid SITALI CXRA 120 Instructions For Installation, Use And Maintenance Manual

Olimpia splendid SITALI CXRA 120 Instructions For Installation, Use And Maintenance Manual

Table of Contents
  • Table of Contents
  • Avvertenze E Precauzioni
  • Informazioni DI Prodotto
  • Generale
  • Dimensioni E Peso
  • Connessioni Delle Tubazioni
  • Spazio Richiesto
  • Etichetta Dati
  • Trasporto E Stoccaggio
  • Installazione
  • Rimozione Dell'imballo
  • Dove/Come Installarlo
  • Installazione a Soffitto
  • Installazione a Parete
  • Collegamento Elettrico Precablato
  • Collegamenti Elettrici Aggiuntivi
  • Messa in Servizio
  • Settaggio Velocità Dei Ventilatori
  • Prima DI Avviare Il Sistema
  • Funzionamento
  • Funzionamento a 3 Velocità con Comando Remoto CTRL-V1 (in Dotazione)
  • Remote Enable
  • Controllo Tramite Modbus
  • Manutenzione Ordinaria E Straordinaria
  • Lista Componenti
  • Descrizione Dei Componenti
  • Manutenzione Ordinaria
  • Manutenzione Straordinaria
  • Risoluzione Guasti
  • Smaltimento E Riciclaggio

Advertisement

Available languages

Available languages

Quick Links

SITALI CXRA 120
MANUALE DI INSTALLAZIONE ED USO E MANUTENZIONE
2
IT
INSTALLATION, USE AND MAINTENANCE MANUAL
16
EN
Olimpia Splendid SpA
Via Industriale 1/3, 25060 Cellatica (BS)
www.olimpiasplendid.it - info@olimpiasplendid.it
I dati tecnici e le caratteristiche estetiche dei prodotti possono subire cambiamenti. Olimpia Splendid si riserva di modificarli in ogni momento senza preavviso.

Advertisement

Table of Contents
loading

Summary of Contents for Olimpia splendid SITALI CXRA 120

  • Page 1 INSTALLATION, USE AND MAINTENANCE MANUAL Olimpia Splendid SpA Via Industriale 1/3, 25060 Cellatica (BS) www.olimpiasplendid.it - info@olimpiasplendid.it I dati tecnici e le caratteristiche estetiche dei prodotti possono subire cambiamenti. Olimpia Splendid si riserva di modificarli in ogni momento senza preavviso.
  • Page 2: Table Of Contents

    SITALI CXRA 120 Unità di ventilazione con recupero di calore Leggere questo manuale attentamente prima di utilizzare il prodotto e conservarlo in un posto sicuro così da poterlo consultare all’occorrenza. Il prodotto è costruito a regola d’arte e nel rispetto delle normative vigenti in materia di apparecchiature elettriche e deve essere installato da personale tecnicamente qualificato.
  • Page 3: Avvertenze E Precauzioni

    Per ottenere il funzionamento corretto e sicuro del prodotto, leggere questo manuale con attenzione, utilizzare l’unità seguendo le linee guida di seguito elencate e attenersi a tutte le prescrizioni di sicurezza. Il modello SITALI CXRA 120 è fornito con il pannello di comando remoto CTRL-V1.
  • Page 4: Dimensioni E Peso

    3.2 Dimensioni e Peso SUPPLY EXAUST INSERIRE OUTSIDE RETURN VISTA CON FILTRI E SCAMBIATORE TRATTEGGIATI E SIMBOLI DEI VARI Scarico (COME DA ETICHETT CONDENSATION condensa DRAIN Ø16 Peso Kg 11,5 DETAIL A SUPPLY EXAUST DETAIL A Dimensioni in mm Fig.3.a 3.3 Connessioni delle tubazioni CONDENSATION DRAIN Ø16...
  • Page 5: Installazione

    5 INSTALLAZIONE ATTENZIONE Assicurarsi che le avvertenze e le precauzioni indicate nel Capitolo 2 siano attentamente lette, comprese e rispettate! Questa sezione descrive come installare l’unità correttamente. L’unità deve essere installata seguendo queste istruzioni. 5.1 Rimozione dell’imballo Verificare che l’unità (e gli eventuali accessori) siano conformi a quanto ordinato prima di procedure all’installazione. Eventuali discrepanze rispetto a quanto ordinato devono essere comunicate al fornitore.
  • Page 6: Installazione A Parete

    5.a Preparare la superficie sulla quale l’unità deve essere montata. Assicurarsi che essa sia piana, livellata e che sia costruita in modo da poter sostenere il peso dell’unità. Effettuare l’installazione conformemente a quanto richiesto dalle norme e regolamenti locali in vigore. 5.b E’ importante che l’unità sia inclinata di 2° affinché lo scarico condensa funzioni appropriatamente: a tale scopo usare i 2 distanziali in dotazione che devono essere montati sulle staffe di fissaggio del lato con scarico condensa.
  • Page 7: Collegamento Elettrico Precablato

    5.4 Collegamento elettrico precablato ATTENZIONE Assicurarsi che l’interruttore generale dell’impianto sia spento prima di qualsiasi operazione di installazione, manutenzione ordinaria o straordinaria o collegamento elettrico! ATTENZIONE L’installazione e la manutenzione dell’unità e del sistema di ventilazione completo devono essere eseguite da un installatore autorizzato e in conformità...
  • Page 8: Collegamenti Elettrici Aggiuntivi

    L’unità necessita della messa a terra. I collegamenti interni sono eseguiti durante l’assemblaggio in fabbrica. In caso in allungamento del cavo tra il comando esterno CTRL-V1 e la scheda madre del SITALI CXRA 120, utilizzare un cavo 6 poli di lunghezza max. 30 metri.
  • Page 9: Messa In Servizio

    6 MESSA IN SERVIZIO 6.1 Settaggio velocità dei ventilatori La velocità dei ventilatori può essere regolata durante l‘installazione in base al tasso di ventilazione richiesta, impostando i relativi dip switch. La figura 6. a rappresenta la curva di prestazione alle diverse regolazioni del segnale 0-10V fornito ai motori. L’assorbimento indicato si riferisce ai 2 motori. La tabella 6. b indica l’efficienza del pacco scambiatore e la condensa prodotta in diverse condizioni climatiche, per aiutare la decisione, demandata al progettista o all’installatore dell’impianto, di collegare uno o entrambi gli scarichi condensa.
  • Page 10: Prima Di Avviare Il Sistema

    Lw dB - LIVELLO DI POTENZA SONORA PER BANDA DI OTTAVA Lp dB(A) LwA dB(A) Velocità 100% Lw dB - LIVELLO DI POTENZA SONORA PER BANDA DI OTTAVA Lp dB(A) LwA dB(A) Velocità 80% Lw dB - LIVELLO DI POTENZA SONORA PER BANDA DI OTTAVA Lp dB(A) LwA dB(A) Velocità 60% Lw dB - LIVELLO DI POTENZA SONORA PER BANDA DI OTTAVA Lp dB(A) LwA dB(A) Velocità 40% Lw dB - LIVELLO DI POTENZA SONORA PER BANDA DI OTTAVA Lp dB(A) LwA dB(A) Velocità 20%* < 9 Tabella 6.c Emissioni sonore: I dati dB(A) sono valori medi in propagazione sferica in campo libero e riportati a scopo comparativo. *misure comparabili con rumore di fondo della camera di prova. 6.2 Prima di avviare il sistema Ad installazione ultimata, prima di avviare l’unità verificate che: • I filtri siano correttamente inseriti.
  • Page 11: Funzionamento A 3 Velocità Con Comando Remoto Ctrl-V1 (In Dotazione)

    7.1 Funzionamento a 3 velocità con comando remoto CTRL-V1 (in dotazione) Per attivare/spegnere l’unità ventilante Per diminuire la velocità preimpostata Per aumentare la velocità preimpostata Per attivare manualmente la velocità Boost Per resettare l’Allarme Filtro Led verde: velocità 1 selezionata Led verde: velocità 2 selezionata Led verde: velocità 3 selezionata Led blu: attivazione anti-frost Led rosso: segnalazione malfunzionamento Led giallo: i filtri necessitano di manutenzione/sostituzione Led giallo: blocco tastiera Fig.
  • Page 12: Remote Enable

    7.2 Remote Enable Permette di attivare/disattivare l’unità da remoto mediante un contatto pulito connesso all’ingresso In1 di Fig. 5.j. Per abilitare questa funzione è necessario agire sul dip switch 8. DIP8 Remote Enable non abilitato abilitato 7.3 Controllo tramite Modbus L’unità è predisposta per comunicare via Modbus RTU su RS485. Per le specifiche contattare il servizio clienti.
  • Page 13: Descrizione Dei Componenti

    8.2 Descrizione dei Componenti Ventilatori I ventilatori sono costituiti da motori a rotore esterno di tipo EC che possono essere controllati continuamente ciascuno tra il 10-100%. I cuscinetti a sfera rimangono lubrificati per tutta la loro durata e non necessitano di manutenzione. Se necessario è possibile scollegare e sostituire i ventilatori con estrema facilità. Filtri L’unità é provvista di 2 filtri di tipo G4 posti sul lato immissione ed estrazione. Durante le operazioni di manutenzione ordinaria essi necessitano di essere puliti regolarmente (e sostituiti se intasati). I filtri di ricambio possono essere acquistati presso il vostro installatore o rivenditore.
  • Page 14: Manutenzione Straordinaria

    8.4 Manutenzione straordinaria ATTENZIONE Assicurarsi che l’interruttore generale dell’impianto sia spento prima di qualsiasi operazione di installazione, manutenzione ordinaria o straordinaria o collegamento elettrico! ATTENZIONE L’installazione e la manutenzione dell’unità e del sistema di ventilazione completo devono essere eseguite da un installatore autorizzato e in conformità...
  • Page 15: Risoluzione Guasti

    • Pulire i ventilatori ogni anno con un aspirapolvere. La necessità di eseguire questa operazione può variare da caso in caso a seconda delle condizioni ambientali interne ed esterne. Non rimuovere mai le graffette di bilanciatura presenti sul motore (Fig. 8.e-h-k). Fig. 8.k 8.5 Risoluzione guasti I ventilatori non si attivano 1. Verificare che l’unità sia sotto tensione. 2. Verificare che tutti i collegamenti funzionino correttamente (collegamenti nella scatola collegamenti elettrici e al gruppo dei ventilatori in immissione ed estrazione). Indicatori led accesi su controllo remoto CTRL-V1 1.Vedere specifiche di paragrafo 7 Volume d’aria ridotto...
  • Page 16 SITALI CXRA 120 Heat Recovery Ventilation Unit Read this manual carefully before using the product and keep it in a safe place for reference as necessary. This product was constructed up to standard and in compliance with regulations relating to electrical equipment and must be installed by technically qualified personnel. The manufacturer assumes no responsibility for damage to persons or property resulting from failure to observe the instructions contained in this manual. 1 INDEX 1 Index 2 Precautions 3 Product information 3.1 General...
  • Page 17 3.1 General This is the Installation, Use and Maintenance Manual of the heat recovery ventilation units, model SITALI CXRA 120. This manual consists of basic information and recommendations concerning installation, commissioning, use and service operations to ensure a proper fail-free operation of the unit. The key to proper, safe and smooth operation of the unit is to read this manual thoroughly, use the unit according to given guidelines and follow all safety requirements. The SITALI CXRA 120 is supplied with the CTRL-V1 remote control panel.
  • Page 18 3.2 Dimensions and Weight SUPPLY EXAUST INSERIRE OUTSIDE RETURN VISTA CON FILTRI E SCAMBIATORE TRATTEGGIATI E SIMBOLI DEI VARI Condensation (COME DA ETICHETT CONDENSATION drainage DRAIN Ø16 Weight Kg 11,5 DETAIL A SUPPLY EXAUST DETAIL A Dimensions in mm Fig.3.a 3.3 Duct connections CONDENSATION DRAIN Ø16...
  • Page 19 5 INSTALLATION WARNING Make sure that specific warnings and cautions in Chapter 2 are carefully read, understood and applied! This section describes how to install the unit correctly. The unit must be installed according to these instructions. 5.1 Unpacking Verify that the unit (and eventual accessories) delivered is according to order before starting the installation. Any discrepancies from the ordered equipment must be reported to the supplier. 5.2 Where/how to install • All SITALI units are meant for indoor installation in a heated space. • Mount the unit on flat surface.
  • Page 20 5.a Prepare the surface where the unit is to be mounted. Make sure that the surface is flat, leveled and that it supports the weight of the unit. Perform the installation in accordance with local rules and regulations. 5.b It is important that the unit is tilted by 2° in order for the condensate drain to function properly: use the spacers supplied which must be mounted on the fixing brackets of the side with the condensate drain. Use appropriate plugs and rods or screws (not supplied) to fix the unit to the ceiling. It is recommended to fit the unit with anti-vibration mounts (not supplied). 5.c Connect the drain connection to the drainage hole. Make sure of water and air tightness of all connections. It is recommended to use a U-bend (or similar) in the condensation drainage pipe.
  • Page 21 5.4 Precabled electric connections WARNING Make sure that the mains supply to the unit is disconnected before performing any installation, service, maintenance or electrical work! WARNING The installation and service of the unit and complete ventilation system must be performed by an authorized installer and in accordance with local rules and regulations. The unit must be earthed. The unit is wired internally from factory. Unit comes pre-wired with: - power supply cable (3-core: brown, blue, yellow/green). - control cable, for connection to CTRL-V1 supplied (6-core: brown, yellow, white, green, grey, pink). Factory setting: speed 1 at 40%, speed 2 at 70% and speed 3 at 100%. CONTROL POWER SUPPLY CTRL-V1 Fig. 5.h Precabling Fig. 5.i CTRL-V1 (supplied as standard)
  • Page 22 5.5 Additional electric connections WARNING Make sure that the mains supply to the unit is disconnected before performing any installation, service, maintenance or electrical work! WARNING The installation and service of the unit and complete ventilation system must be performed by an authorized installer and in accordance with local rules and regulations. The units must be earthed. The unit is wired internally from factory. To connect the the CTRL-V1 to the mother board use a 6-core cable: 30m max length. Figures below show the wiring diagram. TRANSFORMER YELLOW/GREEN BLUE BROWN Input (Air Quality e.g. SEN-HY) CTRL-V1 Fig. 5.j Electrical connections on the motherboard fitted in the terminal box. Inputs/commands N°1 AC supply connector.
  • Page 23 6 COMMISSIONING 6.1 Setting Fan speed The speed of the unit can be adjusted during installation according to required ventilation rate, by setting the relevant dip switch. Figure 6. a below shows performance curve at different settings of the 0-10V signal to the motors. Consumption refers to the 2 motors. Table 6. b indicates the efficiency of the heat exchanger and of the condensation produced in different climatic conditions, to help the installer or the designer of the ventilation system to decide if to connect one or both condensation drainages. High production of condensation is the direct consequence of a high efficiency level as well as of the humidity rate.
  • Page 24 Lw dB - SOUND POWER OCTAVE BAND Lp dB(A) LwA dB(A) Speed 100% Lw dB - SOUND POWER OCTAVE BAND Lp dB(A) LwA dB(A) Speed 80% Lw dB - SOUND POWER OCTAVE BAND Lp dB(A) LwA dB(A) Speed 60% Lw dB - SOUND POWER OCTAVE BAND Lp dB(A) LwA dB(A) Speed 40% Lw dB - SOUND POWER OCTAVE BAND Lp dB(A) LwA dB(A) Speed 20%* < 9 Tabella 6.c Sound level: dB(A) figures are average spherical free-field, for comparitive use only. *measurements compared with chamber background noise. 6.2 Before Starting the System When the installation is finished, check that: • Filters are mounted correctly.
  • Page 25 7.1 3-speed operation with CTRL-V1 remote controller (supplied as standard) to activate/deactivate the unit to change the speed to change the speed to manually activate the Boost function to reset the filter alarm green led: speed 1 indicator green led: speed 2 indicator green led: speed 3 indicator blue led: anti-frost activation indicator red led: malfunction indicator yellow led: filter maintenance/replacement indicator yellow led: keypad lock indicator Fig. 7.b CTRL-V1 TOUCH FUNCTIONALITY DESCRIPTION ICON BUTTON...
  • Page 26 7.2 Remote Enable It allows to activate/deactivate the unit from remote by means of a volt-free contact by connecting the In1 input as per fig.5.j. To enable this function it is necessary to act on dip switch 8. DIP8 Remote Enable disable enable 7.3 Modbus control The unit can be controlled via Modbus (Modbus RTU over RS485). For specification, contact our customer service. 8 MAINTENANCE AND SERVICE WARNING Make sure that specific warnings and cautions in Chapter 2 are carefully read, understood and applied! Maintenance can be carried out by the user. Service must be performed only by an authorized installer and in accordance with local rules and regulations. Questions regarding installation, use, maintenance and service of the unit should be answered by your installer or place of purchase! 8.1 Components list...
  • Page 27 8.2 Description of Components Fans The fans have external rotor motors of EC type which can be steplessly controlled individually between 10-100%. The motor bearings are life time lubricated and maintenance free. It is possible to easily disconnect and replace the fans if necessary. Filters The 2 filters are of filter quality G4 for both the supply air and extract air filter. The filters need to be cleaned regularly (and replaced when polluted) during maintenance. New sets of filters can be acquired from your installer or wholesaler. Heat exchanger The unit is equipped with a highly efficient, counter-flow plate heat exchanger. Supply air temperature is therefore normally maintained without adding additional heat. The heat exchanger is removable for cleaning and maintenance during service. Condensation drainage Depending on the relative humidity in the extract air, condensation may occur on the cold surfaces of the heat exchanger (Table. 6.b). The condensate water is led out through drainage pipe. Thermistor Temperature probe to implement temperature dependent functions.
  • Page 28 8.4 Service WARNING Make sure that the mains supply to the unit is disconnected before performing any installation, service, maintenance or electrical work! WARNING The installation and service of the unit and complete ventilation system must be performed by an authorized installer and in accordance with local rules and regulations. • Keep the unit surface free from dust. • Once every 3 months (fixed period), the unit warns the user to perform the filter maintenance (Fig. 7.b - ). The actual need to perform this operation may vary depending on indoor and outdoor ambient conditions. • Clean the filters every 3 months with a vacuum cleaner (Fig. 8.e-f-g). • Press the CTRL-V1 button (Fig. 7.b) to reactivate the filter alarm. • Replace the filters every year. MANUTENZIONE ORDINARIA Fig. 8.e Fig.
  • Page 29: Fiche Tecnica Erp

    • Clean the fans every year with a vacuum cleaner. This may differ per situation depending on internal and external environmental conditions and on frequency of filter cleaning. Do not move the balance clips of the fan (Fig. 8.e-h-k). Fig. 8.k 8.5 Troubleshooting Fans do not start 1. Check that main supply gets to the unit. 2. Check that all connections are working (all connections in terminal box and fast couplings of intake and exhaust air fans). Led on CTRL-V1 lights on 1.Check paragraph 7 Reduced airflow 1.
  • Page 30 10. Direttiva ErP - Regolamenti 1253/2014 - 1254/2014 ErP Directive - Regulations 1253/2014 - 1254/2014 a) Marchio - Mark OLIMPIA SPLENDID b) Modello - Model SITALI CXRA 120 c) Classe SEC - SEC class c1) SEC climi caldi - SEC warm climates kWh/m -14,1...
  • Page 31 NOTE...
  • Page 32 Olimpia Splendid SpA Via Industriale 1/3, 25060 Cellatica (BS) www.olimpiasplendid.it - info@olimpiasplendid.it I dati tecnici e le caratteristiche estetiche dei prodotti possono subire cambiamenti. Olimpia Splendid si riserva di modificarli in ogni momento senza preavviso. 005844 - 00 - 1122...