AYK550-UH User's Manual
Commissioning the Override Mode:
1. Enter the parameters in all groups as needed, except group 17.
2. Select the digital input that will activate override mode P1701.
3. Enter the frequency or speed reference for override mode, P1702 and P1703,
according to the motor control mode P9904.
4. Enter the pass code P1704 (358).
5. Enable the override mode P1705.
Changing the Override Parameters:
1. If override mode is already enabled, disable it:
• Enter the pass code P1704.
• Disable the override mode P1705.
2. If needed, load the override parameter set P9902.
3. Change the parameters as needed, except group 17.
4. Change the parameters in group 17 as needed:
• Digital input for override mode P1701.
• Frequency or speed reference, P1702 or P1703.
5. Enter the pass code P1704.
Enable the override mode P1705. The drive replaces the override parameter set with
new values of all parameters.
Code
Description
1701
OVERRIDE SEL
Selects the source of the override activation signal.
0 =
– Override activation signal not selected.
NOT SEL
1 =
1 – Defines digital input DI1 as the override activation signal.
DI
• This digital input must be activated for override activation signal.
2...6 =
2...
DI
DI
• See DI1 above.
(-1) =
1(
) – Defines an inverted digital input DI1 as the override activation signal.
DI
INV
(-2)...(-6) =
2(
DI
• See
1(
DI
INV
1002
PAR PFC IOCONF
1003
PAR AI SCALE
1004
PAR AO SCALE
1006
PAR EXTROMISSING
1007
PAR FBUSMISSING
1008
PAR PFCWOSCALAR
Group 17: Override
Range
-6...6
6 – Defines digital input DI2...DI6 as the override activation signal.
)...
6(
) – Defines an inverted digital input DI2...DI6 as the override activation signal.
INV
DI
INV
) above.
Resolution
DefaultS
1
0
YORK Default
DI6
78
Start-Up