York AYK 550 User Manual page 44

Air modulators
Hide thumbs Also See for AYK 550:
Table of Contents

Advertisement

40
Internal Timer with Constant Speeds / PRV
This macro configures for applications such as a timed powered roof ventilator
(PRV) which alternates between two constant speeds (constant speed 1 and 2)
based on a built-in timer.
Momentarily activating digital input 3 (DI3) provides a boost function which operates
the motor. See group 36, Timer Functions, for more information on setting up timers.
mA
9902
1002
1103
1106
1201
1301
1401
1601
1609
3207
3415
Start-Up
X1
Signal cable shield (screen)
1
SCR
External reference 0(2)...10 V or 0(4)...20 mA
2
AI1
+
Analog input circuit common
3
AGND
Reference voltage 10 VDC
4
10V
Not configured
5
AI2
Analog input circuit common
6
AGND
Output frequency: 0(4)...20 mA
7
AO1
mA
8
AO2
Output current: 0(4)...20 mA
9
AGND
Analog output circuit common
Auxiliary voltage output +24 VDC
10 24V
Common for DI return signals.
11 GND
Digital input common for all
12 DCOM1
Timer enable: Activate to start/stop drive from timer
13 DI1
Run permissive: Deactivate to stop drive (P 1601)
14 DI2
Timer override: Activate to start drive
15 DI3
Safety interlock 1: Deactivate to stop drive (P 1608)
16 DI4
Safety interlock 2: Deactivate to stop drive (P 1609)
17 DI5
Not configured
18 DI6
19 RO1C
Relay output 1 (P 1401)
Default operation: Started =>19 connected to 21
20 RO1A
21 RO1B
22 RO2C
Relay output 2 (P 1402)
Default operation: Running =>22 connected to 24
23 RO2A
24 RO2B
25 RO3C
Relay output 3 (P 1403)
Default operation: Fault (-1) =>25 connected to 27
26 RO3A
27 RO3B
Parameters Changed Relative to HVAC Default
Parameter
9 (
APPLIC MACRO
INT TIMER CS
2
0 (
EXT
COMMANDS
NOT SEL
1
0 (
REF
SEL
KEYPAD
3
2 (
REF
SEL
AI
15 (
CONST SPEED SEL
TIMER
1
0.0%
MINIMUM AI
1
7 (
RELAY OUTPUT
STARTED
2 (
RUN ENABLE
DI
2
5 (
START ENABLE
DI
3
0103 (
SUPERV
PARAM
3
0105 (
SIGNAL
PARAM
(Fault => 25 connected to 26)
Value
)
3416
SIGNAL
)
3417
SIGNAL
)
3419
OUTPUT
2)
3420
OUTPUT
1)
3421
OUTPUT
3622
BOOST SEL
)
4001
GAIN
2)
4002
INTEGRATION TIME
5)
4101
GAIN
)
4102
OUTPUT FREQ
INTEGRATION TIME
)
4110
TORQUE
SETPOINT SEL
AYK550 User's Manual
J1
Jumper Settings
AI1: 0(2)
AI2: 0(4)
Parameter
3
-200.0%
MIN
3
200.0%
MAX
3
4 (%)
DSP UNIT
3
-200.0%
MIN
3
200.0%
MAX
3 (
3)
DI
1.0
60.0 s
1.0
60.0 s
1 (
1)
AI
...
10 V
...
20 mA
Value

Advertisement

Table of Contents
loading

Table of Contents