Page 2
WARNING: This product can expose you to chemicals, including carbon monoxide and benzene, which are known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65warnings.ca.gov WARNING: Breathing diesel engine exhaust exposes you to chemicals known to the State of California to cause cancer and birth defects or other reproductive harm.
Safety Precautions and Instructions IMPORTANT SAFETY INSTRUCTIONS. Electromechanical equipment, including generator sets, transfer switches, switchgear, and accessories, can cause bodily harm and pose life-threatening danger when improperly installed, operated, or maintained. To prevent accidents be aware of potential dangers and act safely. Read and follow all safety precautions and instructions. SAVE THESE INSTRUCTIONS.
Page 8
WARNING Explosion. Can cause severe injury or death. Relays in the battery charger cause arcs or sparks. Locate the battery in a well‐ventilated area. Isolate the battery charger from explosive fumes. Battery electrolyte is a diluted sulfuric acid. Battery acid can cause severe injury or death. Battery acid can cause blindness and burn skin.
Page 9
Exhaust System WARNING Carbon monoxide. Can cause severe nausea, fainting, or death. The exhaust system must be leakproof and routinely inspected. Generator set operation. Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide is an odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Avoid breathing exhaust fumes when working on or near the generator set.
Page 10
Gas fuel leaks. Explosive fuel vapors can cause severe injury or death. Fuel leakage can cause an explosion. Check the LPG vapor or natural gas fuel system for leakage by using a soap and water solution with the fuel system test pressurized to 6– 8 ounces per square inch (10–14 inches water column).
Page 11
Installing the battery charger. Hazardous voltage will cause severe injury or death. An ungrounded battery charger may cause electrical shock. Connect the battery charger enclosure to the ground of a permanent wiring system. As an alternative, install an equipment grounding conductor with circuit conductors and connect it to the equipment grounding terminal or the lead on the battery charger.
Page 12
WARNING Hot engine and exhaust system. Can cause severe injury or death. Do not work on the generator set until it cools. Servicing the alternator. Hot parts can cause severe injury or death. Avoid touching the alternator field or exciter armature. When shorted, the alternator field and exciter armature become hot enough to cause severe burns.
Wiring diagram manuals are available separately. Refer to the engine operation manual for generator set engine scheduled maintenance information. Information in this publication represents data available at the time of print. Kohler Co. reserves the right to change this publication and the products represented without notice and without any obligation or liability whatsoever.
Page 14
List of Related Materials Separate literature contains communication and software information not provided in this manual. Figure 1 lists the available literature part numbers. Literature Description Literature Part No. APM402 Controller Spec Sheet G6-161 ® Decision-Maker 3000 Controller Spec Sheet G6-100 Multiple Part Numbers Contact Generator Set/Controller Wiring Diagram Manual...
(86) 10 6518 7950 Visit the Kohler Co. website at KOHLERPower.com. (86) 10 6518 7951 Look at the labels and decals on your Kohler product (86) 10 6518 7952 or review the appropriate literature or documents Fax: (86) 10 6518 7955 included with the product.
Section 1. Specifications and Features 1.1 Introduction The spec sheets for each generator set provide model-specific generator and engine information. The controller spec sheet provides specifications for this controller. Refer to the respective spec sheet for data not supplied in this manual. Refer to the generator set service manual, installation manual, engine operation manual, and engine service manual for additional specifications.
1.2.1 Switches and Controls Note: US/Metric Display is selectable in the Generator Set System Menu. See the section titled: Digital Display-Generator Set System Menu. Alarm Horn. The alarm horn alerts the operator or other attendants that a shutdown or warning condition exists. Alarm (Horn) Silence.
1.2.2 Annunciator Lamps The controller has a single annunciator fault lamp providing visual generator set status. In addition, each button has a corresponding lamp. See Figure 3. Lamp/Button Lamp color Alarm (Fault) Lamp Yellow (Warning) or Red (Shutdown) Off/Reset Button Auto Button Green (System Ready) Run Button...
Page 20
Input/output communication loss Low battery voltage Low coolant temperature Low cranking voltage Low engine oil level * Low fuel (level for diesel-powered models) * Low fuel (pressure for gas-powered models) * Low oil pressure ...
(GM/PSI and Doosan gas-powered models only) Metering communication loss No coolant temperature signal No oil pressure signal Overcrank Overfrequency Overvoltage (each phase) Run relay overload Underfrequency Undervoltage (each phase) (Voltage) regulator communication loss * Requires optional input sensors 1.2.3 Digital Display...
Page 22
Digital Outputs Analog Inputs Event Log Volt Select Overview Menu When a new shutdown or warning fault occurs, the auto-paging display feature activates. Active Shutdowns display if any are present. This alerts the user to single or multiple shutdown fault conditions. See the section titled: Annunciator Lamps—System Shutdown Fault Lamp for a list of possible shutdown faults.
Page 23
Battery displays the DC voltage of the engine starting battery(ies). This value also shows in the Overview Menu. Fuel Pressure displays fuel pressure for some engines. Refer to the Appendix, Controller Displays from the Engine ECM. This value also shows in the Overview Menu. Generator Metering Menu Total Power kVA and kW displays alternator output as actual output values.
Page 24
Generator Set Run Time Menu Engine Run Time displays the total run time hours. This value also shows in the Overview Menu. Engine Loaded displays the total loaded hours. Engine Starts displays the total number of generator set startup events. Total Energy displays the total kW hours.
Page 25
If the unit is running and Yes is entered when the Enter Calib? is shown, the display will show the following values for three- phase generator sets. Single-phase generator sets will only display items marked (*). Volts L1-L2 * ...
Page 26
Digital Inputs Menu This menu allows the user to review the settings. There are up to three digital inputs that are programmer selectable if not reserved by factory options. The displays for digital inputs appear as shown below with Values true or false. Items shown in the digital display as True are active.
Page 27
Event Log Menu This menu allows the user to review up to 1000 entries of system events including shutdown faults, warning faults, and status events. See the section titled: Controller Fault Diagnostics for a list of the items that appear on the Event Log. Volt Select Menu Note: The generator set must be stopped before changing the voltage selection.
1.2.4 Controller Fault Diagnostics This table provides descriptions of the system events and their types—warning, shutdown, status, and notice. Warnings show yellow fault lamp and signal an impending problem. Shutdowns show red fault lamp and stop the generator set. Status is an event that is not an alert but is part of the event history. Notice is an alert that is NOT part of the event history. System events are available as a Relay Output as shown.
Page 29
Warning Shutdown Status/ Relay Description Display Message Function Function Notice Output General Functions Alarm horn silenced (Alarm Silence LED only) Alarm silence, auto only (NFPA 110) or always AlrmSilence: Auto Only or AlrmSilence: Always Aux. inputs 0- 5 VDC, 1 analog Aux Input Warning (2 additional inputs available with I/O module option) Aux.
1.2.5 Digital Display Circuit Board and Connections The digital display circuit board provides: The backlit LCD (liquid crystal display) for monitoring the generator set functions and output values Master control switches with status lights Fault lamp Pushbutton/rotary selector dial to navigate the generator set displays ...
1.2.6 Main Logic Circuit Board The main logic circuit board provides the terminal strips and connection sockets to connect the controller to the engine/generator, input/output connections, optional I/O module kit, and circuit protection fuses. See Figure 5 and Figure 6 for the circuit board connections.
1.2.8 Communication Ports ® The main logic circuit board contains a single mini USB communication port for PC connections, see Figure 7. For Modbus communication using RS-485, see the figure titled: Main Circuit Board Connectors (P21). Refer to the List of Related Materials in the Introduction for corresponding SiteTech™...
V7/V8/V9 fuses, 1.5 Amp. (qty. 3) GM69407 Figure 8 AC Circuit Fuses in Control Box F2 1 Amp. auto-resettable F3 12 Amp. non-replaceable F1 1 Amp. auto-resettable GM6435-C Figure 9 Controller DC Fuses 1.3 Controller Logic Specifications The controller logic specifications section is an overview of the various features and functions of the controller. Certain features function only when optional accessories are connected.
1.3.1 Status Event and Fault Specifications The Factory-Defined Settings List contains all status events and faults with ranges and time delays including items that do not have user adjustments. Note: The engine ECM may limit the crank cycle even if the controller is set to a longer time period. Factory-Defined Settings List GenSet Fault...
Page 36
GenSet Fault Write Mode Time Default Controller Lamp Access Always Delay Time Display Alarm Warning Display Running Range Default Range Delay Description Message Horn Shutdown SiteTech Stopped Setting Selection (sec.) (sec.) Low cranking voltage Lo Crank Vlt Fixed Fixed Warning Low engine oil level * Oil Level Low Warning...
Page 37
GenSet Fault Write Mode Time Default Controller Lamp Access Always Delay Time Display Alarm Warning Display Running Range Default Range Delay Description Message Horn Shutdown SiteTech Stopped Setting Selection (sec.) (sec.) Chicago Code Chicago code active * Active Common Fault Common fault Shutdwn Common...
Page 38
GenSet Fault Write Mode Time Default Controller Lamp Access Always Delay Time Display Alarm Warning Display Running Range Default Range Delay Description Message Horn Shutdown SiteTech Stopped Setting Selection (sec.) (sec.) Alternator protection Alt Protect Shutdwn Ground fault input * Ground Fault Warning kW overload...
Page 39
GenSet Fault Write Mode Time Default Controller Lamp Access Always Delay Time Display Alarm Warning Display Running Range Default Range Delay Description Message Horn Shutdown SiteTech Stopped Setting Selection (sec.) (sec.) Charger Depleted Battery 4–12 Voltage Target (12 V) (12 V) 18–24 (24 V) (24 V)
Page 40
GenSet Fault Write Mode Time Default Controller Lamp Access Always Delay Time Display Alarm Warning Display Running Range Default Range Delay Description Message Horn Shutdown SiteTech Stopped Setting Selection (sec.) (sec.) Charger Voltage Absorption (V) 13–15 14.25 (12 V)** (12 V) 26–30 28.5 (24 V)**...
1.3.2 Voltage Regulator and Calibration Specifications The controller has a voltage regulation function that is internal to the processor. This means that no external voltage regulator is necessary. The voltage regulation of the controller uses root mean square (rms) sensing for fast response to changes in indicated and regulated voltages resulting in excellent regulation accuracy.
Section 2. Operation 2.1 Prestart Checklist To ensure continued satisfactory operation, perform the following checks or inspections before or at each startup, as designated, and at the intervals specified in the service schedule. In addition, some checks require verification after the unit starts. DANGER Hazardous voltage.
2.2 Exercising Generator Set DANGER Hazardous voltage. Moving parts. Will cause severe injury or death. Operate the generator set only when all guards and electrical enclosures are in place. Operate the generator set under load once each week for one hour. Perform the exercise in the presence of an operator when the generator set does not have an automatic transfer switch with an exercise option.
2.4.1 Starting Local Starting Press the master control RUN button to start the generator set at the controller. Note: The alarm horn sounds and the Not-In-Auto Warning display appears whenever the generator set master control button is not in the AUTO mode. Button Generator Alarm...
2.4.2 Stopping (User Stopping and Fault Shutdown) Normal Stopping Run the generator set without load for 5 minutes to ensure adequate engine cooldown. The controller has a programmable cooldown timer that functions only when the master control button is in the AUTO mode. To stop the generator set, press the generator set master control OFF/RESET button and wait until the generator set comes to a complete stop.
Page 47
Use the Silence Alarm button to silence the alarm horn at the operator’s discretion. If the controller is setup for an NFPA 110 application, press the AUTO button before silencing the alarm horn. The alarm horn cannot be silenced unless the master control button is in the AUTO mode. See the section titled: Status and Notice Digital Displays for more information.
specifications. The high battery voltage feature monitors the battery and battery charging system in the generator set operating and off modes. Engine Electrical System Voltage High Battery Voltage Range High Battery Voltage Default Setting 13.2- 16.2 26.4- 32.4 Figure 11 High Battery Voltage Specs High Coolant Temperature.
Page 49
If the controller is set up for an NFPA 110 application, press the AUTO button before silencing the alarm horn. The alarm horn cannot be silenced unless the master control button is in the AUTO mode. See the section titled: Status and Notice Digital Displays for more information.
Page 50
High Coolant Temperature. The fault lamp illuminates red, the alarm horn sounds, and the unit shuts down because of high engine coolant temperature. The high coolant temperature shutdown does not function during the preset inhibit time delay period after startup. The local display shows Coolnt Temp High Shutdwn. Note: The high engine temperature shutdown function and the low coolant level shutdown function are independent.
Page 51
Overvoltage (Each Phase). The fault lamp illuminates red, the alarm horn sounds, and the unit shuts down when the voltage exceeds the overvoltage setting for the preset time delay period. The local display shows Volts (L1- L2, L2- L3, or L3- L1) High Shutdwn.
Chicago Code Active. This notice message indicates that the controller is locked in AUTO mode. This feature requires a digital input assigned to Chicago Code Active. A Kohler authorized distributor or dealer can use SiteTech™ software to assign a digital input to Chicago Code Active. When the digital input is active, the local display shows Chicago Code Active.
Page 53
The user can individually calibrate the values above or reset all of them. The local display Reset all calib? No or Yes. Select No to make no changes and exit GenSet Calibration. Select Yes to reset all of the values. When calibrating voltage, the metered value and the number being entered as the calibrated value must be within 10% of the system operating voltage.
2.4.8 Controller Resetting (Following System Shutdown or Warning) Use the following procedure to restart the generator set after a system shutdown or to clear a warning lamp condition. This procedure includes the resetting of the optional remote annunciator. Refer to the section titled: Emergency Stop Switch Reset Procedure, to reset the generator set after an emergency stop. Disconnect the generator set load using the line circuit breaker or automatic transfer switch.
Update the firmware to version 3.10 or higher using a PC with SiteTech™ software. Access Service Support on the Kohler Power Resource Center (KPRC) for the firmware update. Refer to the SiteTech™ Software Operation Manual TP-6701 as needed. Use the following information to determine the controller firmware version and perform the engine ECM power up procedure.
Page 56
Powered Figure 20 ECM Powered Display After several seconds, the display will change to provide the option to power down the controller. See Figure 21. ECM powered Push to Stop Figure 21 ECM Power Down Display If desired, press the selector dial to power down the engine ECM. Rotate the selector dial to navigate to any of the available menus.
2.5 Menu Displays Use the Menu Summary List section after reading and understanding the features of the pushbutton/rotary selector dial. See the section titled: Graphical Display. The Menu Summary List provide a quick reference to the digital display data. Some digital display data may not be identical to your display due to generator set application differences.
Page 58
Menu Summary List Continued (Legend: ● First level submenu, ○ second level submenu) Voltage Regulator Menu (DEC3000 before Digital Inputs Menu Analog Inputs Menu Event Log Menu Version 3.0.25) Enter Voltage Regulator? DIn A1 AIn A1 (factory See the section titled: ...
2.6 Monitoring and Programming Setup The user programmer can access the controller data with the controller digital display or a personal computer (PC) with optional SiteTech™ software to monitor and/or program. Access the controller system with a PC using a USB cable with a mini USB plug.
2.6.2 Modbus® Communications ® ® The controller communicates using Modbus as a slave connection with the Modbus master initiating the communication. The ® controller seeks the system and alternator parameters and diagnostic information then responds back to the Modbus master. In addition, the controller accepts information to alter controller parameters including generator set starting and stopping.
Page 61
Controller Controller SiteTech Menu Name Viewable Adjustable Adjustable Overview Engine Metering Generator Metering GenSet Information GenSet Run Time GenSet System Voltage Regulation Digital Inputs Digital Outputs Analog Inputs Event Log Volt Select * Requires initial activation using SiteTech™ Figure 27 Displays for Viewing and Adjusting (DEC3000 Firmware Version 3.0.25 to 4.8.4) Controller Controller...
2.7.1 Error Messages Certain entries or attempted entries may cause the controller to display an error message. Some of the error messages shown here are also shown as part of the section titled: System Fault Warning Lamp with Digital Displays and the section titled: System Fault Shutdown Lamp with Digital Displays.
2.7.2 Overview Displays basic and commonly sought after information about the generator set. This information scrolls automatically after about 5 minutes of no user input (pushbutton/rotary selector dial or button activity). To change from auto scrolling to fixed display, press the rotary dial and the main menu will appear. Press the rotary dial again to select the first menu item Overview.
Overview (Fixed Display) Overview - - > ### V ##.# Hz ##.# hr ### A #### kW English Display ###_F ###% Measurements - > ### PSI ##.# V Metric Display ###_ C ##.# % Measurements - > #.# MPa ##.# V CHG1: ##.#V With 10 Amp Charger ##.# A...
Page 65
To enable calibration, start the generator set and select the Volts L1-L2 display. Then push and hold the pushbutton/rotary selector dial until the Calibration Enabled popup appears. Calibration of each display is now available. The display will show the following values for three-phase generator sets. Single-phase generator sets will only display items marked (*). ...
Page 66
Momentarily press the pushbutton/rotary selector dial. Stop the generator set if not already done. Generator Metering APM402 firmware versions before Generating - - > Total Power: Metering V1.6.3 show the power in VA and W. # kVA Total Power: # k W Rated Power: Select this Display to Enable or Disable...
2.7.5 GenSet Information Displays generator set and controller information. Displayed data is factory entered. GenSet Information GenSet - - > Genset M/N: Information GenSet S/N: Cntrllr S/N: 2.7.6 GenSet Run Time Displays the generator set’s operating record including total run time loaded and unloaded, number of starts, and total energy kW hours GenSet Run Time GenSet - - >...
GenSet System GenSet - - > System System Freq: ##.# Hz SystemPhase: ##### System Volt: ###.# V Pwr Rating: ##.# kW Amp Rating: ##.# A Power Type: ##### Battery v: ## V Meas System User Selectable - > English or Metric Contrast User Selectable - >...
Page 69
GenSet Calibration GenSet - - > Enter Calib? GenSet - - > Calibration Calibration Enter Calib? User Selectable - > Volts L1- L2: #.# V Volts L2- L3: #.# V Volts L3- L1: #.# V Volts L1- N: #.# A Volts L2- N: #.# A Volts L3- N:...
2.7.9 Voltage Regulator ® Decision-Maker 3000 Controllers with Firmware Versions Before 3.0.25. Displays the voltage regulator adjustment value. All other voltage regulator adjustments are changed using SiteTech™ software. The voltage regulator value is reviewable at all times. In order to review the value when the generator set is NOT running, enter Yes when the Enter volt reg? is displayed.
2.7.10 Digital Inputs Displays the selected programming user-defined digital notice, warning, and shutdown inputs. These inputs provide a multitude of choices for configuring customized auxiliary inputs. See Figure 29 for a list of digital input choices. For descriptions of the inputs listed refer to the following sections: ...
Critical Analog and Digital High High High Inputs Notice Warning Warning Warning Warning Shutdown Shutdown Shutdown Auxiliary Input Battery Charger Fault Chicago Code Active Enclosure Temperature: High Shutdown (Din A3) Engine Fuel Level Fuel Tank Leak Ground Fault Low Engine Oil Level Low Fuel Pressure Figure 29 Analog and Digital Inputs...
Page 73
Digital Outputs Digital - - > DOut A1 Outputs ##### DOut A1 Value: True or False DOut B1 ##### DOut B1 Value: True or False DOut B2 ##### DOut B2 Value: True or False DOut B3 ##### DOut B3 Value: True or False DOut B4 ##### DOut B4...
Page 74
Critical No Signal High High High Shut- Shut- Shut- Digital Outputs Notice Warning Warning Warning Warning Shutdown down down down AC Sensing Lost Alternator Protection Auxiliary Input Battery Charger Fault Battery Voltage Chicago Code Active Common Fault Common Warning Cranking Voltage ECM Comm Loss Emergency Stop Engine Coolant Level...
2.7.12 Analog Inputs Displays the selected programming user-defined analog notice, warning, and shutdown inputs. These inputs provide a multitude of choices for configuring customized auxiliary inputs. See the figure titled: Analog and Digital Inputs for a list of analog input choices.
2.7.13 Battery Charger 1 and 2 WARNING Explosion. Can cause severe injury or death. Relays in the battery charger cause arcs or sparks. Locate the battery in a well‐ventilated area. Isolate the battery charger from explosive fumes. Battery gases. Explosion can cause severe injury or death. Incorrect use of the equalize charge state may lead to hazardous situations.
2.7.14 Event Log Displays up to 1000 stored status, warning, and shutdown events. After the first 1000 events, each additional new event replaces the oldest event. See the section titled: Controller Fault Diagnostics for a list of possible events. Event Log Event Log - - >...
Note: Have maintenance work, including battery service, performed by appropriately skilled and suitably trained maintenance personnel familiar with generator set operation and service. Kohler recommends the use of Kohler Genuine oil and filters for maintenance and service. TP-6694 6/22...
3.3 Service Schedule Action System—Component Visually Inspect Check Change Clean Test Interval Fuel System Day tank level Weekly Flexible lines and connections Weekly Fuel level switch Weekly Main tank supply level Weekly Solenoid valve operation Weekly Transfer pump operation Weekly ●...
Page 81
Action Visually Inspect Check Change Clean Test System—Component Interval AC Electrical System Controller lamp test Weekly General Inspection Weekly Circuit breakers, fuses† Monthly Wire abrasions where subject to motion Quarterly Safety and alarm operation Six Months Tighten control and power wiring Yearly connections Transfer switch main contacts†...
3.4 Alternator Bearing Service Have an authorized service distributor/dealer perform service. 3.4.1 20-300 kW Models Replace the end bracket bearing every 10,000 hours of operation. Service the bearing more frequently if the annual inspection indicates excessive rotor end play or bearing damage. The sealed end bracket bearing requires no additional lubrication. 3.4.2 300-1000 kW Models with 4M/5M/7M Single-Bearing Alternator The alternator bearing requires lubrication at intervals specified in the alternator operation and maintenance manual.
Close the fuel valves on each side of the fuel prime pump. 3.6 Gaseous Fuel Systems Gaseous fuel systems apply to KG_ (Kohler Powered), (REZG_/RZG_/ERES_ (GM/PSI Powered), REZX_/RZX_ (Doosan Powered) generator set models. This section describes natural gas and liquified petroleum gas (LPG) fuel systems that are not covered in the engine operation manual or engine service manual.
3.6.1 Gaseous Fuel System Concept (Single Fuel) The gaseous fuel system uses a fuel solenoid valve to control the fuel flow to the electronic-controlled pressure regulator (EPR) or direct acting electronic pressure regulator (DEPR). The generator set-mounted EPR or DEPR reduces the fuel pressure as fuel passes to the fuel mixer.
3.6.4 Fuel System Changeover Kits (Dual Fuel) A changeover fuel system kit provides automatic changeover from natural gas to LPG vapor. The primary and backup fuels each have a fuel solenoid valve. The primary fuel is natural gas; the backup fuel is LPG vapor. Before starting, both fuel solenoid valves are closed.
3.6.5 Fuel Conversion Connections To change the fuel type, change the wiring harness connections. The engine ECM has fuel tables and spark advance curves programmed for both natural gas and LPG. Use the following fuel connection tables and wiring diagrams to determine the applicable connections for your generator set model.
Page 87
Natural Gas LPG Vapor To ECM To ECM controller controller LPG Liquid To ECM controller Auto Changeover Natural Gas and LPG Vapor To ECM controller ADV-7600B-F Figure 34 Gaseous Fuel Connections Wiring Diagram, Typical 25-45 kW Models with PSI or GM Engines TP-6694 6/22...
Page 88
50-150 kW Models See Figure 35 and Figure 36. Natural Gas Connections Disconnect lead 65 from lead N5. Disconnect leads 70G, 73B, and N8 from fuel solenoid valve FV2 (LPG vapor). Connect leads 70E, 73A, and 73B to fuel solenoid valve FV1 (NG). LPG Vapor Connections ...
Page 89
LPG Vapor Natural Gas To ECM To ECM controller controller LPG Liquid To ECM controller Auto Changeover Natural Gas and LPG Vapor To ECM controller ADV-8557 Figure 36 Gaseous Fuel Connections Wiring Diagram, Typical 50-150 kW Models with PSI or GM Engines TP-6694 6/22...
Page 90
For KG40, KG45, KG50, KG60 (Kohler Engine KG6208), use the following: See Figure 37 and Figure 38. Natural Gas Operation Disconnect 78/78a and 70G/70R from the fuel valve. Disconnect 49 and N17. Connect 77/77a and 70H/70T to the fuel valve.
Page 91
Natural Gas LPG Vapor To ECM To ECM controller controller Auto Changeover Natural Gas and LPG Vapor To ECM controller To ECM controller ADV-9774D-C Figure 38 Gaseous Fuel Connections Wiring Diagram, KG40–KG60 (KG6208) TP-6694 6/22...
Page 92
For KG80–KG125, KG80R–KG125R (Kohler Engines KG6208TSD and KG6208THD), use the following: See Figure 39 and Figure 40. Natural Gas Operation Disconnect the black fuel connector (J7). Disconnect 49 and N17. Connect the white fuel connector (J8). ...
Page 93
Natural Gas LPG Vapor To ECM To ECM controller controller Auto Changeover Natural Gas and LPG Vapor To ECM controller ADV-9052D-D Figure 40 Gaseous Fuel Connections Wiring Diagram, KG80–KG125/KG80R–KG125R TP-6694 6/22...
Page 94
KG80–KG125, KG80R–KG125R Dual Fuel Operation The dual fuel system for the KG80–KG125 and KG80R–KG125R includes an LPG indicator light and a reset switch. This LPG indicator light turns on when the NG fuel valve closes and the LP fuel valve opens, indicating that the fuel source has switched. The reset switch resets the fuel source to natural gas.
Page 95
For KG150, KG180, and KG200 (Kohler Engines KG10V08T-6CGS and KG10V08T-6DGS), use the following: To change the fuel type, change the wiring harness connections. The engine ECM has fuel tables and spark advance curves programmed for both natural gas and LPG. Use the following fuel connection tables and wiring diagrams to determine the applicable connections for your generator set model.
Page 96
Natural Gas LPG Vapor To ECM and To ECM and controller controller ADV-9116 Figure 43 Gaseous Fuel Connections Wiring Diagram, Single Fuel, KG150, KG180, and KG200 TP-6694 6/22...
Page 97
For 180-500 RZXB/REZXB/REZXC/RZXD/REZXD (PSI/ Doosan 11.1L, 14.6L, 18.3L, and 21.9L Engines), use the following: To change the fuel type, change the wiring harness connections. The engine ECM has fuel tables and spark advance curves programmed for both natural gas and LPG. Use the following fuel connection lists and wiring diagrams to determine the applicable connections for your generator set model.
Page 98
180-500 RZXB/REZXB/REZXC/RZXD/REZXD (PSI/ Doosan 11.1L, 14.6L, 18.3L, and 21.9L Engines) Natural Gas with Additional Fuel Valve, Required for UL Approval See Figure 45. Disconnect lead N5. Disconnect lead 65. Disconnect lead 65A. Disconnect lead 73B. Connect lead 70B2 to fuel valve 1 (FV1), red/black wire.
Page 99
Natural Gas 250 – 300 kW (14.6 L) 180 – 200 kW (11 L) ADV-7968-G ADV-7968-G 300 – 500 kW (18 – 22 L) ADV-7994-K Figure 45 Natural Gas with Additional UL Fuel Valve TP-6694 6/22...
Page 100
180-500 RZXB/REZXB/REZXC/RZXD/REZXD (PSI/ Doosan 11.1L, 14.6L, 18.3L, and 21.9L Engines) LPG Vapor or Liquid Withdrawal with Single Fuel Valve See Figure 46. Disconnect lead 70E. Disconnect lead N6. Disconnect lead N11 (250 – 500 kW). Disconnect lead 73A (180 – 200 kW). ...
Page 101
180-500 RZXB/REZXB/REZXC/RZXD/REZXD (PSI/ Doosan 11.1L, 14.6L, 18.3L, and 21.9L Engines) LPG Vapor or Liquid Withdrawal with Additional Fuel Valve, Required for UL Approval See Figure 47. Disconnect lead 73A (180 – 200 kW). Disconnect lead 73A and 73A1 (250 – 500 kW). ...
Page 102
LPG Vapor and Liquid Withdrawal UL Valve 180 – 200 kW (11 L) ADV-7968-G 250 – 300 kW (14.6 L) ADV-7970-G 300 – 500 kW (18 – 22 L) ADV-7994-K Figure 47 LPG Vapor or Liquid Withdrawal with Additional UL Fuel Valve TP-6694 6/22...
3.7 Crankcase Ventilation (CCV) Heater Kit GM78171-KP1 Applies to 125/150 kW, 8.1 L GM-powered and 8.8 L PSI-powered generator set models. Consult your local generator set distributor/dealer for additional information. The crankcase ventilation (CCV) heater kit provides a controlled heating source to the crankcase ventilation system preventing freezing water buildup during cold weather.
3.9 Cooling System The cooling system maintenance information applies to radiator-cooled models which have a radiator with a pressure cap and coolant recovery tank. WARNING Hot coolant and steam. Can cause severe injury or death. Before removing the pressure cap, stop the generator set and allow it to cool. Then loosen the pressure cap to relieve pressure.
Open the air-bleed petcocks, if equipped. Close the air-bleed petcocks when coolant begins to flow from them. Note: Refer to the engine operation manual for air-bleed petcock locations. Fill the cooling system with the recommended genuine Kohler coolant/antifreeze mixture based on the engine manufacturer’s recommendation. Replace the pressure cap.
11. Add coolant to bring the coolant level to just below the overflow tube opening of the filler neck. 12. Replace the pressure cap. 13. Maintain the coolant level in the coolant recovery tank (if equipped) between the high and low marks. Check the coolant level at the radiator fill on models without a coolant recovery tank.
Page 107
12-Volt 24-Volt To positive (+) terminal on starter solenoid. To ground (-) terminal on or near starter motor. EZ-273000-J Figure 50 Engine Electrical System Single Starter Motor Typical Battery Connection To positive (+) terminal on starter solenoid. To ground (-) terminal on or near starter motor.
3.10.1 Clean the Battery Clean the battery and cables and tighten the battery terminals according to the service schedule recommendations. Clean the battery by wiping it with a damp cloth. Keep the electrical connections dry and tight. If corrosion exists, disconnect the cables from the battery and remove the corrosion with a wire brush. Clean the battery and cables with a solution of baking soda and water.
3.10.3 Specific Gravity Check Use a battery hydrometer to check the specific gravity of the electrolyte in each battery cell of batteries with filler caps. Holding the hydrometer vertically, read the number on the glass bulb at the top of the electrolyte level or the number adjacent to the pointer.
3.10.4 Charge Battery Use a battery charger to maintain a fully charged battery when the generator set is used in a standby application. The engine battery-charging alternator charges the battery while the generator set is running. Refer to the battery charger operation manual for installation, operation, and service procedures.
Prepare the engine lubricating system for storage as follows. Note: Kohler recommends the use of Kohler genuine oil and filters. Run the generator set for a minimum of 30 minutes to bring it to normal operating temperature. Stop the generator set.
3.11.4.1 Internal Engine Components If you have access to a fogging agent or SAE 10 oil prepare the pistons and cylinders for storage as follows: While the engine is running, spray a fogging agent or SAE 10 engine oil into the air intake for about two minutes until the engine stops.
3.11.7 Battery WARNING Explosion. Can cause severe injury or death. Relays in the battery charger cause arcs or sparks. Locate the battery in a well‐ventilated area. Isolate the battery charger from explosive fumes. Perform battery storage after all other storage procedures. Confirm that the generator set is stopped.
Section 4. General Troubleshooting This section contains generator set troubleshooting, diagnostic, and repair information. Use the following charts to diagnose and correct common problems. First check for simple causes such as a dead engine starting battery or an open circuit breaker. The charts include a list of common problems, possible causes of the problem, recommended corrective actions, and references to detailed information or repair procedures.
4.1 General Troubleshooting Chart Exercise run time and/or event records inoperative Displays error message/locks up Excessive or abnormal noise High fuel consumption Low oil pressure Overheats Lacks power Stops suddenly No or low output voltage Starts hard Cranks but does not start Does not crank TP-6694...
Page 117
Exercise run time and/or event records inoperative Displays error message/locks up Excessive or abnormal noise High fuel consumption Low oil pressure Overheats Lacks power Stops suddenly No or low output voltage Starts hard Cranks but does not start Does not crank TP-6694 6/22...
Page 118
Exercise run time and/or event records inoperative Displays error message/locks up Excessive or abnormal noise High fuel consumption Low oil pressure Overheats Lacks power Stops suddenly No or low output voltage Starts hard Cranks but does not start Does not crank TP-6694 6/22...
Page 119
Exercise run time and/or event records inoperative Displays error message/locks up Excessive or abnormal noise High fuel consumption Low oil pressure Overheats Lacks power Stops suddenly No or low output voltage Starts hard Cranks but does not start Does not crank TP-6694 6/22...
Page 120
Exercise run time and/or event records inoperative Displays error message/locks up Excessive or abnormal noise High fuel consumption Low oil pressure Overheats Lacks power Stops suddenly No or low output voltage Starts hard Cranks but does not start Does not crank TP-6694 6/22...
Section 5. Voltage Reconnection 5.1 Introduction Use the following voltage reconnection procedure to change the voltage of 10- and 12- lead generator sets. Frequency changes require voltage regulator and governor adjustments. Refer to the respective spec sheet to determine if frequency is fixed or field- convertible.
5.2 Voltage Reconnection Procedure Note: ® For Decision-Maker 3000 Controllers with software versions before 2.8, go to the next Section. Press the generator set master control OFF/RESET button Turn the controller pushbutton/rotary selector dial until it stops at the Volt Select menu. See Figure 55 Note: If the Volt Select menu does not appear, the controller voltage selection feature was not activated using SiteTech™...
5.3 Voltage Reconnection Procedure Note: ® This procedure applies to Decision-Maker 3000 Controllers with software versions before 2.8 only. Press the generator set master control OFF/RESET button. Disconnect the generator set engine starting battery, negative (-) lead first. Disconnect power to the battery charger (if equipped) Use Figure 56, Figure 57, Figure 58, or Figure 59 to determine the generator set voltage configuration.
Section 6. Accessories 6.1 Accessories and Connections Several accessories help finalize installation, add convenience to operation and service, and establish state and local code compliance. Accessories vary with each generator set model and controller. Select factory-installed and/or shipped-loose accessories. See Figure 60 for a list of available kits. Obtain the most current accessory information from your local authorized service distributor/dealer.
6.1.1 Battery Chargers The following battery chargers are available for the generator sets covered in this manual: 6 amp, 12 volt battery charger 10 amp battery charger with alarms (meets NFPA requirements) Refer to the documentation provided with the battery charger for installation and operation instructions. Communication port 6 Amp Battery Charger 10 Amp Battery Charger w/Alarms...
Page 133
DEC 3000 Controller Figure 63 Battery Charger to Controller Connections TP-6694 6/22...
6.1.3 Common Fault/Failure (32A) Relay The common fault relay is standard on the controller circuit board and located at the TB2 terminal strip connections. Contacts are rated at 2 amps at 32 VDC or 0.5 amps at 120 VAC max. See Figure 64 and Figure 65. The optional common fault relay shown in Figure 65 as DCB2 has contacts rated at 10 amps at 28 VDC or 120 VAC and can be connected to user-supplied accessories.
SiteTech™ software is required to assign the inputs and outputs. SiteTech™ is available only ® A personal computer with Kohler to Kohler-authorized distributors and dealers. The module has four digital inputs and two analog inputs. There are fourteen programmable relay outputs (K1 – K14) and one common fault relay output (K15).
Page 136
Battery negative (-) connections (TB5-2) P35 4-position jack connects to controller (factory-connected) CAN connections (TB5-CAN (+)/-CAN (-) TB5 output connections C and NO for the common TB6 8-position terminal block, fault relay K15 (other TB5 terminals are factory digital inputs/digital returns connections only) (D11, D12, D13 and D14) Battery positive (+) connections (TB5-42A)
Page 137
WARNING Accidental starting. Can cause severe injury or death. Disconnect the battery cables before working on the generator set. Remove the negative (–) lead first when disconnecting the battery. Reconnect the negative (–) lead last when reconnecting the battery. Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the generator set or equipment connected to the set, disable the generator set as follows: (1) Press the generator set off/reset button to shut down the generator set.
Page 138
Program the inputs and outputs using SiteTech™ Use a computer with Kohler SiteTech™ software to assign functions to digital and analog inputs and outputs. Each input and output corresponds to a controller connection. Verify that the settings are appropriate for the connected sensor, switch, or equipment.
Refer to the respective generator set wiring diagrams for additional information and for LP liquid applications. Typical for PSI, GM, and Doosan Engines KG80–KG125, KG80R–KG125R (KG6208TA Engine) Connections Note: UL fuel valve is standard on KG40-KG60 (KG6208). Figure 70 Gas Fuel Valve Kit Connections TP-6694...
See the following subsection, Accessory Connections, for terminal identification. Use a computer with Kohler SiteTech™ software to assign functions to digital outputs. Each input and output corresponds to a controller connection. Verify that the settings are appropriate for the connected sensor, switch, or equipment.
Optional 5 V Power Optional 5 V Power (50 mA max.) (50 mA max.) Output Analog Analog Device Device 100 ohm min. or TP-6694-6 50 mA max. current 0-5 Volt Ratiometric Sensor 0-5 Volt Analog Device +/- 3 Volt Analog Device Figure 74 Analog Input Connections P28 6.1.7...
6.1.8 Low Fuel (Level/Pressure) Switch Some gaseous-fueled models offer a low fuel pressure switch. The low fuel pressure switch connects to the same controller terminal as the low fuel level switch on diesel-fueled models. See Figure 76, Figure 77, and Figure 78. Note: The main tank or the transfer/day tank includes the low fuel level switch.
6.1.9 Manual Speed Adjust (Engine RPM Menu) Note: ® Not available for Decision-Maker 3000 controllers with software versions before 3.10.3. The control allows varying the engine speed for applications using closed transition ATS. The user can set the nominal running frequency slightly above or below the utility frequency to ensure that synchronization occurs.
APM402 / DEC 3000 Controller To Engine Harness Prime Power Switch Toggle switch shown in the prime power mode off position (contacts open) Figure 80 Prime Power Switch Connections 6.1.11 Remote Emergency Stop Kit The emergency stop (E-stop) kit allows immediate shutdown of the generator set from a remote location. If the emergency stop switch is activated, the EMERGENCY STOP lamp lights and the unit shuts down immediately, bypassing the engine cooldown cycle.
6.1.12 Remote emergency stop kit. This switch uses a glass piece that must be replaced after activation. To stop the generator set, pull down on the handle, breaking the glass piece. To reset the emergency stop switch, return the handle to the original position and replace the glass piece with a new one.
6.1.14 Remote Reset Feature The remote reset switch provides generator set controller resetting after a fault shutdown at a remote location. See Figure 82 and Figure 83 for user-supplied switch connection. Press and hold the switch for 2-3 seconds and release to reset the generator set controller. See the following subsection, “Accessory Connections,”...
6.1.15 Remote Serial Annunciator The RSA III is an annunciator panel offered in several kit configurations to support Kohler power equipment. See Figure 84. The RSA III is a remote serial annunciator that monitors the status of the generator set and/or ATS from a remote location. The RSA III alerts the operator through visual and audible signals using LED indication and a horn.
Page 148
System Monitoring LEDs and Functions System Common Common Ready Generator Communications Fault Fault Fault and Status Condition Fault LED Running LED Status LED Output Horn Overcrank (Shutdown) Red SF Red SF Green Red SF High Engine Temperature (Warning) Yellow SF Red SF Green Green...
6.1.16 Run Relay Kit The run relay kit energizes only when the generator set runs. Use the run relay kit to control air intake and radiator louvers, alarms, and/or other signalling devices. See Figure 86 and Figure 87. See the section titled: Accessory Connections, for terminal identifications. 273705 Figure 86 Run Relay Kit...
6.1.17 Shunt-Trip Line Circuit Breaker A shunt-trip line circuit breaker provides a 12- or 24-DC volt solenoid within the line circuit breaker case that can energize the trip mechanism. This feature allows the circuit breaker to be tripped by the common fault (32A). Connection requires a shunt- trip wiring kit and a dry contact kit.
6.2 Accessory Connections The controller contains a circuit board equipped with terminal strip(s) for use in connecting external optional accessories including alarms, battery chargers, and remote switches. The optional I/O board provides an additional two analog or digital inputs and five digital outputs. For specific information on accessory connections, refer to the accessory wiring diagrams in the wiring diagram manual and the instruction sheet accompanying the kit.
Appendix A. Abbreviations A, amp ampere blk. htr. block heater digital to analog converter ABDC after bottom dead center BMEP brake mean effective pressure decibel alternating current bits per second dB(A) decibel (A weighted) analog to digital Brass direct current advanced digital control;...
Page 158
(2 bytes) megabyte (2 bytes) gallons per hour KBus Kohler communication protocol MCCB molded-case circuit breaker gallons per minute kilogram one thousand circular mils grade, gross kg/cm kilograms per square meggar megohmmeter centimeter...
Page 159
N, norm. normal (power source) permanent magnet generator silicon controlled rectifier (electrical), selective catalytic reduction (exhaust emissions) not available, not applicable potentiometer, potential s, sec. second Systeme international d’unites, nat. gas natural gas parts per million International System of Units National Bureau of Standards PROM programmable read-only...
Page 160
ultrahigh frequency user interface Underwriter’s Laboratories, Inc. unified coarse thread (was NC) unified fine thread (was NF) univ. universal uniform resource locator (web address) undersize, underspeed ultraviolet, undervoltage volt volts alternating current voltampere reactive volts direct current vacuum fluorescent display video graphics adapter very high frequency watt...
Appendix B. Programmer-Defined Settings Use the table below to record programmer-defined settings during the generator set controller setup and calibration. The controller default settings and ranges provide guidelines. The table contains all faults with ranges and time delays including items that do not have adjustments. Some notices give the programmer a choice to make them active Not adjustable programmer-defined settings result when the controller logic does not allow changes or the values are engine limited.
Page 162
GenSet Write Mode Time Default Controller Access Always Delay Time Programmer- Display Display Running Range Default Range Delay Defined Description Message SiteTech Stopped Setting Selection (sec.) (sec.) Settings Coolant Lvl Low Low coolant level * Fixed Not adjustable Shutdwn 0-10 Low coolant Coolant Temp 16°C...
Page 163
GenSet Write Mode Time Default Controller Access Always Delay Time Programmer- Display Display Running Range Default Range Delay Defined Description Message SiteTech Stopped Setting Selection (sec.) (sec.) Settings Battery fault Battery Flt Not adjustable Chicago Code Chicago code active Active Common Fault Common fault Not adjustable...
Page 164
GenSet Write Mode Time Default Controller Access Always Delay Time Programmer- Display Display Running Range Default Range Delay Defined Description Message SiteTech Stopped Setting Selection (sec.) (sec.) Settings Ground Fault Ground fault input * Not adjustable Warning 102% Total Power standby, kW overload Fixed...
Page 165
GenSet Write Mode Time Default Controller Access Always Delay Time Programmer- Display Display Running Range Default Range Delay Defined Description Message SiteTech Stopped Setting Selection (sec.) (sec.) Settings Charger Equalize Stage Duration (Min) Note: Equalize is only 60–480 available with FLA/VRLA topology selected.
Page 166
GenSet Write Mode Time Default Controller Access Always Delay Time Programmer- Display Display Running Range Default Range Delay Defined Description Message SiteTech Stopped Setting Selection (sec.) (sec.) Settings 13–15 14.25 Adjustable with Charger Voltage Bulk (12 V)§ (12 V) Charger 26–30 28.5 Custom Profile...
Appendix C. Voltage Regulator Definitions and Adjustments The following definitions and adjustment/setting specifications are intended for users planning to adjust the voltage regulator beyond the default settings in order to customize the alternator for a specific application. This information is not intended to be a comprehensive explanation of all the terms mentioned. There are numerous documents available that define these terms more completely than described herein.
Page 168
Frequency Setpoint or Cut-In Point The point at which the underfrequency unloading begins to take effect is adjustable, allowing the system to be tailored for each application. Because the characteristics of the engine have the largest effect on the system’s performance, the engine’s response should determine the unloading point.
Page 169
Adjustment and Setting Specifications Voltage Adjust The voltage adjust is entered as the rated or otherwise desired line-to-line voltage. The average of the line-to-line voltages is then regulated to the corresponding value as previously described. The setting may be as fine as tenths of volts. The voltage adjust defaults to the rated system voltage whenever the system voltage is changed.
Appendix D. Alternator Protection The controller has built-in thermal protection for the alternator. This feature functions similarly to a thermal circuit breaker. When the output current exceeds the nominal rating for a short period of time the condition causes the fault shutdown. The amount of time at which current is over the rating is inversely related to the amount of current above the nominal rating.
Some engines do not have an ECM and in some cases the ECM information is not available as a controller display. In these situations, critical information like oil pressure and coolant temperature are displayed by the controller using independent engine sensors not used by the ECM. Engine Manufacturer (and model) Kohler Gas (KG6208, Controller Displays Kohler...