STEP 6 - Adjust refrigerant level to attain proper gage pressure.
Add refrigerant if the Liquid Gage Pressure is lower than the chart value.
1. Connect gages to refrigerant bottle and unit as illustrated.
2. Purge all hoses.
3. Open bottle.
4. Stop adding refrigerant when liquid line temperature and Liquid Gage Pressure matches the charging chart
Final Subcooling value.
Recover refrigerant if the Liquid Gage Pressure is higher than the chart value.
STEP 7 - Stabilize the system.
1. Wait 20 minutes for the system condition to stabilize between adjustments.
Note: When the Liquid Line Temperature and Gage Pressure approximately match the chart, the system
is properly charged.
2. Remove gages.
3. Replace service port caps to prevent leaks. Tighten finger tight plus an additional 1/6 turn.
STEP 8 - Verify typical performance.
Refer to System Pressure Curves in this document to verify typical performance.
14
R-410A REFRIGERANT CHARGING CHART
LIQUID
8
TEMP
(
F)
°
55
179
60
195
65
211
70
229
75
247
80
267
85
287
309
90
331
95
107 °F
355
100
381
105
407
110
115
435
120
464
125
495
INDOOR ENTERING WET BULB CURVES TOP TO BOTTOM 71,
67, 63 AND 59 DEG F.
500
450
400
350
(4)
300
250
200
55
65
INDOOR ENTERING WET BULB CURVES TOP TO BOTTOM
160
71, 67, 63 AND 59 DEG F.
155
150
145
140
(5)
135
130
125
120
115
110
55
65
COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 65 DEG F
Table 14.2
FINAL SUBCOOLING (
°
9
10
11
12
LIQUID GAGE PRESSURE (PSI)
182
185
188
191
198
201
204
208
215
218
222
225
232
236
240
243
251
255
259
263
271
275
279
283
291
296
300
304
313
318
322
327
336
341
346
351
360
365
370
376
386
391
396
402
413
418
424
429
441
446
452
458
470
476
482
488
501
507
514
520
From Dwg. D154557P01 Rev. 3
(Example only)
TAM4A0A36S31
TAM4A0A36S31
Cooling
INDOOR ENTERING DRY BULB CURVES TOP TO BOTTOM 80, 70, AND 60
DEG F.
(2)
500
450
400
(3)
350
300
(1)
250
75
85
95
105
115
-5
5
15
OUTDOOR TEMPERATURE (Degree F)
INDOOR ENTERING DRY BULB CURVESTOP TO BOTTOM 80, 70, AND
160
60 DEG F.
150
140
(2)
130
120
110
(3)
100
90
80
70
60
50
(1)
40
75
85
95
105
115
-5
5
15
OUTDOOR TEMPERATURE (Degree F)
F)
13
14
195
198
211
215
229
232
247
251
267
271
287
291
309
313
331
336
355
360
381
386
407
413
435
441
464
470
495
501
527
533
Heating
25
35
45
55
65
25
35
45
55
65
88-A4HP4001-1G-EN

Advertisement

Table of Contents
loading

Table of Contents