Heat detector, interconnectable radio, lithium battery 10 years
Table of Contents

Advertisement

3
Line the marker up with the LEDs in order to position the detector on its
base.
5
Proceed to chapter 3. Testing the detector.
2.3. Installing the detector in association with a hager alarm system
Recognition programming allows the detector to be recognised by the control panel.
The control panel allocates a detector number following the chronological order of programming.
All the radio detector must be recognized and in radio range with the control panel.
• To perform recognition programming operations, the control panel must be in installation mode.
If it is not, enter on the control panel keypad:
master code
• There is no need to place the product close to the control panel for recognition programming. Indeed, it is advisable to move it away
from the control panel by at least 2 metres.
• If the detector is installed in association with a control panel with a version lower than 1.11.6, it must be placed by at least 4 meters
from this one.
Control panel in installation mode, enter
• It is possible to record a personalised message vocally identifying the fire detector (see Control panel installation manual § Detector
vocal identification message).
1. Perform the following learning sequence:
then
Hold down the Cfg2 key for 10 s until the response
Press then # on the
of the control panel.
control panel keypad.
2. Keeping in mind the precautions outlined in the chapter entitled Choosing the best place to install the detector, position
the detector in the chosen location without fixing it in place.
3. Test the radio range with the control panel by pressing and holding down the programming key Cfg2.
• Satisfactory link: the control panel issues the voice message "Beep, test fire detector n° X" to confirm,
• Unsatisfactory link: no voice message is issued. Move the detector closer to the control panel or use a radio repeater
relay.
4. Fix the detector in place following steps 1 to 4 in chapter 2.2. Installing the detector as a standalone device.
5. Put the control panel back in user mode by entering:
installer code
6. Proceed to chapter 3. Testing the detector.
Red LED/yellow LED
then
installer code
10 s max.
4
Turn the detector clockwise until it is
completely locked. The yellow
indication LED flashes for 5 s and then
once every 10 s to indicate the detector
is operating normally.
on her keypad to check the version.
"beep, smoke detector n°"