MANUALE DI PROGRAMMAZIONE IT
PROGRAMMING INSTRUCTIONS UK
MANUEL DE RÉGLAGE FR
MANUAL DE REGULACIÓN
ES
_____________________MP2-HT mA

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MP2-HT mA and is the answer not in the manual?

Questions and answers

Summary of Contents for MICRODOS MP2-HT mA

  • Page 1 MANUALE DI PROGRAMMAZIONE IT PROGRAMMING INSTRUCTIONS UK MANUEL DE RÉGLAGE FR MANUAL DE REGULACIÓN _____________________MP2-HT mA...
  • Page 2: Table Of Contents

    INDEX ITALIANO ....................................... 6 DESCRIZIONE DELLE CARATTERISTCHE E DEL FUNZIONAMENTO ..................6 DESCRIZIONE PANNELLO FRONTALE ............................. 6 FUNZIONI GENERALI ................................... 6 CONNESSIONI ......................................7 REGOLAZIONI DI FABBRICA ................................7 RIPRISTINO REGOLAZIONI DI FABBRICA ............................7 DISPLAY NEI DIVERSI FUNZIONAMENTI ............................8 STAND BY (STOP) ....................................
  • Page 3 ENGLISH ....................................... 17 DESCRIPTION OF CHARACTERISTICS AND OPERATION ......................17 FRONT PANEL DESCRIPTION ................................17 GENERAL FUNCTIONS..................................17 CONNECTIONS ....................................18 DEFAULT SETTINGS ..................................18 DEFAULT SETTINGS RESTORE ................................ 18 DISPLAY IN DIFFERENT DOSING ..............................19 STAND BY (STOP) ....................................19 PRIME BUTTON ....................................
  • Page 4 FRANCAIS ......................................28 DESCRIPTION DES CARACTERISTIQUES ET DU FONCTIONNEMENT ..................28 DESCRIPTION DU PANNEAU AVANT ............................. 28 FONCTIONS GÉNÉRALES: ................................. 28 CONNECTIONS ....................................29 REGLAGES PAR DEFAUT .................................. 29 RESTAURATION DES PARAMETRES D'USINE ..........................29 AFFICHAGE DANS DIFFÉRENTES TYPES DE DOSAGE ....................... 30 STAND BY (STOP) ....................................
  • Page 5 ESPAÑOL ......................................39 DESCRIPCIÓN DE LAS CARACTERÍSTICAS Y FUNCIONAMIENTO..................39 DESCRIPCION DEL PANEL FRONTAL ............................39 FUNCIONES GENERALES: ................................. 39 CONEXIONES ....................................... 40 PARÁMETROS DE FÁBRICA ................................40 RESTAURACIÓN DE AJUSTES DE FÁBRICA ..........................40 PANTALLA EN DIFERENTES OPERACIONES ..........................41 STAND BY (STOP) ....................................
  • Page 6: Italiano

    DESCRIZIONE DELLE CARATTERISTCHE E DEL FUNZIONAMENTO Le pompe dosatrici serie “MP2-HT mA” sono ideali per il dosaggio nelle più svariate applicazioni. Possono funzionare in modo Manuale, mA e la portata è regolabile dal 10% al 100% della portata massima. Regolano la portata variando la velocità...
  • Page 7: Connessioni

    A - è il cavo di alimentazione elettrica, 90-250V-50-60Hz CONNESSIONI B - è l’ingresso di Enable o consenso al dosaggio (110Vac; 230Vac; a richiesta 24V). OPTIONAL C - è il connettore dell’uscita relè per gli allarmi (contatti 3 e 4). ( 5A 250Vca/30Vdc) NORMALMENTE APERTO.
  • Page 8: Display Nei Diversi Funzionamenti

    DISPLAY NEI DIVERSI FUNZIONAMENTI ➔ Dosaggio: Manuale con ciclo disattivo; ➔ La pompa è in dosaggio con Portata 80% ➔ Dosaggio: Manuale con ciclo attivo; ➔ La pompa sta dosando con portata 80% per un Ton di 10 secondi ➔ Dosaggio: mA ➔...
  • Page 9: Struttura Del Menu Principale

    STRUTTURA DEL MENU PRINCIPALE Premere il tasto ENTER/MENU per 3 secondi per entrare in 3sec programmazione. Con il tasto ▼ spostare il cursore sui sottomenu di interesse. Premere ENTER per entrare nel sottomenu. Se si vuole abbandonare la programmazione e tornare in misura, premere per 3 secondi il tasto ESC.
  • Page 10: Password

    PASSWORD La password protegge la modifica dei menu di Dosaggio, Utilità e Relè e non blocca la Calibrazione ed il Set up. Di default la password non è presente ed è quindi possibile accedere a tutta la programmazione. Prima definizione della password: All’interno del Menu Set up, selezionare con il cursore “Password”...
  • Page 11: Rottura Tubo (A Richiesta)

    ROTTURA TUBO (A RICHIESTA) Che cos’è? È un sensore che si accorge se il tubo peristaltico si lacera e lascia fuoriuscire il prodotto chimico da dosare. Quando l’allarme di rottura del tubo scatta, blocca il dosaggio e viene segnalato sul display.
  • Page 12: Metodo Veloce (Tabella Portata)

    METODO VELOCE (TABELLA PORTATA): Leggere il modello di pompa che si possiede sulla etichetta applicata sulla pompa (vedere figura a lato) e scriverlo sul parametro “Tabella portata” come segue: All’interno del Menu Calibrazione, selezionare con il cursore “Tabella Portata” e premere ENTER. Leggere sull’etichetta della pompa la portata e con i tasti ▼▲...
  • Page 13: Menu Utilitá

    MENU UTILITÁ Il menu di Utilità permette di programmare il Ritardo di accensione, e permette di ripristinare i parametri di fabbrica della programmazione. Premere il tasto ENTER/MENU per 3 secondi per entrare in programmazione. 3sec Con il cursore selezionare Utilità e premere ENTER. Posizionare il cursore sulla voce da modificare.
  • Page 14: Allarme

    3sec Premere il tasto ENTER/MENU per 3 secondi per entrare in programmazione. Con il cursore selezionare Relè e premere ENTER. Posizionare il cursore sulla voce da modificare. Premere ENTER per entrare nel sottomenu e procedere alla modifica. Se si vuole abbandonare la programmazione e tornare in misura, premere per 3 secondi il tasto ESC.
  • Page 15: Dosaggio Manuale

    DOSAGGIO MANUALE Ci sono 2 tipi di dosaggio Manuale: 1) Con il parametro Ciclo disattivo (Ciclo [dis]) il dosaggio è costante alla portata definita (%Portata) 2) Con il parametro Cicllo attivo (Ciclo [att]) il dosaggio è costante alla portata definita (% Portata) ma è anche ciclico con tempi di ON (Ton) e OFF (Toff) programmabili.
  • Page 16 PARAMETRI: mA Min: valore della corrente minima % Min: portata della pompa quando l’ingresso supera la corrente minima. Dos.Min: permette di scegliere se al di sotto della corrente minima la pompa deve dosare [att] alla portata % Min oppure non deve dosare [dis]. mA Max: valore della corrente massima % Max: portata della pompa quando in ingresso c’è...
  • Page 17: English

    ENGLISH DESCRIPTION OF CHARACTERISTICS AND OPERATION The "MP2-HT mA" dosing pumps series are ideal for the most varied treatments. They can operate in Manual, mA and the flowrate is adjustable from 10% to 100% of the maximum flowrate. They can adjust the flowrate by varying the rotation speed of the roll holder.
  • Page 18: Connections

    A - Power cable, 90-250V-50-60Hz CONNECTIONS B - Enable input (dosing consent) (110Vac; 230Vac; upon request 24V). OPTIONAL C - Alarm output connector (3 and 4 contacts). ( 5A 250Vca/30Vdc) NORMALLY OPEN. OPTIONAL. D - Level probe connector (3 and 4 contacts). OPTIONAL.
  • Page 19: Display In Different Dosing

    DISPLAY IN DIFFERENT DOSING ➔ Dosing: Manual with cycle deactive; ➔ The pump is dosing with 80% Flowrate ➔ Dosing: Manual with cycle active; ➔ The pump is dosing with 80% Flowrate during Ton=10 second ➔ Dosing: mA ➔ The pump doesn’t dose, it is receiving 4 mA from the input STAND BY (STOP) 3sec Keep pushing ESC/SBY button for 3 seconds during the functioning to put the pump in stand by mode:...
  • Page 20: Structure Of The Main Menu

    STRUCTURE OF THE MAIN MENU Press the ENTER / MENU button for 3 seconds to enter 3sec programming. Use the ▼ button to move the cursor to the relevant submenus. Press ENTER to enter the submenu. If you want to esc programming and return to measurement, press the ESC button for 3 seconds.
  • Page 21: Password

    PASSWORD The password protects the modification of the Dosing, Utility and Relay menus. It does not block Calibration and Set up. By default the password is not present and it is therefore possible to access all the programming. First definition of the password: In the Set up menu, select "Password"...
  • Page 22: Broken Hose (Optional)

    BROKEN HOSE (OPTIONAL) What is that? It is a sensor that detects if the peristaltic tube is torn and leaves the chemical to come out. When the broken hose alarm starts, it stops the dosage and the green led flashes and the display shows “broken hose”.
  • Page 23: Fast Way (Table Flowrate)

    FAST WAY (TABLE FLOWRATE): Read the pump model that you have on the label applied on the pump (see figure on the side) and write it on the "Table Flowrate" parameter as follows: In the Calibration Menu, select with cursor “Table Flowrate"...
  • Page 24: Menu Utility

    MENU UTILITY The Utility menu allows you to program the Delay On and to restore the factory programming of the parameters. Press the ENTER/MENU button for 3 seconds to enter programming. 3sec Select by the cursor the menu Utility and press ENTER. Use the ▼▲...
  • Page 25: Alarm

    Press the ENTER/MENU button for 3 seconds to enter programming. 3sec Select by the cursor the menu Relay and press ENTER. Use the ▼▲ buttons to move the cursor to the submenus. Press ENTER to enter the submenu. If you want to esc programming and return to measurement, press the ESC button for 3 seconds.
  • Page 26: Manual Dosing

    MANUAL DOSING There are 2 manual dosage types: 1) With the Cycle parameter deactive (Cycle [dea]) the dosage is constant at the defined flowrate (% Flowrate) 2) With the Cycle parameter active (Cycle [act]) the dosage is constant at the defined flowrate (% Flowrate) but is also cyclical with programmable ON (Ton) and OFF (Toff) times.
  • Page 27 PARAMETERS: mA Min: minimum mA current value % Min: flowrate of the pump when the input exceeds mA Min Dos.Min: allows to choose if, when the input mA current is less than the minimum mA current, the pump must dose [act] at the % Min flowrate or it must not dose [dea] mA Max: maximum mA current value % Max: flowrate of the pump when the input current is equal to mA Max...
  • Page 28: Francais

    DESCRIPTION DES CARACTERISTIQUES ET DU FONCTIONNEMENT Les pompes doseuses de la série "MP2-HT mA" sont idéales pour le dosage dans les applications les plus variées. Elles peuvent fonctionner en mode Manuelle, mA et le débit est réglable de 10% à 100% de la capacité maximale. Ces pompes régulent le débit en faisant varier la vitesse de rotation du porte-rouleau.
  • Page 29: Connections

    A - est le câble d'alimentation, 90-250V-50-60Hz CONNECTIONS B - est l'entrée de consentement à dosage (110Vac; 230Vac; 24V sur demande). EN OPTION. C - est le connecteur de sortie de relais pour les alarmes (contacts 3 et 4). (5A 250Vca/30Vdc). NORMALEMENT OUVERT.
  • Page 30: Affichage Dans Différentes Types De Dosage

    AFFICHAGE DANS DIFFÉRENTES TYPES DE DOSAGE ➔ Dosage: manuelle avec cycle désactivé; ➔ La pompe est en train de doser avec une capacité de 80% ➔ Dosage: manuelle avec cycle actif; ➔ La pompe est en train de doser avec un débit de 80% pour une Ton de 10 secondes ➔...
  • Page 31: Structure Du Menu Principal

    STRUCTURE DU MENU PRINCIPAL Appuyez sur le bouton ENTER / MENU pendant 3 secondes 3sec pour entrer en programmation. Avec la touche ▼ déplacer le curseur sur le sous-menu d'intérêt. Appuyez sur ENTER pour entrer dans le sous-menu. Appuyez sur la touche ESC pendant 3 secondes pour quitter la programmation.
  • Page 32: Password

    PASSWORD Le mot de passe (Password) protège la modification des menus Dosage, Utilitaires et Relais. Il ne bloque pas l’Etalonnage et le Set up. Par défaut, le mot de passe n'est pas présent et il est donc possible d'accéder à toute la programmation. Première définition du mot de passe: Dans le menu Set up, sélectionnez "Password"...
  • Page 33: Rupture Tube (Optionnel)

    RUPTURE TUBE (OPTIONNEL) Qu'est-ce que c'est? C'est un capteur qui détecte si le tube péristaltique est cassé et laisse échapper le produit chimique.Lorsque l'alarme de rupture de tube se déclenche, elle arrête le dosage et s'affiche à l'écran. Avant toute intervention débrancher la pompe du réseau électrique! Au cours de l'opération, utilisez toujours les protections personnelles indiquées dans les avertissements d'utilisation du produit chimique dosé.
  • Page 34: Mode Rapide (Tableau Debit)

    MODE RAPIDE (TABLEAU DEBIT): Lisez le modèle de pompe que vous avez sur l’étiquette appliquée sur la pompe (voir figure à côté) et écrivez-le dans le paramètre "Tableau Debit" comme suit: Dans le menu Etalonnage, sélectionnez "Tableau Debit" avec le curseur et appuyez sur ENTER. Lisez le débit indiqué...
  • Page 35: Menu Utilitaire

    MENU UTILITAIRE Le menu Utilitaire vous permet de programmer le délai d’allumage et rétablir les paramètres d'usine de la programmation. Appuyez sur le bouton ENTER / MENU pendant 3 secondes 3sec pour entrer en programmation. Utilisez la touche ▼ pour déplacer le curseur sur "Utilitaire".
  • Page 36: Alarme

    Appuyez sur le bouton ENTER / MENU pendant 3 secondes 3sec pour entrer en programmation. Avec la touche ▼ déplacer le curseur sur le sous-menu « Relais ». Appuyez sur ENTER pour entrer dans le sous- menu. Positionnez le curseur sur l'élément à modifier. Appuyez sur ENTER pour accéder au sous-menu et procéder au changement.
  • Page 37: Dosage Manuelle

    DOSAGE MANUELLE Il ya 2 types de dosage manuel: 1) Lorsque le paramètre Cycle est désactivé (Cycle [des]), le dosage est constant au débit défini (%Débit). 2) Avec le paramètre Cycle actif (Cycle [act]), le dosage est constant au débit défini (%Débit) mais est également cyclique avec des temps programmables ON (Ton) et OFF (Toff).
  • Page 38 PARAMETRES: mA Min: valeur du courant minimale % Min: débit de la pompe lorsque l'entrée dépasse le courant minimal Dos.Min choisissez si en dessous du courant minimum la pompe doit doser [act] au débit %Min ou si elle ne doit pas doser [des] mA Max: valeur du courant maximum % Max: débit de la pompe lorsque le courant maximum est entré...
  • Page 39: Español

    DESCRIPCIÓN DE LAS CARACTERÍSTICAS Y FUNCIONAMIENTO. Las bombas dosificadoras "MP2-HT mA" son ideales para la dosificación en muy diversas aplicaciones. Pueden operar en modo Manual, mA y el caudal es ajustable del 10% al 100% del flujo máximo. Estas bombas regulan el caudal variando la velocidad de rotación del soporte del rollo.
  • Page 40: Conexiones

    A- es el cable de alimentación, 90-250V-50-60 Hz CONEXIONES B - es la entrada de B de habilitación o consentimiento a dosificación (110Vac; 230Vac; 24V a pedido). OPCIONAL C - es el conector de salida de relé para las alarmas. (Contactos 3 y 4). ( 5A 250Vca/30Vdc) NORMALMENTE ABIERTO.
  • Page 41: Pantalla En Diferentes Operaciones

    PANTALLA EN DIFERENTES OPERACIONES ➔ Dosificación: Manual con ciclo deshabilitado; ➔ La bomba dosifica con caudal del 80%. ➔ Dosificación: Manual con ciclo activo; ➔ La bomba dosifica con un caudal del 80% para una Ton de 10 segundos. ➔ Dosificación: mA;...
  • Page 42: Estructura Del Menú Principal

    ESTRUCTURA DEL MENÚ PRINCIPAL Pulse el botón ENTER / MENU durante 3 segundos para 3sec entrar en la programación. Con la tecla ▼ mover el cursor en el submenú de interés. Pulse ENTER para entrar en el submenú. Si desea abandonar la programación y volver a la medición, presione la tecla ESC durante 3 segundos.
  • Page 43: Contraseña

    CONTRASEÑA La contraseña (Password) protege la modificación de los menús Dosificacion, Utilidades y Relé. No bloquea la Calibración y Set up. Inicialmente la contraseña no está establecida y, por lo tanto es posible acceder a toda la programación. Primera definición de la password: En el menú...
  • Page 44: Ruptura Tubo (Opcional)

    RUPTURA TUBO (OPCIONAL) ¿Qué es? Es un sensor que detecta si el tubo peristáltico está roto y deja salir las sustancias químicas. Cuando se activa la alarma de ruptura del tubo, se detiene la dosificación y se señaliza en la pantalla. Antes de cualquier intervención, desconecte la bomba de la red eléctrica !! Durante la operación, utilice siempre las protecciones personales...
  • Page 45: Modo Rápido (Tabla Caudal)

    MODO RÁPIDO (TABLA CAUDAL) Lea el modelo de bomba que tiene en la etiqueta aplicada en la bomba (vea la figura al lado) y escríbalo en el parámetro "Tabla Caudal" de la siguiente manera: En el menú de Calibracion, seleccione con el cursor "Tabla Caudal"...
  • Page 46: Menú Utilidades

    MENÚ UTILIDADES El menú Utilidades le permite programar el Retraso de ignición y restaurar los parámetros de fábrica de la programación. Pulse la tecla ENTER/MENU durante 3 segundos para entrar 3sec en la programación Con el cursor seleccione Utilidades y pulsa ENTER. Posicione el cursor en el elemento a cambiar.
  • Page 47: Alarma

    Pulse la tecla ENTER/MENU durante 3 segundos para entrar 3sec en la programación Con el cursor seleccione Relé y pulse ENTER. Posicione el cursor en el elemento a cambiar. Presione ENTER para ingresar al submenú y continuar con el cambio. Si desea abandonar la programación y volver a la medición, presione la tecla ESC durante 3 segundos ALARMA...
  • Page 48: Dosificacion Manual

    DOSIFICACION MANUAL Hay 2 tipos de dosis Manuales: 1) Con el parámetro Ciclo desactivado (Ciclo [des]), la dosis es constante a la velocidad de caudal definida (% Caudal) 2) Con el parámetro Ciclo activo (Ciclo [act]), la dosis es constante a la tasa de caudal definida (% caudal) pero también es cíclica con tiempos programables de ENCENDIDO (Ton) y APAGADO (Toff).
  • Page 49 PARAMETROS: mA Min: valor de la corriente mínima % Min: caudal de la bomba cuando la entrada excede la corriente mínima. Dos.Min: elija si, por debajo de la corriente mínima, la bomba debe dosificar [act] al % Min de caudal o no debe dosificar [des].
  • Page 50 Rev 1.1 Cod. 00.009.101...
  • Page 51 Rev 1.1 Cod. 00.009.101...