Pipe Size Selection & Limitation; Additional Charge Calculation - Fujitsu AR C72LHTA Series Design & Technical Manual

Table of Contents

Advertisement

7.
PIPE SIZE SELECTION & LIMITATION
MODEL : AO
 A72LALT, AO  A90LALT
Pipe diameter
[mm (in.)] Gas pipes
Piping length
Max. height difference (H1)
<Indoor unit to outdoor unit>
8.

ADDITIONAL CHARGE CALCULATION

MODEL : AO
 A72LALT, AO  A90LALT
Refrigerant type
Refrigerant amount
Refrigerant charge
z
Refrigerant pipe size
[mm (in.)]
Standard
Liquid
12.70 (1/2)
Gas
25.40 (1)
Size down
Liquid
12.70 (1/2)
Gas
22.22 (7/8)
Size up
Liquid
12.70 (1/2)
Gas
28.58 (9/8)
L1
Liquid pipes
Max. piping length (L1)
(Max. chargeless length)
Min. piping length (L1)
R410A
g
11,200
~20 m
30 m
40 m
None
1,100 g
2,200 g
~20 m
30 m
40 m
None
1,100 g
2,200 g
~20 m
30 m
40 m
None
1,100 g
2,200 g
- (02 - 14) -
H1
Size down
Standard
12.70 (1/2)
22.22
(7/8)
[m (m)]
75 (20)
[m]
[m]
Piping length
50 m
60 m
70 m
3,300 g
4,400 g
5,500 g
50 m
60 m
70 m
3,300 g
4,400 g
5,500 g
50 m
3,300 g
Size up
25.40
28.58
(1)
(9/8)
75 (20)
50 (20)
5
30
75 m
g/m
6,050 g
110 g/m
75 m
g/m
6,050 g
110 g/m
g/m
110 g/m