9.
ELECTRIC CHARACTERISTICS
Model name
Power supply
Max. operating current (Indoor unit)
Wiring spec.
(Indoor unit to outdoor unit)
Note: Wiring specification
1. Selected sample
(Selected based on Japan Electrotechnical Standard and Codes Committee E0005)
2. Limited wiring length : Limit voltage drop to less than 2%. Increase cable gauge if voltage drop is 2% or more.
3. If the transmission wire is longer than 50m, use the bigger conductor size.
Voltage
Frequency
Connection cable
Limited wiring length
- (01 - 21) -
AR C72LHTA
AR C90LHTA
V
230 ~
Hz
50
A
9.3
2
mm
1.5
m
50 or less
2.5
50 to 76