3-2. ELECTRICAL PARTS SPECIFICATIONS
Service ref.
Symbol
Parts name
Room temperature
detection thermistor
Pipe temperature
detection thermistor/liquid
Pipe temperature
detection thermistor/gas
Fuse
FUSE
(Indoor controller board)
Fan motor
(with thermal fuse)
Vane motor
(Upper)
Vane motor
(Lower)
Linear expansion valve
Power supply terminal
block
Transmission terminal
block
MA-Remote controller
terminal block
* Refer to WIRING DIAGRAM for the supplied voltage.
OCHT715A
TPKFYP004LM140A
TPKFYP006LM140A
TPKFYP008LM140A
TH21
Resistance 32°F/15 k", 50°F/9.6 k", 68°F/6.3 k", 77°F/5.4 k", 86°F/4.3 k", 104°F/3.0 k"
TH22
Resistance 32°F/15 k", 50°F/9.6 k", 68°F/6.3 k", 77°F/5.4 k", 86°F/4.3 k", 104°F/3.0 k"
TH23
Resistance 32°F/15 k", 50°F/9.6 k", 68°F/6.3 k", 77°F/5.4 k", 86°F/4.3 k", 104°F/3.0 k"
MF
MV1
MV2
LEV
Port [3/32 (P004), [7/64 (P006/008/012/015/018) (0-2000pulse)
TB2
TB5
TB15
TPKFYP012LM140A
TPKFYP015LM140A
TPKFYP018LM140A
T3.15AL250V
8 X 30W / RC0J30-QD
NSEK302 DC12V
MSBPC20 DC12V
DC12V Stepping motor drive
(L1,L2) Rated to 250V 20A *
(M1, M2, S) Rated to 250V 20A *
(1, 2) Rated to 250V 10A *