Tescom DS3550 User Manual page 26

Table of Contents

Advertisement

REC CODE = XXXX
R00 REC FAULT = XXXX
R01 AC INPUT HIGH
R02 LINE FAILURE
R03 DC BUS HIGH
R05 FREQ TOLER
R06 OVERTEMPERATURE
R07 BLACKOUT
R08 I/P OVERCURRENT
R09 ROTATE PHASE
R14 PFC MANUAL STOP
R15 DC LOW
R17 BATTERY TEST
R18 BOOST CHARGE
R19 AC HIGH
R20 INPUT CB OPEN
R21 PFC STOP
R22 POS CHG LIMIT
R23 NEG CHG LIMIT
R24 WAITING DC BUS
R25 BATTERY FAILURE
R26 BATT TEMP SENSOR
R27 BATT TEMP HIGH
R29 PFC RESET
R30 PLEASE WAIT
R31 RECTIFIER START
L01 TH1 TEMP HIGH
L02 TH2 TEMP HIGH
L03 TH1 TEMP LOW
L04 TH2 TEMP LOW
L05 FAN MAINT
L06 BATTERY MAINT
L07 OPT MAINTENANCE
L08 TH1 SENSOR FAIL
L09 TH2 SENSOR FAIL
L10 ENTER FAULT RESET
L11 BATT CB OPEN
L12 GENERAL MAINT
L13 PFC CAN COMM ERR
L14 INV CAN COMM ERR
INV CODE = 0XXX
A00 INV FAULT = XXXX
A01 O/P OVERCURRENT
A02 OVERTEMP SHUT
A03 BATT HIGH
A04 OUTPUT V.LOW
A05 OUTPUT V.HIGH
A06 OVERLOAD SHUT
A07 SHORT CIRCUIT
Rectifier module alarm codes
XXXX SYSTEM fault occured at the rectifer module
Fault
Rectifier AC input voltage is high
CALL SERVICE !
Alarm
Rectifier AC input voltage is low
Alarm
Rectifier DC output voltage is high
Alarm
The rectifier DC output voltage is high, rectifier stop
Alarm
Rectifier input frequcny out of tolerant
Alarm
Rectifier heatsink temperature high
Alarm
Short voltage blackout at rectifier AC input
Alarm
Rectifier IGBT saturation alarm
Alarm
Rectifier input phase sequency incorrect
Alarm
Inverter module stopped rectifier
Alarm
DC BUS voltage is lower then DC rectifier start voltage
Warning
Currently battery test is performing
Warning
Currently rectifier is in boost charge mode
Alarm
AC Peak voltage is bigger then 20% of nominal range
Warning
Input CB is off
Warning
Currently Rectifier module stop
Warning
(+)Battery charge current limited
Warning
(-)Battery charge current limited
Warning
Rectifier is waiting DC BUS to raise for startup
Warning
Battery test failed
Warning
Battery temperature sensor is defected or not connected
Warning
Battery ambient temperature is high
Warning
Rectifier module power on
Warning
Rectifier waits as adjusted startup delay
Warning
Rectifier is in soft start stage
Panel module alarm codes
Warning
TH1 temperature is high
Warning
TH2 temperature is high
Warning
TH1 temperature is low
Warning
TH2 temperature is low
Warning
FAN maintenance time
Warning
Battery maintenance time
Warning
Optional maintenance time
Warning
TH1 temperature sensor failure
Warning
TH2 temperature sensor failure
Warning
UPS is waiting fault reset for startup
Warning
External interactive battery switch is off
Warning
General maintenance time
Warning
PFC module CAN communication timeout
Warning
INV module CAN communication timeout
Inverter module alarm codes
Current inverter modüle status code
Hata
XXXX fault occured at the inverter module
CALL SERVICE !
Alarm
IGBT saturation alarm on inverter module
Alarm
Overtemperature at inverter power module
Alarm
Inverter module measured battery voltage high
Alarm
Inverter output voltage is low
Alarm
Inverter output voltage is high
Alarm
Overload at UPS output
Alarm
Short circuit at UPS output
23

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ds300 seriesDs3600Ds3650Ds3800