RELAY KIT INSTALLATION FOR MULTIPLE UNIT CONTROL
GAS-FIRED DOWNFLOW HEATER MODEL LDAP, AND
GAS-FIRED UNIT HEATER MODELS UBX, UBZ, UDX, UDZ, AND UEZ
• DO NOT use these multiple unit control options with a two-stage thermostat.
• These instructions are designed to assist a qualified electrician in installing this multiple unit
control kit. For maximum safety, the control is installed in the low voltage circuit. Interruption
of the supply voltage is not recommended.
• All electrical wiring and connections, including electrical grounding, MUST be in accordance with
the National Electric Code ANSI/NFPA No. 70 (latest edition) or, in Canada, with the Canadian
Electrical Code, Part 1, CSA Standard C22.1. In addition, the installation must comply with local
ordinances and applicable gas company requirements.
NOTE: Option CL31 includes components for one control unit and one additional unit. Option
CL32 includes components for each additional non-control unit. Not all kit components will be
used on all models.
• These relay kits are designed to permit the control of up to five units (one control unit and up to four additional
non-control units) with one single-stage thermostat or with a time clock and one or more single-stage thermostats.
• Refer to the installation manual provided with the unit for important safety information.
• Ensure that all components listed in
Item
Component
*
No.
1
Assembly
Relay
2
Relay
3
Bracket
Relay
4
Screw
5
Cable clamp
3/16
6
Label
Wiring diagram
7
Transformer
40VA
8
Wiring harness
Assembly
*See
Figure
1,
Figure
2,
Figure
**
Includes relay(s) (item 2), 24VAC DPDT plug(s) (PN 211411), and socket(s) with wires and terminals (PN 211415). If replacing a
previously-used relay only (PN 98118) on an LDAP unit, order replacement kit PN 263527.
DO NOT DESTROY. PLEASE READ CAREFULLY. KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
OPTIONS CL31 AND CL32 FOR
ELECTRIC UNIT HEATER MODEL EUH,
DESTRATIFICATION FAN MODEL H,
⚠ CAUTION ⚠
RELAY KITS
Table 1
are available before beginning installation.
Table 1. Relay Kit Components
Description
LDAP
1041280
**
208365 (2)
38529 (4)
3,
Figure
4,
Figure
5, and
Figure
Revision: OPT-CL31,32 (08-23) 1042699-B
Supersedes: OPT-CL31,32 (05-23) 1042699-A
LDAP-CL31,32 (05-23) 1041278-B
Option
CL31
Model
EUH
H, UBX,
EUH
(208V,
UBZ
(480V)
240V)
Kit PN
1041281
1042927
1042928
Component PN (Quantity)
18549 (2)
197157 (2)
195249 (4)
16228 (2)
197164 (2)
621709 (1) 202661 (1) 194808 (1)
1042929 (1)
6.
CL32
EUH, H,
UDX, UDZ,
UBX, UBZ,
LDAP
UEZ
UDX, UDZ,
UEZ
1041288
1041286
1041287
208365 (1)
18549 (1)
197157 (1)
38529 (2)
195249 (2)
16228 (1)
197164 (1)
197160 (1)

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the CL31 and is the answer not in the manual?

Questions and answers

Summary of Contents for Reznor CL31

  • Page 1 RELAY KITS NOTE: Option CL31 includes components for one control unit and one additional unit. Option CL32 includes components for each additional non-control unit. Not all kit components will be used on all models.
  • Page 2 (3) Remove screws that secure existing transformer and remove transformer. (4) Install replacement transformer (7) with wiring harness (8) and secure using existing screws. (5) Reconnect transformer wires in accordance with wiring diagram provided with unit. (6) Install control compartment access panel. OPT-CL31,32 (08-23) 1042699-B...
  • Page 3 (2) Secure relay bracket (3) with relay (2) as shown using existing screws. EXISTING SCREWS Figure 3. Relay Installation—Model EUH (Refer to Table b. For destratification fan model H, secure relay (2) as shown in Figure 4 using two screws (4). Figure 4. Relay Installation—Model H (Refer to Table OPT-CL31,32 (08-23) 1042699-B...
  • Page 4 (3) Secure relay (2), relay bracket (3), and cable clamp (5) as shown using existing screws for model UBX, UBZ, UDX, and UDZ unit sizes 030–125 or one existing screw and one screw (4) from kit for model UBX, UBZ, UDX, and UDZ unit sizes 150–400 and all UEZ models. OPT-CL31,32 (08-23) 1042699-B...
  • Page 5 ⚠ CAUTION ⚠ Be careful NOT TO short thermostat leads to a metal surface. Doing so will cause the transformer to fail and require replacement. Figure 5. Connect relay (2) to TEW-type control wiring in accordance with OPT-CL31,32 (08-23) 1042699-B...
  • Page 6 Wipe surface with clean, dry cloth. d. Remove label backing and adhere label to unit. 7. Restore system to service: a. For gas-fired units, turn ON gas and electric power. For electric units, turn ON electric power. b. Check for proper operation. OPT-CL31,32 (08-23) 1042699-B...
  • Page 7 NOTES OPT-CL31,32 (08-23) 1042699-B...
  • Page 8 Specifications and illustrations subject to change without notice or incurring obligations. Latest version of this manual is available at www.reznorhvac.com. ©2023 Nortek Global HVAC LLC, O’Fallon, MO. All rights reserved. OPT-CL31,32 (08-23) 1042699-B...

This manual is also suitable for:

Cl32

Table of Contents