[8] Troubleshooting

1. Check methods
1. Component and check points
(1) Thermistor
Room temperature thermistor (TH21)
Liquid pipe thermistor (TH22)
Gas pipe thermistor (TH23)
Disconnect the connector and measure the resistance between terminals with a tester.
(Ambient temperature 50°F (10°C) - 86°F (30°C))
Normal
4.3kΩ - 9.6kΩ
(Refer to the thermistor characteristic graph below.)
1) Thermistor characteristic graph
Low-temperature thermistor
Room temperature thermistor (TH21)
Liquid pipe thermistor (TH22)
Gas pipe thermistor (TH23)
Thermistor R
= 15 kΩ 3%
0
Multiplier of B = 3480 kΩ 2%
Rt = 15 exp { 3480(
273+t
32°F (0°C) 15kΩ
50°F (10°C) 9.6kΩ
68°F (20°C) 6.3kΩ
77°F (25°C) 5.2kΩ
86°F (30°C) 4.3kΩ
104°F (40°C) 3.0kΩ
(A) Temperature
(B) Resistance
(2) Fan motor
Refer to the page on "DC fan motor (fan motor/INV board)."(page 47)
(3) Linear expansion valve
Refer to the page on "LEV". ([8] 4)(page 51)
HWE1017B
Abnormal
Open or short