Toshiba RAV-GM561ATP-NZ Service Manual page 69

Table of Contents

Advertisement

Check
Outdoor
code
LED display
[P19]
(Item without special mention Indicates part of outdoor unit.)
[4-way valve inverse error]
Is operation of 4-way valve
correct?
(Check pipe temp. and etc. in
cooling/heating operation.)
YES
Are temperature sensors
correct?
TE sensor: GM56, 80 : CN603
GM110, 140 : CN605
TS sensor: GM56, 80 : CN603
GM110, 140 : CN604
YES
Is refrigerant flow by
PMV correct?
YES
Are resistance value of
indoor TC and TCJ
sensors correct?
YES
4-way valve maintenance check operation (SW01 and SW02
operations)
You can confirm 4-way valve operation by handling service switches
SW01 and SW02. Use this method to check whether there is trouble or
not on the 4-way valve.
[Method]
(1) Check D800 to D804 are turned off (or rapid flashing) and D805 is
turned on. When D800 to D804 flash slowly or D805 flashes, push
and hold SW01 and SW02 for 5 seconds or more simultaneously.
In the result, D800 to D804 are turned off (or rapid flashing) and D805
changes from flashing to lighting.
(2) Push and hold SW01 for 5 seconds or more. D804 changes to slow
flashing.
(3) Push SW01 several time and stop it at LED display of the following
"Self-preservation valve operation"
Self-preservation valve
D800 D801 D802 D803 D804
suck operation
Self-preservation valve
D800 D801 D802 D803 D804
secession operation
: ON,
: OFF,
: Rapid flashing (5 times/second)
(4) Push SW02 and then stop it at LED display of D805 flashes rapidly.
(5) Push and hold SW02 for 5 seconds or more. In the result, D804
changes to slow flashing, D805 changes to lighting and the 4-way
valve is operated.
* If an unknown point generated on the way of the operation, push and
hold SW01 and SW02 for 5 seconds or more simultaneously. You can
return to the item (1).
- 69 -
Check and troubleshooting
Is the 4-way valve
NO
coil is normal?
(Check the resistance value
of 4-way valve coil)
YES
NO
Replace TE sensor.
Replace TS sensor.
NO
Check and
replace of PMV
Replace TC sensor
NO
Replace TCJ sensor
Check indoor P.C. board.
Defect → Replace
GM56, 80: switch to cooling cycle
This function is operated only by ten
seconds, and turned off afterwards.
GM110, 140: switch to heating cycle
This function is operated only by ten
seconds, and turned off afterwards.
GM56, 80: switch to heating cycle
This function is operated only by ten
seconds, and turned off afterwards.
GM110, 140: switch to cooling cycle
This function is operated only by ten
seconds, and turned off afterwards.
FILE NO. SVM-18043
NO
Replace coil
of 4-way valve.
Does power supply to
YES
4-way valve coil when
4-way valve is operated?
NO
Error
Check outdoor
P.C. board.
OK
Check outdoor
P.C. board.
Defect → Replace
Check 4-way valve.
Defect → Replace