Typical Application Diagram Of Diesel Generator - Apex Digital APEX-E-P3-5000L User Manual

Hybrid inverter
Table of Contents

Advertisement

3.11 Typical applica�on diagram of diesel generator
CAN
coil
open
contact
G
S
GS (diesel generator startup signal)
G-start (1,2): dry contact signal for startup
Inverter
①DC
Breaker
Battery pack
① DC Breaker for battery
APEX-E-P3-5000L: 150A DC breaker
APEX-E-P3-6000L: 200A DC breaker
APEX-E-P3-8000L: 250A DC breaker
APEX-E-P3-10KL: 300A DC breaker
APEX-E-P3-12KL: 300A DC breaker
② AC Breaker for backup load
APEX-E-P3-5000L: 16A AC breaker
APEX-E-P3-6000L: 16A AC breaker
APEX-E-P3-8000L: 20A AC breaker
APEX-E-P3-10KL: 32A AC breaker
APEX-E-P3-12KL: 32A AC breaker
③ AC Breaker for Generator port
APEX-E-P3-5000L: 63A AC breaker
APEX-E-P3-6000L: 63A AC breaker
APEX-E-P3-8000L: 63A AC breaker
APEX-E-P3-10KL: 63A AC breaker
APEX-E-P3-12KL: 63A AC breaker
L wire
relay
the diesel generator.
1 2
N wire
PE wire
BMS
GRI D
Remotely control signal line
- 23 -
N
R
S
T
Backup Load
PE
②AC
Breaker
L OA D
G EN
Ground
③AC Breaker
Generator
R
S
T
N
PE

Advertisement

Table of Contents
loading

Table of Contents