Carrier F80VTL Installation, Start-Up, Operating And Service And Maintenance Instructions

80% afue, variable 25-speed, ecm motor, two-stage, 4-way multipoise, non-condensing gas furnace

Advertisement

Quick Links

F80VTL & G80VTL (Major Series B)
80% AFUE, Variable 25-Speed, ECM Motor,
Two-Stage, 4-Way Multipoise, Non-Condensing Gas Furnace
NOTE: Read the entire instruction manual before starting the
installation.

TABLE OF CONTENTS

Table 1 - Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
LOCATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Table 2 - Minimum Free Area Required for Each Combustion Air
opening of Duct to Outdoors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Table 3 - Minimum Space Volumes for 100% Combustion, Ventila-
tion, and Dilution from Indoors . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Table 4 - Opening Dimensions - In. (mm) . . . . . . . . . . . . . . . . . 11
FILTER ARRANGMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
AIR DUCTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
GAS PIPING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Table 5 - Maximum Capacity of Pipe . . . . . . . . . . . . . . . . . . . . . 14
ELECTRICAL CONNECTIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Table 6 - Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
VENTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Table 7 - Combined Appliance Maximum Input Rating
in Thousands of BTUh per Hour . . . . . . . . . . . . . . . . . . . . . . . . . 20
Table 8 - Minimum Allowable Input Rating of
Table 9 - Recommended Minimum Vent Height Per Furnace and Vent
Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
AIR DELIVERY - CFM. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Table 10 - Air Delivery - CFM (with Filter)* . . . . . . . . . . . . . . . 25
Table 11 - Default Airflow Settings . . . . . . . . . . . . . . . . . . . . . . 27
AND NAVIGATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Table 12 - System Status Display Codes. . . . . . . . . . . . . . . . . . . 27
Table 13 - Main Menu Options . . . . . . . . . . . . . . . . . . . . . . . . . . 28
SERVICE LABEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Table 14 - Test Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
ADJUSTMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Table 15 - Altitude Derate Multiplier for U.S.A. . . . . . . . . . . . . 32
Portions of the text and tables are reprinted from NFPA 54/ANSI Z223.1E, with permission of National Fire Protection Association, Quincy, MA
02269 and American Gas Association, Washington DC 20001. This reprinted material is not the complete and official position of the NFPA or ANSI
Installation, Start-up, Operating and
Service and Maintenance Instructions
on the referenced subject, which is represented only by the standard in its entirety.
Table 16 - Gas Rate (CU ft./hr). . . . . . . . . . . . . . . . . . . . . . . . . . 33
Table 17 - Orifice Size and Manifold Pressure (in. w.c.) for Gas Input
Rate (Tabulated Data Based on 22,000 BTUh High-Heat/14,500
Ft.(305 M) Above Sea Level) . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Table 18 - Orifice Size and Manifold Pressure (in. w.c.) for Gas Input
Rate (Tabulated Data Based on 21,000 BTUh High-Heat/14,500
Ft.(305 M) Above Sea Level) . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
SERVICE AND MAINTENANCE PROCEDURES. . . . . . . . . . . . 38
CARE AND MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Table 19 - Filter Size Information - In. (mm) . . . . . . . . . . . . . . . 40
Table 20 - Filter Size Information - In. (mm) . . . . . . . . . . . . . . . 40
SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
TROUBLESHOOTING GUIDE . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
GAS FURNACE CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
PARTS REPLACEMENT INFORMATION GUIDE . . . . . . . . . . . 50
MODEL NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
To learn more about this appliance and installation via a mobile device,
go to
http://www.fasthvacrparts.com/NFC
access airflow tables or troubleshooting guide on your mobile device go
to
mlctraining.com/training/techdocs/77/
or use the QR code below. To
or use the QR code below.
A221533
A200115

Advertisement

Table of Contents
loading

Summary of Contents for Carrier F80VTL

  • Page 1: Table Of Contents

    F80VTL & G80VTL (Major Series B) 80% AFUE, Variable 25-Speed, ECM Motor, Two-Stage, 4-Way Multipoise, Non-Condensing Gas Furnace Installation, Start-up, Operating and Service and Maintenance Instructions NOTE: Read the entire instruction manual before starting the Table 16 – Gas Rate (CU ft./hr)......33 installation.
  • Page 2: Safety Considerations

    F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions A190084 Fig. 1 – Dimensional Drawing Table 1 – Dimensions ACCESSORY VENT SHIP WT. FILTER TOP AND FURNACE SIZE CONNECTION CABINET OUTLET BOTTOM LB (KG) MEDIA...
  • Page 3 F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions WARNING WARNING FIRE, EXPLOSION, ELECTRICAL SHOCK, AND FIRE, INJURY, OR DEATH HAZARD CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in property damage, personal injury, or death.
  • Page 4: Introduction

    F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions 8. A gas-fired furnace for installation in a residential garage must be This furnace is not approved for installation in mobile homes, installed as specified in the warning box in the “Location” section.
  • Page 5: Location

    F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions CAUTION FURNACE RELIABILITY HAZARD Failure to follow this caution may result in unit component damage. Electrostatic discharge can affect electronic components. Take precautions during furnace installation and servicing to protect the furnace electronic control.
  • Page 6 F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions • De-icing salts or chemicals CAUTION • Carbon tetrachloride • Halogen type refrigerants PERSONAL INJURY AND/OR PROPERTY • Cleaning solvents (such as perchloroethylene) DAMAGE HAZARD • Printing inks, paint removers, varnishes, etc.
  • Page 7 F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions The requirements for combustion and ventilation air depend upon whether or not the furnace is located in a space having a volume of at least 50 cubic feet per 1,000 BTUh input rating for all gas appliances installed in the space.
  • Page 8 F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions Table 2 – Minimum Free Area Required for Each Combustion Air opening of Duct to Outdoors TWO HORIZONTAL DUCTS SINGLE DUCT OR OPENING TWO OPENINGS OR VERTICAL DUCTS FURNACE (1 SQ.
  • Page 9: Installation

    F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions Table 3 – Minimum Space Volumes for 100% Combustion, Ventilation, and Dilution from Indoors OTHER THAN FAN-ASSISTED TOTAL FAN-ASSISTED TOTAL (1,000’S BTUH GAS INPUT RATE) (1,000’S BTUH GAS INPUT RATE)
  • Page 10 F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions leveling legs. To remove bottom closure panel, see Item 1 in Bottom Return Air Inlet section in Step 1 above. To install leveling legs: 1. Position furnace on its back. Locate and drill a hole in each bottom corner of furnace.
  • Page 11 F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions Table 4 – Opening Dimensions - In. (mm) FURNACE PLENUM OPENING FLOOR OPENING CASING WIDTH APPLICATION IN. (mm) Upflow Applications on Combustible or Noncombustible Flooring 12-11/16...
  • Page 12: Filter Arrangment

    F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions Not all horizontal furnaces are approved for side return air connections. (Refer to Horizontal Return Air Configurations and Restrictions (Fig. 20) in the “Upflow and Horizontal Furnaces” section.)
  • Page 13: Gas Piping

    F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions flanges or air conditioning coil casing (when used). DO NOT cut main furnace casing side to attach supply air duct, humidifier, or other accessories. All accessories MUST be connected to duct external to furnace main casing.
  • Page 14 F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions 4. The use of copper tubing for gas piping is NOT approved by the WARNING state of Massachusetts. WARNING FIRE OR EXPLOSION HAZARD A failure to follow this warning could result in personal injury, death, FIRE OR EXPLOSION HAZARD and/or property damage.
  • Page 15: Electrical Connections

    F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions below level of furnace gas controls. Place a ground joint union between WARNING furnace gas control valve and exterior manual equipment gas shutoff valve. ELECTRICAL SHOCK HAZARD A 1/8-in.
  • Page 16 F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions A230059 Fig. 24 – Typical Field Wiring Diagram Table 6 – Electrical Data OPERATING VOLTAGE MAX WIRE LENGTH VOLTS - MAX. FUSE MAX. UNIT UNIT MIN WIRE ‡...
  • Page 17: Accessories

    F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions Electrical Connection to J-Box 2. Route listed power cord through 7/8-in. (22 mm) diameter hole in J-Box. Electrical Box on Furnace Casing Side 3. Secure power cord to J-Box bracket with a strain relief bushing or a WARNING connector approved for the type of cord used.
  • Page 18 F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions To HUM Terminal On To Humidifier Leads Furnace Control Board 24 V Coil To Humidifier Leads To Com/24V Screw Terminal on Thermostat Strip A11157 Fig. 28 – Field-supplied Isolation Relay for Humidifiers with...
  • Page 19: Venting

    F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions 13. Thermostat terminal connection order on furnace control may vary- reference furnace control labeling for designations. VENTING The furnace shall be connected to a listed factory built chimney or vent, or a clay-tile lined masonry or concrete chimney.
  • Page 20: In Thousands Of Btuh Per Hour

    F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions Exterior Masonry Chimney Fan + Nat WARNING Installations with Type-B Double-Wall Vent Connectors ENFPA & AGA CARBON MONOXIDE POISONING HAZARD Table 7 – Combined Appliance Maximum Input Rating...
  • Page 21 F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions Refer to the Fig. 31 to perform a chimney inspection. If the inspection of Air for combustion must not be contaminated by halogen compounds a previously used tile-lined chimney: which include chlorides, fluorides, bromides, and iodides.
  • Page 22: Orientation

    F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions Sidewall Venting Select the listed mechanical venter to match the BTUh input of the furnace being vented. Follow manufacturer’s installation This furnace is not approved for direct sidewall horizontal venting.
  • Page 23 F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions A03212 Fig. 39 – Downflow Application - Vent Elbow Up then Right A03211 Fig. 36 – Downflow Application - Vent Elbow Up A03218 Fig. 37 – Horizontal Right Application - Vent Elbow Right A03214 Fig.
  • Page 24 F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions A03219 Fig. 43 – Horizontal Right Application - Vent Elbow Left then Up A02068 Fig. 44 – Horizontal Right Application-Vent Elbow Left Notes for Venting 1. For common vent, vent connector sizing and vent material: United States-use the NFPA 54/ANSI Z223.
  • Page 25: Air Delivery - Cfm

    F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions AIR DELIVERY - CFM Table 10 – Air Delivery - CFM (with Filter)* Airflow External Static Pressure (in.w.c.) Unit Size Default Setting Setting Cont. Fan Low Heating...
  • Page 26 F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions Table 10 – Air Delivery - CFM (with Filter)* (Continued) Airflow External Static Pressure (in.w.c.) Unit Size Default Setting Setting Cont. Fan 1030 1125 1035 1210...
  • Page 27: Furnace Control Programming

    F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions Table 11 – Default Airflow Settings Default Airflow Settings Designated Airflow Settings Unit Size High Heating Low Heating High Cooling Low Cooling High Heating Low Heating...
  • Page 28 F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions Table 13 – Main Menu Options Display Menu Item Current System Status , ... Displays the current furnace operating mode or active fault code. Faults code menu stores the 7 latest faults in memory. If no faults, None (...
  • Page 29: Service Label

    F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions A221509 Fig. 45 – 3 Digit Display Flow Chart SERVICE LABEL A221515 Fig. 46 – Service Label Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
  • Page 30: Start-Up, Adjustment, And Safety Check

    F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions START-UP, ADJUSTMENT, AND SAFETY 1. Purge gas lines after all connections have been made. CHECK 2. Check gas lines for leaks. GENERAL WARNING WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury, or death.
  • Page 31: Wiring Diagram

    F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions WIRING DIAGRAM A221517 Fig. 47 – Wiring Diagram ADJUSTMENTS plate. For installations above 2000 Ft. (610 M), multiply the input on the rating plate by the de-rate multiplier in...
  • Page 32: Rate

    F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions c. Connect a water column manometer or similar device to manifold pressure tap. d. Turn gas valve ON/OFF switch to ON. e. On the 3 digit display, navigate to (Htt) and select (2st) to lock furnace in low-heat operation.
  • Page 33 F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions Table 16 – Gas Rate (CU ft./hr) CAUTION SIZE OF TEST SIZE OF TEST DIAL DIAL SECONDS G SECONDS FURNACE DAMAGE HAZARD FOR 1 REV FOR 1 REV...
  • Page 34: Btuh For Low-Heat Per Burner, Derated 4 Percent For Each 1000 Ft.(305 M) Above Sea Level)

    F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions Table 17 – Orifice Size and Manifold Pressure (in. w.c.) for Gas Input Rate (Tabulated Data Based on 22,000 BTUh High-Heat/14,500 BTUh for Low-Heat per Burner, Derated 4 Percent for Each 1000 Ft.(305 M) Above Sea Level) SPECIFIC GRAVITY OF NATURAL GAS AVG.
  • Page 35: Btuh For Low-Heat Per Burner, Derated 4 Percent For Each 1000 Ft.(305 M) Above Sea Level)

    F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions Table 17 – Orifice Size and Manifold Pressure (in. w.c.) for Gas Input Rate (Tabulated Data Based on 22,000 BTUh High-Heat/14,500 BTUh for Low-Heat per Burner, Derated 4 Percent for Each 1000 Ft.(305 M) Above Sea Level) (Continued) SPECIFIC GRAVITY OF NATURAL GAS AVG.
  • Page 36 F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions Table 18 – Orifice Size and Manifold Pressure (in. w.c.) for Gas Input Rate (Tabulated Data Based on 21,000 BTUh High-Heat/14,500 BTUh for Low-Heat per Burner, Derated 4 Percent for Each 1000 Ft.(305 M) Above Sea Level) (Continued) SPECIFIC GRAVITY OF NATURAL GAS AVG.
  • Page 37 F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions 4. Refer to the FURNACE CONTROL PROGRAMMING AND CAUTION NAVIGATION section of this manual for instructions on adjusting the blower speed. FURNACE DAMAGE HAZARD 5. Replace blower door.
  • Page 38: Service And Maintenance Procedures

    F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions e. Furnace should cycle off within 2 minutes. If gas does not shut CAUTION off within 2 minutes, determine reason draft safeguard switch did not function properly and correct condition.
  • Page 39: Care And Maintenance

    F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions at the sight glass in blower access door. The furnace control LED is WARNING either ON continuously, rapid flashing, or a code composed of 2 digits.
  • Page 40 F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions Blower Motor and Wheel Maintenance 1. Turn off electrical supply to furnace before removing filter access door. The following steps should be performed by a qualified service agency.
  • Page 41 F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions 14. Reinstall 2 screws securing blower assembly to blower deck. f. Hot surface igniter. g. Flame-sensing electrode. 15. Reconnect blower leads to furnace control. Refer to furnace wiring diagram, and connect thermostat leads if previously disconnected.
  • Page 42: Sequence Of Operation

    F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions WARNING FIRE OR EXPLOSION HAZARD Failure to follow this warning could result in personal injury, death, and/or property damage. Never purge a gas line into a combustion chamber. Never test for gas leaks with an open flame.
  • Page 43 F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions control CPU will begin a 15-second prepurge period, and will open de-energizing the humidifier terminal HUM. The continue to run the inducer motor IDM at high-speed.
  • Page 44 F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions the furnace control CPU can turn on the air conditioning relay ACR to a. Low cooling-When the R-to-G-and-Y1 circuit is closed and energize the Y/Y2 terminal and switch the outdoor unit to high-cooling.
  • Page 45 F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions the main burners ignite then shut OFF and remain OFF for 25 seconds before coming back on at heating airflow. When the W/W1 input signal disappears, the furnace control begins a normal inducer post-purge period while changing the blower airflow.
  • Page 46: Troubleshooting Guide

    F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions TROUBLESHOOTING GUIDE A221563 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
  • Page 47 F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions A220342 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
  • Page 48 F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions A221565 Fig. 52 – Troubleshooting Guide Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
  • Page 49: Gas Furnace Checklist

    F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions GAS FURNACE CHECKLIST GAS FURNACE CHECKLIST Installation Date: ____________________________ Equipment Model Furnace Thermostat Humidifier Serial # Indoor Coil Outdoor Unit Furnace Location_____________________________ Installed altitude __________________ Furnace Orientation:...
  • Page 50: Parts Replacement Information Guide

    F80VTL & G80VTL (Major Series B): Installation, Start-up, Operating and Service and Maintenance Instructions PARTS REPLACEMENT INFORMATION GUIDE CASING GROUP GAS CONTROL GROUP Outer door Manifold Blower door Burner assembly Top filler plate Orifice Bottom filler plate Flame sensor Bottom enclosure...