Cooling Operation
30 English
Cool storage mode
It is a cooling operation mode to cool the indoor area by
ice that is stored in the cool storage tank.
Select
Group/
Module
NOTE
• The water outlet temperature range is 5 ~ 25 °C
(41 ~ 77 °F), and you can adjust the set temperature
by pressing
button. However, if you set the low
temperature function of DVM CHILLER, the temperature
range will be -10 ~ 25 °C(14 ~ 77 °F).
• You must set the cool storage mode in the installation
service mode to use it. Contact a service center.
– When using the cool storage mode, you must use anti-
freeze as circulating water.
Select Cool
Storage