Section 5. Refrigerant Line Considerations

5.1 Refrigerant Line and Service Valve Connection Sizes
5.2 Factory Charge
The outdoor condensing units are factory charged with the system charge required for the outdoor condensing
unit, ten (10) feet of tested connecting line, and the smallest rated indoor evaporative coil match. Always verify
proper system charge via subcooling (TXV/EEV) or superheat (fixed orifice) per the unit nameplate.
5.3 Required Refrigerant Line Length
Determine required line length and lift. You will
need this later in STEP 2 of Section 14.
Total Line Length = __________ Ft.
Total Vertical Change (lift) = __________ Ft.
5.4 Refrigerant Line Insulation
Important: The Vapor Line must always be
insulated. DO NOT allow the Liquid Line and
Vapor Line to come in direct (metal to metal)
contact.
8
Line Sizes
Vapor
Model
Line
A4HP4017D
3/4
A4HP4018D
3/4
A4HP4024D
3/4
A4HP4030D
3/4
A4HP4036D
7/8
A4HP4042D
7/8
A4HP4048D
7/8
A4HP4060D
7/8
Table 5.1
Service Valve Connection Sizes
Liquid
Vapor Line
Line
Connection
3/8
3/4
3/8
3/4
3/8
3/4
3/8
3/4
3/8
7/8
3/8
7/8
3/8
7/8
3/8
7/8
Liquid Line
Liquid Line
Connection
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
Line Length
Vapor Line
Insulation
88-A4HP4001-1F-EN