Electrical Characteristics - Fujitsu ASYG24KMTA Design & Technical Manual

Hide thumbs Also See for ASYG24KMTA:
Table of Contents

Advertisement

10. Electrical characteristics

Model name
Voltage
Power
supply
Frequency
Max operating current *1
Starting current
Circuit breaker current
Wiring
Power cable
spec.
Cross-sectional area
Connection
*2
cable *3
Limited wiring length
*1: Maximum operating current is the total current of the indoor unit and the outdoor unit.
*2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005. As
the regulations of wire size and circuit breaker differ in each country or region, select appropriate de-
vices complied to the regional standard.
*3: Limit voltage drop to less than 2%. If voltage drop is 2% or more, increase cable conductor size.
AOYG18KMTA
V
Hz
A
13.5
A
7.0
A
16
2
mm
2
mm
m
26
- 53 -
AOYG24KMTA
230 ~
50
16.0
8.6
20
2.5
1.5—2.5
31
10. Electrical characteristics

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Asyg18kmtaAsyg18kmtbAsyg24kmtbAoyg18kmtaAoyg24kmta