BSR-8020/WP Waterproof Addressable input-output unit
OPERATION VOLTAGE
QUIESCENT CONSUMPTION
ALARM CONSUMPTION
QUIESCENT CONSUMPTION WHEN USED AS A CONVENTIONAL DEVICE DRIVER
ALARM CONSUMPTION WHEN USED AS A CONVENTIONAL DEVICE DRIVER
EXTERNAL POWER SUPPLY
INSTALLATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTIONAL MATERIAL
DIMENSIONS
WEIGHT
GUARANTEE
GENERAL
The input-output unit is recognized and programmed by the BSR-2100 panel. This device is used in order that
non-addressable devices that have a free relay contact (such as fire alarm panels, flow switches and
conventional detectors) to be connected on the loop. The input unit is fully monitored and has the capability to
send to the panel, with a suitable connection, three states: quiescent, fault, alarm.
The output unit contains a fully programmable by the panel relay with a rating of (30V/1A).
The red LED which blinks periodically in the quiescent state is a power and good operation indication. The
LED lights and remains lit when the specific input unit issues an alarm to the panel. The LED remains also lit
when the sirens are deactivated from the panel in order to indicate the precise point where the alarm
originated from. The Led is turned OFF after a panel reset. Each device must have an address, that is
recognized by the panel. It is not allowed for two devices on the same loop to have the same address. Page 4
contains the full table that shows the addresses and the setting with the dip-switches. Up to 127 units can
connected to each panel.
INSTALLATION (Notice!!! The mounting accessories are included).
1. Unfasten the front cover screws and remove the cover.
2. Locate the mounting holes and use the supplied accessories to mount the unit on the required position.
3. Pass the cables through the cable glands and make the required connections.
4. Notice!! If an additional entry hole is required then remove the break-out plastic and install the supplied
cable gland.
5. Set the address on the dip-switch (page 4 and 5).
6. Reinstall the front cover and fasten the screws that were removed in step 1.
Indicator LED
4
Page 1 from 9
TECHNICAL CHARACTERISTICS
Thank you for your trust in our products
Olympia Electronics - European manufacturer
1
1.3mA (with activated LED)
2
3
5
3
2
21-28V
0.7mA
5.6mA
30mA
21-28V
For internal use only
IP65
EN 54-18
o
-10 to 60 C
Up to 95%
ABS/PC
155x80x43mm
170gr.
2 years
921802002_09_005
ON
OFF

Advertisement

loading

Summary of Contents for olympia electronics BSR-8020/WP

  • Page 1 BSR-8020/WP Waterproof Addressable input-output unit TECHNICAL CHARACTERISTICS OPERATION VOLTAGE 21-28V QUIESCENT CONSUMPTION 0.7mA ALARM CONSUMPTION 1.3mA (with activated LED) QUIESCENT CONSUMPTION WHEN USED AS A CONVENTIONAL DEVICE DRIVER 5.6mA ALARM CONSUMPTION WHEN USED AS A CONVENTIONAL DEVICE DRIVER 30mA 21-28V...
  • Page 2: Operation

    LED is turned OFF after a panel reset. In this operation we have increased consumption and cannot connect more than 7 BSR-8020/WP on each loop. In this function the terminal resistor is 10kΩ and the alarm resistor is 1kΩ .
  • Page 3 Input connection terminals. The input is fully monitored and has by default a (56kΩ) resistor. On the 24V IN terminal you can connect an external power supply if the function conventional detector driving unit with external power supply is selected. Relay connection terminals (NO, C, NC) Address select dip-switch (1-7)
  • Page 4 Dip-switch Dip-switch Dip-switch Dip-switch Address Address Address Address setting setting setting setting Page 4 from 9 921802002_09_005...
  • Page 5 “ DISABLEMENT ” is shown on the panel. The dip-switch 8 of the BSR-8020/WP must be in the ON position. It can be used in a fire extinguishing system.
  • Page 6 BS-685 BS-685 BS-686 BS-686 Loop 10kΩ Connecting gas detectors Connecting a BSR-8020/WP with detectors ΒS-685 or ΒS-686. The auxiliary relay is used so as to interrupt the power to the detectors after a panel reset. Page 6 from 9 921802002_09_005...
  • Page 7 Loop 10kΩ Connecting a BSR-8020/WP with conventional detectors. A 10kΩ terminal resistor must be connected on the last detector. The maximum number of detectors per unit is 10. An external LED BS-572 can be connected on one of the detectors. With the dip-switch 8 we can set if during an alarm the zones power will be interrupted or not.
  • Page 8 4.7kΩ Connecting a BSR-8020/WP to conventional detectors. A 4.7kΩ resistor must be installed on the last detector. The maximum number of detectors per device is 40 conventional detectors of olympia electronics. According to EN 54 the maximum number of detectors per zone is 32 devices.
  • Page 9 Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the buyer the transportation cost.