PRESSURES
Refrigerant Suction
Refrigerant Discharge
Verify Refrigerant Charge using Charging Charts.
GENERAL
Economizer minimum vent and changeover settings to job requirements (if equipped).
Verify smoke detector unit shutdown by utilizing magnet test.
IV. PERFECT HUMIDITY™ SYSTEM START-UP
STEPS
1.
Check UCB (Unit Control Board) for jumper 1, 2, 3 (Jumper 1, 2, 3 must be cut and open).
2.
Open humidistat contacts.
3.
Start unit In cooling (Close Y1).
OBSERVE AND RECORD
a. Suction pressure
b. Discharge pressure
c. Entering air temperature
d. Liquid line temperature at outlet or reheat coil
e. Confirm correct rotation for compressor.
f. Check for correct ramp-up of outdoor fan motor as condenser coil warms.
4.
Switch unit to high-latent mode (sub-cooler) by closing humidistat with Y1 closed.
5.
Check unit charge per charging chart.
OBSERVE
a. Reduction in suction pressure (5 to 7 psi expected).
b. Discharge pressure unchanged.
c. Liquid temperature drops to 50 to 55°F range.
d. LSV solenoid energized (valve closes).
6.
Switch unit to dehumid (reheat) by opening Y1.
OBSERVE
a. Suction pressure increases to normal cooling level.
b. Discharge pressure decreases (35 to 50 psi). (Limited by head pressure control.)
c. Liquid temperature returns to normal cooling level.
d. LSV solenoid energized (valve closes).
e. DSV solenoid energized, valve opens.
7.
With unit in dehumid mode close W1 compressor and outdoor fan stop; LSV and DSV solenoids de-energized.
8.
Open W1 restore unit to dehumid mode.
9.
Open field-installed humidistat input compressor and outdoor fan stop; LSV and DSV solenoids de-energized.
10. Restore set points for thermostat and humidistat.
© 2023 Carrier
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
_____________ PSIG
_____________ PSIG
(Y/N) _____
Cat. No. 04-53559018-01
Printed in U.S.A.
Edition Date: 7-23
(Y/N) _____
(Y/N) _____
(Y/N) _____
(Y/N) _____
(Y/N) _____
______________ PSIG
______________ PSIG
______________ ° F
______________ ° F
(Y/N) _____
(Y/N) _____
(Y/N) _____
(Y/N) _____
(Y/N) _____
(Y/N) _____
(Y/N) _____
(Y/N) _____
(Y/N) _____
(Y/N) _____
(Y/N) _____
(Y/N) _____
(Y/N) _____
Form No. SM559K-4-7-02
CL-2
Replaces: SM559K-4-7-01