Section 4
Analog and binary signal transfer for line differential protection
IEC10000071 V1 EN-US
Figure 46:
4.8.2

Configuration of binary inputs and outputs

4.8.2.1

Configuration of binary inputs and outputs via ACT

LDCM hardware channels can be connected via ACT by right-clicking on the chosen connection
point, and then selecting Connect /Hardware Channel (see Figure 47).
IEC10000241 V1 EN-US
Figure 47:
The following can be done in the Hardware Channel Allocation dialog:
Hardware Module selection
Hardware Channel selection
User Defined Name for the channel
46
Setting example with one communication channel for binary transfer
Signals are available in the Signal Matrix Tool (SMT) and as hardware channels in the
Application Configuration Tool (ACT).
Configuration of binary inputs and outputs via ACT
If an installed LDCM is not used, it should be removed or set to binary mode without any
connections, or the ChannelMode parameter should be set to Blocked. Otherwise parallel
LDCMs may get blocked.