Keep it in a safe place. Review the drawings and illustrations contained in this manual before proceeding. If there are any questions regarding the safe installation or operation of this product, contact Alpha Technologies or the nearest Alpha representative. 1.1 Safety Symbols To reduce the risk of injury or death, and to ensure the continued safe operation of this product, the following sym- bols have been placed throughout this manual.
1.3 Electrical Safety WARNING! Hazardous voltages are present at the input of power systems. The DC output from rec- tifiers and batteries, though not dangerous in voltage, has a high short-circuit current capacity that may cause severe burns and electrical arcing. Before working with any live battery or power system, follow these precautions: a.
2. Product Overview 2.1 Scope of the Manual This instruction manual explains the installation and interconnection of Alpha Technologies’ LPR12-150-IP68 and LPR48-150-IP68 converter system. To aid with installation, frequent reference is made to the drawings located at the rear of the manual.
2.4 Product Features Output Power Each of the two isolated converters on each LPRxx-150-IP68 module has a maximum output capacity of 75W (for a total capacity of 150W per module). The power output is a function of the input voltage into each converter. Proper network engineering and copper pair sizing is a requirement for meeting the power demand of the load.
3. Product Specifications Electrical Input voltage: 200 to 380Vdc (+/- 100 to +/- 190Vdc) Number of Inputs: Input Current per feed: 245mA max LPR12-150-IP68: 12 to 14Vdc Output voltage: LPR48-150-IP68: -54 to -56Vdc up to 150W (the power available from the unit depends on the distance from the up- Power: converter and wire gauge of the twisted copper pairs) 12.5A (12V)at full rated load of 150W (de-rates with input voltage)
4. Pre-installation Requirements 4.1 Effective Capacitance At the time of installation, carry out a system assessment to ensure that the effective capacitance of the total system, including the capacitance from the output of the up-converter (front-end), does not exceed 11μF (Line to Earth) and 40μF (Line to Line).
If the original container is unavailable, make sure that the product is packed with at least three inches of shock-absorbing material to prevent shipping damage. Alpha Technologies is not responsible for damage caused by improper packaging of returned products. 5.2 Check for Damage Before unpacking the product, note any damage to the shipping container.
6. Installation This chapter is provided for qualified personnel to install the product, which shall be mounted in the most non extreme environment. The installer should follow all applicable local rules and regulations for electrical and battery installations; e.g., CSA, UL, CEC, NEC, OSHA, and local fire codes. 6.1 Safety Precautions WARNING! This system is designed to be installed in a restricted access location that is inacces-...
7. Wiring DO NOT SCALE DRAWING WARNING! 5.5 0.22 TH 240.0 9.45 For safety reasons, ensure the shelf is properly bonded to the enclosure’s ground grid. Input voltage shall meet UL60950-21 RFT-V requirements. DO NOT CONNECT TO RFT-C CIRCUITS. Chassis must be permanently grounded. -48V return (RTN) shall be earthed.
SCALE: 1 : 1 0120048-J0 Rev D UNLESS OTHERWISE SPECIFIED THESE DESIGNS AND SPECIFICATIONS ARE DIM ARE IN MM CONFIDENTIAL, REMAIN THE PROPERTY OF ALPHA TECHNOLOGIES LTD., AND SHALL NOT BE COPIED OR USED WITHOUT ITS WRITTEN CONSENT X.XX 0.25...
7.2 LPR Cable Kit The LPR cable kit included provides a set of two, 2m (6ft) long cables each with one cut cable end, and one end pre-terminated with an LPR mating connector. The kit contains: • Input cable • Output/Alarm cable 7.2.1 DC Input DC Input cable use: 4x #22AWG.
7.2.2 DC Output/Alarm DC Output/Alarm cable use: 4x #14AWG. Use the following mating cable assembly for DC output connections. Crimp with Anderson Power Products (APP) tool (PM1000G1). Figure 8 — Anderson Power Products (APP) tool (PM100G1). Output Wire Color Circuit Designation LPR48-150-IP68 LPR12-150-IP68 Output...
8. Initial Start Up 1. Remove customer-supplied 5-pin protectors (if available) from power-pairs termination block and disconnect the output –48V cable. 2. Verify by both measurement and observation that the chassis of the system is bonded to ground. Connect module input cable to the host system 4.
9. Warranty Statement and Service Information 9.1 Technical Support In Canada and the USA, call toll free 1-888-462-7487. Customers outside Canada and the USA, call +1-604-436-5547. 9.2 Warranty Statement For full information details review Alpha's online Warranty Statement at www.alpha.ca/support. 9.3 Product Warranty Alpha warrants that for a period of two (2) years from the date of shipment its products shall be free from defects under normal authorized use consistent with the product specifications and Alpha’s instructions, the terms of the...
10. Acronyms and Definitions Alternating current American wire gauge Canadian Electrical Code Circular mil area Canadian Standards Association Direct current Light emitting diode Line Powering Remote Normally closed National Electrical Code (for the USA) Normally open OSHA Occupational Safety & Health Administration Over voltage protection Rack unit (1.75”) Underwriters Laboratories...
11. Certification About CSA and NRTL CSA (Canadian Standards Association also known as CSA International) was established in 1919 as an independent testing laboratory in Canada. CSA received its recognition as an NRTL (Nationally Recognized Testing Laboratory) in 1992 from OSHA (Occupational Safety and Health Administration) in the United States of America (Docket No.