Encoder input The interface board must be installed in the external option enclosure outside the drive. About this manual The purpose of this manual is to provide you with the information how to install and set up your SV9000 ® ®...
LonTalk protocol. Interoperable nodes use Standard Network Variable Types (SNVT) for communicating over the network. The definition of ® an SNVT includes units, a range, and an increment. SV9000 L uses only Standard ORKS Network Variable Types as data types.
In a doubly terminated bus topology, two terminations are required, one at each end of the bus. The SV9000 SV9NCLW option board is equipped with termination resistors, which can be selected by jumper X6. If the jumper is in the ‘ST’ position single termination is selected and if it is in ‘DT’ double termination is selected.
Option Board is located under drive’s cover in normal use, the service button operation can ORKS be done by changing the value of a service button parameter from 0 to 1 or vice versa on the SV9000 operating panel. The location of the service button parameter depends on the used SV9000 application.
Option Board manual Page ORKS _________________________________________________________________________________________ INSTALLATION Before starting the installation, carefully read the safety instructions in the " SV9000 Drive User's ® Manual" chapter “SAFETY”. Check that you have recieved all the L kit parts: Repeater board ORKS ®...
Page 9
® SV9000 Option Board manual Page ORKS _________________________________________________________________________________________ Figure 3-1. Repeater board on mounting board installed on top of the control board _________________________________________________________________________________________ Cutler-Hammer...
® SV9000 Option Board manual Page ORKS _________________________________________________________________________________________ CONNECTIONS Board layout Terminals: I/O - terminals thermistor input ® network ORKS service power ® Figure 4-1. L option board ORKS Diagnostic LED: power Supply Voltage, Green. Power led is active if the interface board has supply voltage.
Figure 4-1. Control connections NOTE! thermistor input(terminals 327 and 328) must be shorted if not used. READY = ON, when the utility voltage has been applied and the SV9000 is ready to operate = ON, when the motor is running...
SV9000 CX Option Board manual Page ORKS _________________________________________________________________________________________ COMMISSIONING First read how to commission the drive in the SV9000 Drive User's Manual (Chapter 8.) ® Commissioning of the L option board: ORKS 1. Check that Fieldbus Application is selected. - Parameter P0.1 = 0 (Fieldbus Appl) 2.
0 after the fault has been reset. nviMinFreq Defines the minimum frequency for SV9000. If the value is changed via the network it is not saved in the drive’s non-volatile memory, unless bit 0 in nciEeprSave has been set to 1.
1 in nciEeprSave has been set to 1. nviAccelTim Defines the acceleration time for SV9000. If the value is changed via the network it is not saved in the drive’s non-volatile memory, unless bit 2 in nciEeprSave has been set to 1.
Page 15
Table 6-2 Status word bits nvoActFault This network output variable’s value is the SV9000’s active fault code. If the value is 0 the drive has no fault. See the fault code list in the SV9000 Drive User’s Manual for identifying the faults.
This network configuration variable is a bit mask, which defines if some of the network input variables are written to SV9000’s non-volatile memory, when changed from network. If a bit is set to 1, the corresponding variable will be saved.