Environmental
Air Filtration
NOTE: Applies to data center environments
only. Air filtration requirements do not
apply to IT equipment designed to be used
outside a data center, in environments such
as an office or factory floor.
Conductive Dust
NOTE: Applies to data center and non-data
center environments.
Corrosive Dust
NOTE: Applies to data center and non-data
center environments.
Gaseous Contamination
NOTE: Maximum corrosive contaminant levels measured at ≤50% relative humidity.
Copper Coupon Corrosion Rate
Silver Coupon Corrosion Rate
108
Data center air filtration as defined by ISO Class 8
per ISO 14644-1 with a 95 percent upper
confidence limit.
Air must be free from conductive dust, zinc
whiskers, or other conductive particles.
Air must be free from corrosive dust.
Residual dust present in the air must have a
deliquescent point less than 60 percent
relative humidity.
<300 Å/month per Class G1 as defined by ANSI/
ISA71.04-1985.
<200 Å/month as defined by AHSRAE TC9.9.
Get other manuals https://www.bkmanuals.com
NOTE: Air entering the data center must
have MERV11 or MERV13 filtration.