Cv Mode Vs. Cc Mode; Programming Overvoltage Protection - Agilent Technologies 654 A Series Operating Manual

Analog programmable dc power supplies
Table of Contents

Advertisement

n Press
key
.
n The display will return to the meter mode and indicate up to 1.3000 amperes, depending upon the load.
Now raise the current by pressing
a specific increment (depending on the current resolution) each time you press the key and increases rapidly as you hold
down the key. To lower the current, press
Try to program a current greater than the IMAX for your supply. Note that the display shows OUT OF RANGE.

CV Mode vs. CC Mode

Once you program a voltage (V
depending on the resistance of the load (R
voltage maintained at V
. The output current will be at some value below Is as determined by V
s
For an Agilent 6552A supply, I
amperes at 20 volts, the supply will operate in the CV mode for all resistances >0.8 ohms. This represents the operating
resistance shown as R
= C in Figure 5-2. The supply will vary the output current to maintain a constant voltage of 25 volts.
L
If the load resistance is <0.8 ohms, the supply will vary its output voltage to maintain a constant current output of 25
amperes. However, if you reprogram the output voltage to a lower value Vs (see Figure 5-2), then the supply will again be
able to maintain CV operation with the lesser load resistance, such as R

Programming Overvoltage Protection

Overvoltage protection guards the load against voltages that reach a specified value above the programmed output voltage.
Setting the OVP Level
Assuming that a power supply is programmed for 10 volts, you can set the OVP level to 11.5 volts as follows:
. The display will change from meter mode to indicate 0V, followed by the present OVP value.
n Press
n Press
n The display will return to the meter mode and indicate the output (10.000 volts).
again. The display will now indicate 0V 11. 500.
n Press
n Press
to return to the meter mode.
Checking OVP Operation
Assuming the above operating conditions, trip the OVP circuit as follows:
Raise the output voltage close to the trip point, such as 11.0.
Gradually increase the output voltage by pressing
voltage to drop to zero and the Prot annunciator to go on.
There now is no power supply output due to an overvoltage condition.
To verify this, press
58
Front Panel Operation
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
. If you discover a mistake before pressing
(or rotating the Current control clockwise). Note that the current increases by
rotate the Current control counterclockwise.
) and a current (I
), the power supply will try to maintain itself in either CV or CC mode,
s
s
). If the load demands less current than I
L
= 25.594 amperes and V
MAX
.
and observe that the display indicates 0V.
, erase the incorrect value with the backspace
, operation will be in CV mode with the
s
= 20.475 volts. If you program the output for <≤25
MAX
=B in Figure 5-2.
L
until the OVP circuit trips. This will cause the output
÷ R
s
L.

Advertisement

Table of Contents
loading

Table of Contents