OM11 - EPI
DeviceNet interface
2
Installation & Maintenance Instructions
7.2 DeviceNet MACID configuration
The DeviceNet interface module allows MACID setting both for manual configuration as for software
configuration by means of two ten-position BCD rotary switches as indicated in the figure.
The current setting is read in decimal representation:
MSB_ADD specifies the ten (1x, 2x, 3x, ...); LSB_ADD specifies the unit (x1, x2, x3, ...).

Manual configuration

When BCD rotary switches specify a valid DeviceNet MACID, i.e. a value from 00 to 63, the module
considers this value as the device MACID.

Software configuration

If the switches specify an invalid DeviceNet MACID, i.e. a value greater than 63, the module uses the
value stored in non-volatile memory and is ready for software configuration of MACID via specific
communication message.
Configuration procedure
To change the current value of the BCD rotary switches to set a different MACID, the user shall
follow this procedure:
• Move the dip switch ENA_CFG to the ON position: the ON_CFG LED is activated to indicate that
the actuator has entered Configuration Mode
• Set the new MACID via the rotary switches MSB_ADD and LSB_ADD.
E.g.: to set MACID = 28:
MSB_ADD. on position 2
LSB_ADD on position 8
• Press the pushbutton ENTER to confirm the new set: if the new MACID is correct the CFG_OK
LED turns ON
• Move the dip switch ENA_CFG on the OFF position to exit from Configuration Mode: the
DeviceNet interface module is reset to activate the new configuration.
7.3 DeviceNet communication speed configuration
The DeviceNet interface module allows also Date Rate setting via manual configuration (or software
configuration) by means of one ten-position BCD rotary switch DATA_RATE as indicated in the
figure.
Manual configuration
When BCD rotary switch specify one of the following valid DeviceNet Data Rate:
0: 125 Kbps
1: 250 Kbps
2: 500 Kbps
the module will work at the selected data rate.
Software configuration
If the switches specify any other invalid DeviceNet Data Rate, i.e. a value from 4 to 9, the module
uses the value stored in non-volatile memory and is ready for software configuration of Data Rate
via a specific communication message.
Configuration procedure
To change the current value of the BCD rotary switch to set a different Data Rate, the user shall
follow this procedure:
• Move the dip switch ENA_CFG on the ON position: the ON_CFG LED turns ON to indicate that
the actuator is entered in Configuration Mode
• Set the new Data Rate on the rotary switches DATA_.
• Press the pushbutton ENTER to confirm the new set: if the new MACID is correct the CFG_OK
LED turns ON
• Move the dip switch ENA_CFG on the OFF position to exit from Configuration Mode: the
DeviceNet interface module is reset to activate the new setting.
8. Bluetooth communication module
The OM11 module is provided with integrated Bluetooth module. In www.biffi.it you can download
A-Manager program to modify each settings by integrated Bluetooth module. After installation of
A-Manager program, please clic on 'Operations'button and then clic on 'Bluetooth Control'button
and tick 'on'.
The features and functionalities performed with Bluetooth module are indicated in A-Manager IOM
for PDA (BIFCS-0029) and PC (BIFCS-0028).
9. DeviceNet certificate
EPI
actuators family equipped with DeviceNet interface module have passed the DeviceNet
2
Conformance Test and can be declared.
DeviceNet CONFORMANCE TESTED™
Copy of the DeviceNet certificate can be viewed at ODVA website: www.odva.org
Pentair reserves the right to change the contents without notice
MACID configuration
Communication speed configuration
page 8