ABB ACH580-01 Quick Installation And Start-Up Manual page 13

Table of Contents

Advertisement

Warning
Fault
Name
A2B3
2330
Earth leakage
A2B4
2340
Short circuit
-
3130
Input phase loss
-
3181
Wiring or earth fault
A3A1
3210
DC link overvoltage
A3A2
3220
DC link undervoltage
-
3381
Output phase loss
-
5090
STO hardware failure
A5A0
5091
Safe torque off
A7CE
6681
EFB comm loss
A7C1
7510
FBA A communication
A7AB
-
Extension I/O
configuration failure
AFF6
-
Identification run
-
FA81
Safe torque off 1
-
FA82
Safe torque off 2
Ratings, fuses and typical power cable sizes
ACH58
Nominal ratings
0-01-...
Input
Output
current
current
I
I
I
1
1
2
(480 V)
A
U
= 3-phase 230 V
n
04A7-2
4.7
-
4.7
06A7-2
6.7
-
6.7
07A6-2
7.6
-
7.6
012A-2
12.0
-
12.0
018A-2
16.9
-
16.9
025A-2
24.5
-
24.5
032A-2
31.2
-
31.2
047A-2
46.7
-
46.7
060A-2
60
-
60
089A-2
89
-
89
091A-2
91
-
91
115A-2
115
-
115
144A-2
144
-
144
171A-2
171
-
171
213A-2
213
-
213
276A-2
276
-
276
U
=3-phase 400 V or 480 V
n
02A7-4
2.6
2.1
2.6
03A4-4
3.3
3.0
3.3
04A1-4
4.0
3.4
4.0
05A7-4
5.6
4.8
5.6
07A3-4
7.2
6.0
7.2
09A5-4
9.4
7.6
9.4
12A7-4
12.6
11.0
12.6
018A-4
17.0
14.0
17.0
026A-4
25.0
21.0
25.0
033A-4
32.0
27.0
32.0
039A-4
38.0
34.0
38.0
046A-4
45.0
40.0 45.0 44.0
062A-4
62
52
62
062A-4
62
52
62
073A-4
73
65
73
073A-4
73
65
73
089A-4
89
77
89
088A-4
88
77
88
106A-4
106
96
106
145A-4
145
124
145
169A-4
169
156
169
206A-4
206
180
206
246A-4
246
240
246
293A-4
293
260
293
363A-4
363
361
363
430A-4
430
414
430
Description
A load unbalance that is typically caused by an earth fault in the motor or the
motor cable.
There is a short-circuit in the motor or the motor cable.
The intermediate DC circuit voltage oscillates due to missing input power
line phase.
Incorrect input and motor cable connection.
Intermediate DC circuit voltage is too high.
Intermediate DC circuit voltage is too low.
All three phases are not connected to the motor.
STO hardware diagnostics has detected hardware failure. Contact ABB.
The Safe torque off (STO) function is active.
Break in embedded fieldbus communication.
Communication lost between drive (or PLC) and fieldbus adapter.
The installed C-type module is not the same as configured, or there is an
error in the communication between the drive and module.
The motor ID run occurs at the next start.
The Safe torque off circuit 1 is broken.
The Safe torque off circuit 2 is broken.
Motor
gG fuse (IEC
1)
60269)
power
I
P
ABB type
Ld
n /
P
(480 V)
Ld (480 V)
A
kW
hp
-
0.75
1.0
OFAF000H25
-
1.1
1.5
OFAF000H25
-
1.5
2.0
OFAF000H25
-
3.0
3.0
OFAF000H25
-
4.0
5.0
OFAF000H25
-
5.5
7.5
OFAF000H40
-
7.5
10.0
OFAF000H40
-
11.0
15.0
OFAF000H63
-
15
20
OFAF000H63
-
22
30
OFAF00H125
-
22
30
OFAF00H125
-
30
40
OFAF00H125
-
37
50
OFAF0H200
-
45
60
OFAF0H250
-
55
75
OFAF1H315
-
75
100
OFAF2H400
2.1
0.75
1.0
OFAF000H4
3.0
1.1
1.5
OFAF000H6
3.5
1.5
2.0
OFAF000H6
4.8
2.2
3.0
OFAF000H10
6.0
3.0
3.0
OFAF000H10
7.6
4.0
5.0
OFAF000H16
12.0
5.5
7.5
OFAF000H16
14.0
7.5
10.0
OFAF000H25
23.0
11.0
15.0
OFAF000H32
27.0
15.0
20.0
OFAF000H40
34.0
18.5
25.0
OFAF000H50
22.0
30.0
OFAF000H63
52
30
40
OFAF000H80
52
30
40
OFAF000H80
65
37
50
OFAF000H100
65
37
50
OFAF000H100
77
45
60
OFAF000H100
77
45
60
OFAF000H100
96
55
75
OFAF00H125
124
75
100
OFAF00H160
156
90
125
OFAF0H250
180
110
150
OFAF1H315
240
132
200
OFAF1H355
260
160
250
OFAF2H425
361
200
300
OFAF2H500
414
250
350
OFAF3H630
Fuses
Typical power cable sizes,
uR/aR fuse
UL class
2) 3) 4)
(DIN 43620)
T
Bussmann type
170M1563
JJS-15
3×1.5 + 1.5
170M1563
JJS-15
3×1.5 + 1.5
170M1563
JJS-15
3×1.5 + 1.5
170M1563
JJS-15
3×1.5 + 1.5
170M1563
JJS-30
3×2.5 + 2.5
170M1565
JJS-40
3×4.0 + 4.0
170M1565
JJS-40
3×6.0 + 6.0
170M1566
JJS-80
3×10 + 10
170M1566
JJS-80
3×16 + 16
170M3815
JJS-150
3×35 + 16
170M1569
JJS-150
3×50 + 25
170M3815
JJS-150
3×50 + 25
170M3817
JJS-200
3×70 + 35
170M5809
JJS-250
3×95 + 50
170M5810
JJS-300
3×120 + 70
170M6810
JJS-400 2×(3×70 + 35)
170M1561
JJS-15
3×1.5 + 1.5
170M1561
JJS-15
3×1.5 + 1.5
170M1561
JJS-15
3×1.5 + 1.5
170M1561
JJS-15
3×1.5 + 1.5
170M1561
JJS-15
3×1.5 + 1.5
170M1561
JJS-15
3×2.5 + 2.5
170M1561
JJS-15
3×2.5 + 2.5
170M1563
JJS-30
3×2.5 + 2.5
170M1563
JJS-30
3×6 + 6
170M1565
JJS-40
3×10 + 10
170M1565
JJS-60
3×10 + 10
170M1566
JJS-60
3×10 + 10
170M1567
JJS-80
3×25 + 16
170M1567
JJS-80
3×25 + 16
170M1568
JJS-100
3×35 + 16
170M1568
JJS-100
3×35 + 16
170M1569
JJS-110
3×50 + 25
170M1569
JJS-110
3×50 + 25
170M3817
JJS-150
3×70 + 35
170M3817
JJS-200
3×95 + 50
170M5809
JJS-225
3×120 + 70
170M5810
JJS-300
3×150 + 70
170M5812
JJS-350
2×(3×70+35)
170M6812D
JJS-400
2×(3×95+50)
170M6814D
JJS-500 2×(3×120+70)
170M8554D JJS-600 2×(3×150+70) 2×300 MCM
Frame
Cu
size
2
mm
AWG
14
R1
14
R1
14
R1
14
R1
10
R1
8
R2
8
R2
6
R3
4
R3
2
R5
2
R4 v2
1/0
R5
3/0
R6
4/0
R7
300 MCM
R7
2×2/0
R8
14
R1
14
R1
14
R1
14
R1
14
R1
14
R1
14
R1
12
R2
10
R2
8
R3
8
R3
6
R3
4
R4
4
R4 v2
4
R4
4
R4 v2
3
R4 v2
3
R5
1
R5
2/0
R6
3/0
R7
4/0
R7
2×1/0 or
R8
350 MCM
2×2/0
R8
2×4/0
R9
R9
13

Advertisement