Tamco AIR-IQ2 Installation Manuallines page 6

Airflow measurement damper packaged solution
Table of Contents

Advertisement

AIR-IQ2 AIRFLOW MEASUREMENT SOLUTION
FLANGED TO DUCT INSTALL TYPE
1"
1"
4"
5"
5.1" 2.4"
6"
12.5"
13.5"
Non-ducted applica�on
Ducted applica�on
Minimum distance to
trailing edge of intake louver
AIR-IQ2 shown with
sleeve and flare
T.A. Morrison & Co. Inc. | P.O. Box 157 Smiths Falls Stn Main, Ontario, Canada K7A 4T1 | 800 561 3449 | Fax: 800 668 8476 | tamcodampers.com
EBTRON, Inc. | 1663 Hwy. 701 S., Loris, SC USA 29569 | 800.2EBTRON (232.8766) | Fax: 843.756.1838 | www.ebtron.com
6
AIR-IQ2: TYPICAL TWO-SECTION HORIZONTAL BLADE DAMPER
PROBES MOUNTED PARALLEL TO BLADES
1"
Airflow
B
Minimum 4" clearance for EBTRON insertion style sensor probes and electronic
actuator. Does not include access for wiring after installation of assembly. See
9"
specific EBTRON and TAMCO series technical documentation for more information.
Jumpers will always be on the face of damper, downstream from the louver, and
will ship with all damper units that are two sections wide.
A
A + 2"
*NOTES:
A x B: = Always opening dimensions
Width = A: Always dimension parallel
to blades
Height = B: Always dimension
perpendicular to blades
INSIDE SLEEVE DIMENSIONS:
Parallel to blade = A
Perpendicular to blade = B
OUTSIDE DAMPER FRAME DIMENSIONS:
Parallel to blade = A + 2"
Perpendicular to blade = B + 2"
OUTSIDE FLARE DIMENSIONS:
Parallel to blade = A + 2"
Perpendicular to blade = B + 2"
1"
B
+
2"
4"