IFM N0531A Operating Instructions Manual
IFM N0531A Operating Instructions Manual

IFM N0531A Operating Instructions Manual

Switching amplifiers

Advertisement

Quick Links

Operating instructions
GB
Switching amplifiers
N0531A
N0532A
N0534A

Advertisement

Table of Contents
loading

Summary of Contents for IFM N0531A

  • Page 1 Operating instructions Switching amplifiers N0531A N0532A N0534A...
  • Page 2: Table Of Contents

    Contents 1 Preliminary note ..................... 3 2 Safety instructions..................3 3 Intended use ....................3 Classification................... 4 ATEX certificate ..................4 IECEx certificate ..................4 Identification.................... 4 4 Installation...................... 4 Requirements for cables and connection cables ........5 Requirements in case of use as associated equipment......5 5 Electrical connection ..................
  • Page 3: Preliminary Note

    1 Preliminary note You will find instructions, technical data, approvals and further information using the QR code on the unit / packaging or at www.ifm.com. 2 Safety instructions • The unit described is a subcomponent for integration into a system. – The system architect is responsible for the safety of the system.
  • Page 4: Classification

    The unit is an associated equipment according to IEC/EN 60079-11. The unit is not suitable for separating signals in power measurement technology. The unit transmits binary signals of NAMUR sensors or mechanical contacts from the hazardous area into the non-hazardous area. u Only use the unit within the permissible operating conditions.
  • Page 5: Requirements For Cables And Connection Cables

    The unit has the protection rating IP20 according to IEC/EN 60529. u Only install and use the unit under operating conditions that do not exceed soiling degree 2 according to IEC EN 60664-1. In case of use under operating conditions with a higher degree of soiling, the unit must be protected accordingly.
  • Page 6: Electrical Connection

    u If the unit is connected to intrinsically safe equipment, the upper limiting values of the unit must be observed. u If intrinsically safe units are connected to the intrinsically safe circuits of the corresponding equipment, the respective upper limiting values consistent with the explosion protection according to IEC/EN 60079-14 or IEC/EN 60079-25 must be observed (proof of intrinsic safety).
  • Page 7: Operating And Display Elements

    6 Operating and display elements Ι ΙΙ Ι ΙΙ 1: LED yellow Indication of the switching status output 1 / output 2; lights when the corresponding output is switched / the relay is en- ergised. 2: LED red Fault indication for input circuit 1 / input circuit 2; lights in case of wire break or short circuit in the respective input circuit.
  • Page 8: Maintenance, Repair And Disposal

    6: Selector switch S3 Setting for short circuit / wire monitoring • When proximity sensors are connected monitoring is always active. S3 must be in position I. • When mechanical switches are connected the following applies: – Monitoring active for input circuit no. 1; S3 must be in position –...

This manual is also suitable for:

N0532aN0534a