  • Page 1 HC10 Series Analog Module User Manual V1.2 2021.12...
  • Page 2: Table Of Contents

    Size and Gross Weight ..........1 Structure Description ..........2 L0303A Terminal Description ........4 L0402A Terminal Description ........5 L0800A Terminal Description ........6 Product Specifications ..........7 General Specifications ............7 Analog Input Specifications (L0303A/L0800A)....8 Analog Input Specifications (L0402A) ....... 9 Analog Output Specifications (L0303A) ......
  • Page 3 Warning • Be sure to check the terminal label carefully when wiring. • Avoid installation in places exposed to direct sunlight, moisture, or water. • Avoid installation in locations with flammable and explosive gases and liquids. • Avoid installation in areas with oily dust, fibers and metal particles.
  • Page 4: Size And Gross Weight

    Size and Gross Weight 74.5 GW: 0.25kg 74.5 GW: 0.3kg Unit: mm HC10 Series Analog Module User Manual V1.2...
  • Page 5: Structure Description

    Structure Description Input and output terminal Mounting fixing hole (M3) Extension cable DIN guideway groove (35mm) Expansion port DIN rail fixing buckle Power/run/fault indicator HC10 Series Analog Module User Manual V1.2...
  • Page 6 Structure Description (Continued) HC10 Series Analog Module User Manual V1.2...
  • Page 7: L0303A Terminal Description

    HC10-L0303A Analog Input Voltage VI1 ~ VI3 (GND) Current AI1 ~ AI3 (GND) Analog Output Voltage VO1 ~ VO3 (GND) Current AO1 ~ AO3 (GND) Size and Structure Size and structure Figure 1 HC10 Series Analog Module User Manual V1.2...
  • Page 8: L0402A Terminal Description

    L0402A Terminal Description Model HC10-L0402A Analog Input Voltage VI1 ~ VI4 (VI-) Current AI1 ~ AI4 (VI-) Analog Output Voltage VO1, VO2 (VO-) Current AO1, AO2 (VO-) Size and Structure Size and structure Figure 1 HC10 Series Analog Module User Manual V1.2...
  • Page 9: L0800A Terminal Description

    L0800A Terminal Description Model HC10-L0800A Analog Input Voltage VI1 ~ VI8 (GND) Current AI1 ~ AI8 (GND) Size and Structure Size and structure Figure 2 HC10 Series Analog Module User Manual V1.2...
  • Page 10: Product Specifications

    Environmental Run: -10 ~ +55℃ Storage: -40 ~ +70℃ Temperature Relative Humidity 5 ~ 95%, no condensation Run: <2000m Altitude Storage: 0 ~ 3000m (not less than 70kPa) Pollution Level Pollution level 2 HC10 Series Analog Module User Manual V1.2...
  • Page 11: Analog Input Specifications (L0303A/L0800A)

    Voltage: 0 ~ 10V Current: 0 ~ 20mA Resistance Voltage: 31kΩ Current: 500Ω Voltage: 0.3125mV Current: 0.625uA Resolution (10V / 32000) (20mA / 32000) Digital Input 0 ~ 32000 Comprehensive ±1% full range Accuracy HC10 Series Analog Module User Manual V1.2...
  • Page 12: Analog Input Specifications (L0402A)

    -20 ~ +20mA Resistance Voltage: 1kΩ Current: 250Ω Voltage (V): Current (mA): Resolution Full range / 32000 Full range / 32000 Digital Input -16000 ~ +16000, 0 ~ 32000 Comprehensive ±0.1% full range Accuracy HC10 Series Analog Module User Manual V1.2...
  • Page 13: Analog Output Specifications (L0303A)

    Current: 0 ~ 20mA Resistance Voltage: 2kΩ ~ 1MΩ Current: 0 ~ 500Ω Voltage: 0.3125mV Current: 0.625uA Resolution (10V / 32000) (20mA / 32000) Digital Output 0 ~ 32000 Comprehensive ±1% full range Accuracy HC10 Series Analog Module User Manual V1.2...
  • Page 14: Analog Output Specifications (L0402A)

    Resistance Voltage: 2kΩ ~ 1MΩ Current: <550Ω Voltage (V): Current (mA): Resolution Full range / 32000 Full range / 32000 Digital Output -16000 ~ +16000, 0 ~ 32000 Comprehensive ±0.1% full range Accuracy HC10 Series Analog Module User Manual V1.2...
  • Page 15: Instructions

    • Please isolate it from other power cables. • If the analog input or output is disturbed by noise, it can be connected with 0.1 ~ 0.47uF/25V capacitor or a ferrite magnetic ring. HC10 Series Analog Module User Manual V1.2...
  • Page 16 • See page 14 for instruction description. • See page 16 for the description of the module data address. • The configuration wizard function of HCStduio (programming software) can be used to configure the initial parameters of the module. HC10 Series Analog Module User Manual V1.2...
  • Page 17: Instruction Description (From, To, Rd3A)

    TO S1 S2 S3 S4 S1: Module number. S2: Module data write start address. S3: Write the data register. • When writing multiple data, write data sequentially from this address. S4: Write data length. HC10 Series Analog Module User Manual V1.2...
  • Page 18 S3: Store the analog input channel data set by S2. Note: The read value is the analog input value that refreshes the cache periodically. It is recommended to use this instruction to read the analog input. HC10 Series Analog Module User Manual V1.2...
  • Page 19: Module Data Address Description (L0303A/L0800A)

    1): 0.0 ~ 10.0V or 0.0 ~ 20.0mA, corresponding 0 ~ 32000. 2): 0 is voltage type (default), 1 is current type. Set the channel in binary, starting from Bit0. • Bit0 corresponds to AI1/VI1/AO1/VO1; • Bit1 corresponds to AI2/VI2/AO2/VO2; • And so on. HC10 Series Analog Module User Manual V1.2...
  • Page 20: Module Data Address Description (L0402A)

    AO1, AO2, VO1, VO2 Read and write 21, 22 Input filter coe cient Read and write Input range selection Read and write Output range selection Read and write Channel enable Read and write HC10 Series Analog Module User Manual V1.2...
  • Page 21 • 0: No filtering (default); • 1: The filtering e ect is the weakest; • 255: The filtering e ect is the strongest and the data is the most stable, but it may cause data lag. HC10 Series Analog Module User Manual V1.2...
  • Page 22 -16000 ~ +16000 29: Channel Enable Module Data Bit15 ~ Bit7 ~ Bit11 Bit10 Bit9 Bit8 Bit1 Bit0 Address Bit12 Bit2 AI4/ AI3/ AI2/ AI1/ AO2/ AO1/ 1 is enable (default), 0 is disable. HC10 Series Analog Module User Manual V1.2...
  • Page 23 0, 1, 2, 3, 4, 5, 6, 7. Number Module Number Mapped Address D8265 D8267 D8269 D8271 Data 0x20: L0303A, 0x21: L0808A, 0x22: L0402A Number Module Number Mapped Address D8273 D8275 D8277 D8279 Data 0x20: L0303A, 0x21: L0808A HC10 Series Analog Module User Manual V1.2...
  • Page 24 Hpmont Group Company Shenzhen Hpmont Technology Co., Ltd. Mont Korea Co., Ltd. Add: Building 28, Wangjingkeng Industry Add: Ace pyungchon tower, Park, Xili Town, Nanshan District, #811, 361 Slimin-daero, Dongan- Shenzhen, China gu, Anyang-si, Gyeonggi-Do, 14057 Tel: +86 755-26791688 Tel: +82-31-345-8181 Fax: +86 755-26558128 Email: info.kr@hpmont.com.hk...