ZEZ SILKO PFR 6 Manual

Power factor regulator

Advertisement

Quick Links

PFR 6/ PFR 12
The Controller
obtain a target programmed value.
This manual is an easy guide for the use and operation of the
PFR 6/PFR 12
Controller
manual can be downloaded from the web site of ZEZ SILKO:
www.zez-silko.cz
1.- Regulator Connection
For proper operation it's necessary to install a current transformer, CT
(normally In / 5 A), which primary must be sized according to the
maximum expected load current in the installation.
The regulator supply (C-D terminals) must be taken between two
phases and the CT should be located in the third phase. See technical
characteristics for cable sizes and required protections.
Must use an switch or automatic switch for supply the regulator
The current transformer , CT,
must
be
located
so
that
measures the whole load current
plus the correction capacitors
2.- TECHNICAL CHARACTERISTICS
Supply and V measurement input
400 VAC - standard, 110, 230, 480 VAC-on request, +15%-10%
terminals (C-D)
45-65 Hz, Connect preferably to phases L2-L3
Supply cables size and protection
Cross section 1,5mm
Current transformer (CT) , In /5 , Place preferably in phase L1
Current measurement circuit
Minimum cabling cross section 2,5mm
Current measurement margin
0,1 to 5 A (maximum overload +20%)
Accuracy of measurements
Voltage and current :1%; cosϕ : 2% ± 1 dígit
110V: 7 VA (no load) ; 8 VA(6 relays); 9,8 VA(12 relays)
230V: 7 VA (no load) ; 8 VA(6 relays); 9,6 VA(12 relays)
Power consumptions
400V: 6 VA (no load) ; 7,5 VA(6 relays); 9,5 VA(12 relays)
480V: 7,8 VA (no load) ; 8,6 VA(6 relays); 10 VA(12 relays)
Display
1 line x 3 digits x 7segments + 20 icons
Output Relay Contacts
Max. 250 VAC, 10 A, AC1
Output Relay Cabling and
Cabling cross section 1,5mm
Protection
circuit breaker (C curve) or by a 6A fuse (gl type)
Alarm Output Relay
Last relay automatically set as alarm output , if not in use
EN 61010, EN 61000-3-2, EN 61000-3-3, EN 50081-2, EN 50082-
Compliant to the following
1, EN 50082-2, EN 61000-4-2, EN 61000-4-4, EN 61000-4-8, EN
Standards
61000-4-5, EN 61000-4-11 , UL 94
Safety / Insulation
Category III , Class II, According to EN 61010-1,
Temperature limits: -20ºC a +60ºC; Relative Humidity 95%
Environment limit conditions
(without condensation). Max. Altitude: 2000m
IP51 (panel mounted)
Protection degree
IP30 (regulator box) , According to EN-60529
POWER FACTOR REGULATOR Controller
PF regulators measure cosϕ in a supply system and control the connection and disconnection of capacitors to
. For more information, the complete
S1
CT
it
S2
CAPACITORS
; 0,5 to 2A Fuses gl type
2
2
, Protection by means of a 6A
2
controller PFR 6 / PFR 12
PFR 6/ PFR 12
Standard mode: Displays cosϕ
cosϕ Indication / setting
C/K setting. See paragraph 6
Program setting. See 4.2
Delay time setting for switching on/off operations
Nr of steps setting
Setting CT phase and polarity connection
- Cursor keys (when in setting mode)
- Manual ON / OFF (push during more than 1s when in RUN mode)
- Push both to see the Nr of connected steps
SETUP KEY: Push during more than 1s to enter SETUP mode
Lagging current indication (Inductive load)
11
Leading current indication (Capacitive load)
Any manipulation or use of the equipment out of the conditions
specified by the manufacturer may put in risk the user safety. Before
any maintenance operation the equipment must be disconnected from power
supply. In case of miss operation or protection fault the equipment must be
disconnected from supply and remain out of service ensuring against any
accidental reconnection.
A B
COM
1 2
S1
S2
COM 7
Control system
FCP (Minimum number of operations)
3.- Four Quadrants Operation
PFR 6/PFR 12
The Controller
for imported or exported active power). For exported power, a negative
symbol is displayed in the cosϕ indication. Check phase connection and
setup if there is no exported energy and the indication is not correct (see 4.3,
SET-UP - phase)
Lagging / Inductive
KW -
kVAr +
Cosϕ -
180º
KW -
kVAr -
Cosϕ -
Leading/Capacitive
Exported Power
Display
3 4 5 6
C
L2
RELAY
C1..C6
RELAY
C7..C12
Sólo en
Computer
8
9 10 11 12
regulators operate in 4 quadrants (suitable
90º
Lagging / Inductive
KW +
kVAr +
Cosϕ +
KW +
kVAr -
Cosϕ +
Leading/Capacitive
-90º
Imported Power
D
POWER
SUPPLY
L3
max
12

Advertisement

loading

Summary of Contents for ZEZ SILKO PFR 6

  • Page 1 . For more information, the complete any maintenance operation the equipment must be disconnected from power manual can be downloaded from the web site of ZEZ SILKO: supply. In case of miss operation or protection fault the equipment must be www.zez-silko.cz...
  • Page 2 PFR 6 / PFR 12 4.- SETUP AND MEASUREMENTS To enter the SETUP mode, press the setup key (9), for more than 1s. If all the capacitors are disconnected, the access in immediate, otherwise a disconnection sequence starts and then accesses to setup menu. In the SETUP mode, if no key is pressed for 3 minutes, the equipment exits such mode and returns to normal operation mode.

This manual is also suitable for:

Pfr 12