Troubleshooting - GE 040324 Operator's Manual

Generator system
Table of Contents

Advertisement

Available languages

Available languages

Troubleshooting

Problem
Engine is running, but no AC output
is available.
Engine runs good at no-load but "bogs
down" when loads are connected.
Engine will not start; or starts and runs
rough.
Engine shuts down during operation.
Loss of power on circuits.
Unit will not exercise weekly.
Excessive Vibration
Odor of fuel
Utility power returns, unit does not stop
Cause
1.
Circuit breaker open or defective.
2.
Fault in generator control panel.
3.
Poor wiring connections or defective
transfer switch.
1.
Short circuit in a connected load.
2.
Generator is overloaded.
3.
Shorted generator circuit.
4.
Fuel pressure or mixture is incorrect.
5.
Kinked fuel line between regulator
and engine.
1.
15 Amp fuse missing or blown.
2.
Fuel supply turned off or depleted.
3.
Check if thermal fuse assembly is
blown.
4.
Failed battery.
5.
Clogged air filter.
1.
Fuel supply turned off or depleted.
2.
Control panel digital display shows a
fault code.
1.
Generator circuit breaker is open.
2.
Transfer switch problems.
1.
System Switch not on AUTO.
2.
Exercise timer not set.
3.
Failed battery.
4.
15 Amp fuse missing or blown.
1.
Lose mechanical fastener.
1.
Fuel leak.
1.
Blown fuses in transfer switch.
2.
5 minute minimum runtime not
lapsed.
3.
Poor wire connection or defective
controllers.
Correction
1.
Reset or replace circuit breaker.
2.
Contact local service facility.
3.
Check and repair or contact local
service facility.
1.
Disconnect shorted electrical load.
2.
Turn off one or more loads.
3.
Contact local service facility.
4.
See Gaseous Fuel System in the
installation manual.
5.
Remove kink. Replace
if necessary.
1.
Install (new) 15 Amp fuse.
See System Control Panel.
2.
Open fuel valve(s); check propane
tank.
3.
Replace thermal fuse assembly.
4.
Failed battery.
5.
Clean or replace air filter.
1.
Check fuel valves, fill
propane tank.
2.
Refer to Fault Detection System.
1.
Reset circuit breaker.
2.
See transfer switch manual.
1.
Set system switch to AUTO.
2.
Set exercise timer.
3.
Replace battery.
4.
Install (new) 15 Amp fuse.
See System Control Panel.
1.
Check and repair or contact local
service facility.
1.
Turn off manual shutoff fuel valve.
Contact local service facility.
1.
Install (new) fuses.
2.
Wait 5 minutes.
3.
Check and repair or contact local
service facility.
25